Bulletin 100S-D IEC Safety Contactors
Bulletin 100S-D IEC Safety Contactors
Product Selection
3-Pole AC-Operated Contactors
| Ie [A]
|
Switching of 3-phase motors AC-2, AC-3
|
Auxiliary contacts
|
Cat. No.Ø
|
| 60 °C
|
40 °C
|
kW (50 Hz)¬
|
Hp (60 Hz)
|
N.O.
|
N.C.T
|
| AC-3
|
AC-1
|
230V
|
400V
|
415V
|
500V
|
690V
|
1000V
|
200V
|
230V
|
460V
|
575V
|
|
|
| 95
|
160
|
25
|
50
|
50
|
55
|
90
|
45
|
25
|
30
|
60
|
75
|
2
|
2
|
100S-D95Ä22BC
|
| 110
|
160
|
32
|
55
|
55
|
63
|
100
|
55
|
40
|
40
|
75
|
100
|
2
|
2
|
100S-D110Ä22BC
|
| 140
|
250
|
45
|
75
|
75
|
80/100
|
110/132
|
75
|
40
|
50
|
100
|
125
|
2
|
2
|
100S-D140Ä22BC
|
| 180
|
250
|
55
|
90
|
100
|
90/125
|
132/160
|
90
|
50
|
60
|
150
|
150
|
2
|
2
|
100S-D180Ä22BC
|
| 210
|
350
|
63
|
110
|
110
|
150
|
200
|
110
|
60
|
75
|
150
|
200
|
2
|
2
|
100S-D210Ä22BC
|
| 250
|
350
|
80
|
132
|
150
|
160
|
250
|
133
|
75
|
100
|
200
|
250
|
2
|
2
|
100S-D250Ä22BC
|
| 300
|
450
|
90
|
160
|
160
|
200
|
300
|
160
|
100
|
125
|
250
|
300
|
2
|
2
|
100S-D300Ä22BC
|
| 420
|
540
|
132
|
220
|
250
|
300
|
425
|
220
|
150
|
175
|
350
|
400
|
2
|
2
|
100S-D420Ä22BC
|
| 630
|
800
|
200
|
355
|
355
|
450
|
500
|
—
|
200
|
250
|
500
|
600
|
2
|
2
|
100S-D630Ä22BC
|
| 860
|
1000
|
250
|
500
|
500
|
560
|
600
|
—
|
250
|
300
|
600
|
700
|
2
|
2
|
100S-D860Ä22BC
|
|
|
¬ Preferred values according to IEC 60072-1. T The N.C. contacts meet IEC 60947-4 Annex F requirements for mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit. Higher kW rating only applies to contactors with electronic coil. Ø If standard cross-stamped auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-D95Ä22BC becomes Cat. No. 100S-D95Ä22C.
|
ÄCoil voltage code—see Ä Coil Voltage Codes
Ä Coil Voltage Codes
| Conventional Coil
|
[V]
|
24
|
48
|
100
|
110
|
120
|
200
|
208
|
220 …230
|
230
|
240
|
277
|
380 …400
|
415
|
440
|
480
|
500
|
550
|
600
|
| 100S-D95…100S-D180
|
AC, 50 Hz
|
K
|
Y
|
—
|
D
|
—
|
—
|
—
|
A
|
—
|
T
|
—
|
N
|
B
|
G
|
—
|
M
|
C
|
—
|
| AC, 60 Hz
|
J
|
X
|
—
|
—
|
D
|
—
|
H
|
—
|
—
|
A
|
T
|
—
|
—
|
N
|
B
|
—
|
—
|
C
|
| 100S-D95…100S-D110
|
AC, 50/60 Hz
|
—
|
—
|
KP
|
KN
|
—
|
KG
|
—
|
KL
|
KF
|
KA
|
KT
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
|
|
Electronic Coil w/ PLC Interface§
|
[V]
|
24
|
42…64
|
100
|
110… 130
|
200
|
208…277
|
200…220
|
230…250
|
277
|
380… 415
|
380… 440
|
440… 480
|
380… 500
|
500
|
| 100S-D95…100S-D300
|
AC, 50/60 Hz
|
EJ§
|
EY
|
EP
|
ED
|
EG
|
EA
|
—
|
—
|
—
|
—
|
VN
|
—
|
EN
|
—
|
| 100S-D420
|
AC, 50/60 Hz
|
—
|
—
|
EP
|
ED
|
EG
|
EA
|
—
|
—
|
—
|
—
|
—
|
—
|
EN
|
—
|
| 100S-D630…100S-D860
|
AC, 50/60 Hz
|
—
|
—
|
EP
|
ED
|
EG
|
—
|
EG
|
EA
|
ET
|
EN
|
—
|
EB
|
—
|
EM
|
|
|
§ Signal voltage of the Cat. No. 100S-D… electronic interface Ue: 24V DC/Ie: 15 mA
Pick-up voltage: 13.0V DC…30.2V DC
Drop-out voltage: -3.0V DC…+5.0V DC
§ Not available with 100S-D300.
