Contactors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Contactors > Bulletin 100S-D IEC Safety Contactors

Bulletin 100S-D IEC Safety Contactors

Introduction Standards Compliance and Certifications Product Selection Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications Bulletin 100S-D Approximate Dimensions
Product Selection

3-Pole AC-Operated Contactors

Ie [A] Switching of 3-phase motors AC-2, AC-3 Auxiliary contacts Cat. No.Ø 
60 °C 40 °C kW (50 Hz)¬  Hp (60 Hz) N.O. N.C.T 
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V Click to enlarge - 100M-66-3a Click to enlarge - 100S-D-80-6
95 160 25 50 50 55 90 45 25 30 60 75 2 2 100S-D95Ä22BC
110 160 32 55 55 63 100 55 40 40 75 100 2 2 100S-D110Ä22BC
140 250 45 75 75 80/100‡  110/132‡  75 40 50 100 125 2 2 100S-D140Ä22BC
180 250 55 90 100 90/125‡  132/160‡  90 50 60 150 150 2 2 100S-D180Ä22BC
210 350 63 110 110 150 200 110 60 75 150 200 2 2 100S-D210Ä22BC
250 350 80 132 150 160 250 133 75 100 200 250 2 2 100S-D250Ä22BC
300 450 90 160 160 200 300 160 100 125 250 300 2 2 100S-D300Ä22BC
420 540 132 220 250 300 425 220 150 175 350 400 2 2 100S-D420Ä22BC
630 800 200 355 355 450 500 200 250 500 600 2 2 100S-D630Ä22BC
860 1000 250 500 500 560 600 250 300 600 700 2 2 100S-D860Ä22BC
  
¬ Preferred values according to IEC 60072-1.
T The N.C. contacts meet IEC 60947-4 Annex F requirements for mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit.
‡ Higher kW rating only applies to contactors with electronic coil.
Ø If standard cross-stamped auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-D95Ä22BC becomes Cat. No. 100S-D95Ä22C.

ÄCoil voltage code—see Ä Coil Voltage Codes


Ä Coil Voltage Codes

Conventional Coil [V] 24 48 100 110 120 200 208 220
…230
230 240 277 380
…400
415 440 480 500 550 600
100S-D95…100S-D180 AC, 50 Hz K Y D A T N B G M C
AC, 60 Hz J X D H A T N B C
100S-D95…100S-D110 AC, 50/60 Hz KP KN KG KL KF KA KT
  

Electronic Coil
w/ PLC Interface§ 
[V] 24 42…64 100 110…
130
200 208…277 200…220 230…250 277 380…
415
380…
440
440…
480
380…
500
500
100S-D95…100S-D300 AC, 50/60 Hz EJ§  EY EP ED EG EA VN EN
100S-D420 AC, 50/60 Hz EP ED EG EA EN
100S-D630…100S-D860 AC, 50/60 Hz EP ED EG EG EA ET EN EB EM
  

§ Signal voltage of the Cat. No. 100S-D… electronic interface Ue: 24V DC/Ie: 15 mA
Pick-up voltage: 13.0V DC…30.2V DC
Drop-out voltage: -3.0V DC…+5.0V DC
§ Not available with 100S-D300.


3-Pole DC-Operated Contactors

Ie [A] Switching of 3-phase motors AC-2, AC-3 Auxiliary contacts Conventional Coil
Cat. No.
Electronic Coil
Cat. No.Ø 
60 °C 40 °C kW (50 Hz) ¬  Hp (60 Hz) N.O. N.C. T  ¬ 
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V Click to enlarge - 100M-66-3a Click to enlarge - 100S-D-80-6
95 160 25 50 50 55 90 45 25 30 60 75 2 2 100S-D95Ä33LC‡  100S-D95Ä22BC
110 160 32 55 55 63 100 40 40 75 100 3 2/1L 100S-D110Ä33LC‡  100S-D110Ä22BC
140 250 45 75 75 80/100§  110/132§  40 50 100 125 3 2/1L 100S-D140Ä33LC‡  100S-D140Ä22BC
180 250 55 90 100 90/125§  132/160§  90 50 60 150 150 3 2/1L 100S-D180Ä33LC‡  100S-D180Ä22BC
210 350 63 110 110 150 200 110 60 75 150 200 2 2 100S-D210Ä22BC
250 350 80 132 150 160 250 133 75 100 200 250 2 2 100S-D250Ä22BC
300 450 90 160 160 200 300 160 100 125 250 300 2 2 100S-D300Ä22BC
420 540 132 220 250 300 425 220 150 175 350 400 2 2 100S-D420Ä22BC
630 800 200 355 355 450 500 200 250 500 600 2 2 100S-D630Ä22BC
860 1000 250 500 500 560 600 250 300 600 700 2 2 100S-D860Ä22BC
  
¬ Preferred values according to IEC 60072-1.
T The N.C. contacts meet IEC 60947-4 Annex F requirements for mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit.
‡ For conventional DC coil only. The pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts.
§ Higher kW rating only applies to contactors with electronic coil.
Ø If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the Cat. No. Example: Cat. No. 100S-D95Ä22BC becomes Cat. No. 100S-D95Ä22C.

Ä Coil Voltage Codes

Conventional Coil [V] 24 48 110 125 220 250
100S-D95…100S-D180 DC ZJ ZY ZD ZS ZA ZT
  

Electronic Coil
w/ EI Interface § 
[V] 24 48…72 110…130 200…255
100S-D95…100S-D300 DC EZJ EZY EZD EZA
100S-D420 DC EZD EZA
100S-D630…860 DC ED EA
  

§ Signal voltage of the cat. no. 100S-S… electronic interface Ue: 24V DC/Ie: 15 mA
Pick-up voltage: 13.0V DC…30.2V DC
Drop-out voltage: -3.0V DC…+5.0V DC