3-Pole DC-Operated Contactors
| Ie [A]
|
Switching of 3-phase motors AC-2, AC-3
|
Auxiliary contacts
|
Conventional Coil Cat. No.
|
Electronic Coil Cat. No.Ø
|
| 60 °C
|
40 °C
|
kW (50 Hz) ¬
|
Hp (60 Hz)
|
N.O.
|
N.C. T ¬
|
| AC-3
|
AC-1
|
230V
|
400V
|
415V
|
500V
|
690V
|
1000V
|
200V
|
230V
|
460V
|
575V
|
|
|
| 95
|
160
|
25
|
50
|
50
|
55
|
90
|
45
|
25
|
30
|
60
|
75
|
2
|
2
|
100S-D95Ä33LC
|
100S-D95Ä22BC
|
| 110
|
160
|
32
|
55
|
55
|
63
|
100
|
—
|
40
|
40
|
75
|
100
|
3
|
2/1L
|
100S-D110Ä33LC
|
100S-D110Ä22BC
|
| 140
|
250
|
45
|
75
|
75
|
80/100§
|
110/132§
|
—
|
40
|
50
|
100
|
125
|
3
|
2/1L
|
100S-D140Ä33LC
|
100S-D140Ä22BC
|
| 180
|
250
|
55
|
90
|
100
|
90/125§
|
132/160§
|
90
|
50
|
60
|
150
|
150
|
3
|
2/1L
|
100S-D180Ä33LC
|
100S-D180Ä22BC
|
| 210
|
350
|
63
|
110
|
110
|
150
|
200
|
110
|
60
|
75
|
150
|
200
|
2
|
2
|
—
|
100S-D210Ä22BC
|
| 250
|
350
|
80
|
132
|
150
|
160
|
250
|
133
|
75
|
100
|
200
|
250
|
2
|
2
|
—
|
100S-D250Ä22BC
|
| 300
|
450
|
90
|
160
|
160
|
200
|
300
|
160
|
100
|
125
|
250
|
300
|
2
|
2
|
—
|
100S-D300Ä22BC
|
| 420
|
540
|
132
|
220
|
250
|
300
|
425
|
220
|
150
|
175
|
350
|
400
|
2
|
2
|
—
|
100S-D420Ä22BC
|
| 630
|
800
|
200
|
355
|
355
|
450
|
500
|
—
|
200
|
250
|
500
|
600
|
2
|
2
|
—
|
100S-D630Ä22BC
|
| 860
|
1000
|
250
|
500
|
500
|
560
|
600
|
—
|
250
|
300
|
600
|
700
|
2
|
2
|
—
|
100S-D860Ä22BC
|
|
|
¬ Preferred values according to IEC 60072-1. T The N.C. contacts meet IEC 60947-4 Annex F requirements for mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit. For conventional DC coil only. The pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts. § Higher kW rating only applies to contactors with electronic coil. Ø If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the Cat. No. Example: Cat. No. 100S-D95Ä22BC becomes Cat. No. 100S-D95Ä22C.
|
Ä Coil Voltage Codes
| Conventional Coil
|
[V]
|
24
|
48
|
110
|
125
|
220
|
250
|
| 100S-D95…100S-D180
|
DC
|
ZJ
|
ZY
|
ZD
|
ZS
|
ZA
|
ZT
|
|
|
Electronic Coil w/ EI Interface §
|
[V]
|
24
|
48…72
|
110…130
|
200…255
|
| 100S-D95…100S-D300
|
DC
|
EZJ
|
EZY
|
EZD
|
EZA
|
| 100S-D420
|
DC
|
—
|
—
|
EZD
|
EZA
|
| 100S-D630…860
|
DC
|
—
|
—
|
ED
|
EA
|
|
|
§ Signal voltage of the cat. no. 100S-S… electronic interface Ue: 24V DC/Ie: 15 mA
Pick-up voltage: 13.0V DC…30.2V DC
Drop-out voltage: -3.0V DC…+5.0V DC