Bulletin 100-K Miniature Contactors

Click to enlarge - 100-K05_4c Click to enlarge - 104-K

Bulletin 100-K/104-K IEC Contactors


Your order must include: cat. no. (with coil voltage code) of the mini contactor specified and, if required, cat. no. of any accessories

Allen-Bradley Bulletin 100-K miniature contactors are designed for commercial and light industrial applications where panel space is at a premium. These miniature devices, while 45 mm wide, are shallower and have less panel depth requirements than standard IEC contactors.

The miniature contactors have been designed with flexibility in mind. They are available with AC or DC operating coils, several contact ratings, and optional 2- or 4-pole adder decks in a variety of auxiliary contact configurations.

Standards Compliance and Certifications

Standards Compliance

IEC/EN 60947-1,-4-1,-5-1,-5-4
UL 508
CSA 22.2. No. 14
NF F 62-000


Certifications

CE marked
cULus Listed (File No. E41850, Guide NLDX, NLDX7)


Product Selection

3-Pole AC- and DC-Operated Contactors

Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts Pkg. Qty.¬  Cat. No.
3Æ kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
40 °C 230V 400/415V 500V 690V 1Æ 3Æ
AC-1 115V 230V 200V 230V 460V 575V N.O. N.C.
20 1.5 2.2 2.2 2.2 1/2 1 1-1/2 1-1/2 3 3 1 0 1 100-K05Ä10
0 1 1 100-K05Ä01
20 3 4 4 4 1/2 1-1/2 2 2 5 5 1 0 1 100-K09Ä10
0 1 1 100-K09Ä01
20 3 5.5 5.5 5.5 3/4 2 3 3 7-1/2 7-1/2 1 0 1 100-K12Ä10
0 1 1 100-K12Ä01
  
¬ May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 100-K09ZJ10M.
Ä The Cat. No. as listed is incomplete. Select a Coil Voltage Code from Ä Coil Voltage Code to complete the Cat. No.
    Example: 24V DC: Cat. No. 100-K05Ä10 becomes Cat. No. 100-K05ZJ10.

4-Pole AC- and DC-Operated Contactors

Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Contact Configuration, Main Pole Pkg. Qty.¬  Cat. No.
3Æ kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
40 °C 230V 400/415V 500V 690V 1Æ 3Æ
AC-1 115V 230V 200V 230V 460V 575V N.O. N.C.
20 1.5 2.2 2.2 2.2 1/2 1 1-1/2 1-1/2 3 3 4 0 1 100-K05Ä400
3 1 1 100-K05Ä300
2 2 1 100-K05Ä200
20 3 4 4 4 1/2 1-1/2 2 2 5 5 4 0 1 100-K09Ä400
3 1 1 100-K09Ä300
2 2 1 100-K09Ä200
20 3 5.5 5.5 5.5 3/4 2 3 3 7-1/2 7-1/2 4 0 1 100-K12Ä400
3 1 1 100-K12Ä300
2 2 1 100-K12Ä200
  
¬ May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 100-K09ZJ400M.
Ä The Cat. No. as listed is incomplete. Select a Coil Voltage Code from Ä Coil Voltage Code to complete the Cat. No.
    Example: 24V DC: Cat. No. 100-K05Ä400 becomes Cat. No. 100-K05ZJ400.

Reversing AC- and DC-Operated Contactors

Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts per Contactor ¬  Cat. No.
3Æ kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
40 °C 230V 400/415V 500V 690V 1Æ 3Æ
AC-1 115V 230V 200V 230V 460V 575V N.O. N.C.
20 1.5 2.2 2.2 2.2 1-1/2 1-1/2 3 3 0 1 104-K05Ä02
20 3 4 4 4 2 2 5 5 0 1 104-K09Ä02
20 3 5.5 5.5 5.5 3 3 7-1/2 7-1/2 0 1 104-K12Ä02
  
¬ Used for electrical interlocking
Ä The Cat. No. as listed is incomplete. Select a standard Coil Voltage Code from Ä Coil Voltage Code to complete the Cat. No.
    Example: 230V, 50/60 Hz: Cat. No. 104-K05Ä02 becomes Cat. No. 104-K05KF02.
Bulletin 104-K reversing contactors are factory assembled and include contactors, mechanical interlock (Cat. No. 100-KMCH) and wiring kit (Cat. No. 100-KPR) for power and control circuit (electrical interlock). Wiring schematic see 100-KPR

Ä Coil Voltage Code

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz:
Cat. No. 100-K09Ä10 becomes Cat. No.100-K09D10.


AC Voltages [V] 24 110 120 230 240 400 480 600
50 Hz D
60 Hz D B VC
50/60 Hz KJ KF KA KN
  

DC Voltages [V] 12 24 110 125 220 250
Standard ZQ ZJ ZD ZS ZA ZT
with Integrated Diode DJ
  

Assignment of Contacts

Device Combinations in Accordance with IEC 60947-1 / -4-1

Table valid for : AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C, normal position (horizontal rail mounting) ¬ 

Auxiliary Contact Blocks Miniature Contactors 100-K (AC and DC Control)
  Circuit Diagram Control 100-K05Ä10
100-K09Ä10
100-K12Ä10
100-K05Ä01
100-K09Ä01
100-K12Ä01
100-K05Ä400
100-K09Ä400
100-K12Ä400
100-K05Ä300
100-K09Ä300
100-K12Ä300
100-K05Ä200
100-K09Ä200
100-K12Ä200
Click to enlarge - 100-K_3pol_10_Dia Click to enlarge - 100-K_3pol_01_Dia Click to enlarge - 100-K_4pol_400_Dia Click to enlarge - 100-K_3pol_300_Dia Click to enlarge - 100-K_2pol_200_Dia
Front Mounting  
100-KFA02E Click to enlarge - 100-KFA02E_Dia AC/DC T  01 + 02 = 03 ‡  T  T  ‡ 
100-KFC02 Click to enlarge - 100-KFC02_Dia AC/DC 10 + 02 = 12 00 + 02 = 02 00 + 02 = 02 ‡ 
100-KFA11E Click to enlarge - 100-KFA11E_Dia AC/DC T  01 + 11 = 12 T  T  T 
100-KFB11 Click to enlarge - 100-KFB11_Dia AC/DC 10 + 11 = 21 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11
100-KFC11 Click to enlarge - 100-KFC11_Dia AC/DC 10 + 11 = 21 T  00 + 11 = 11 00 + 11 = 11 00 + 11 = 11
100-KFA20E Click to enlarge - 100-KFA20E_Dia AC/DC T  01 + 20 = 21 T  T  T 
100-KFC20 Click to enlarge - 100-KFC20_Dia AC/DC 10 + 20 = 30 T  00 + 20 = 20 00 + 20 = 20 00 + 20 = 20
100-KFA04E Click to enlarge - 100-KFA04E_Dia AC/DC T  ‡  T  ‡ 
100-KFC04 Click to enlarge - 100-KFC04_Dia AC/DC 10 + 04 = 14 ‡  00 + 04 = 04 ‡ 
100-KFA13E Click to enlarge - 100-KFA13E_Dia AC/DC T  01 + 13 = 14 ‡  T  T  ‡ 
100-KFC13 Click to enlarge - 100-KFC13_Dia AC/DC 10 + 13 = 23 T  ‡  00 + 13 = 13 00 + 13 = 13 ‡ 
100-KFA22Z Click to enlarge - 100-KFA22Z_Dia AC/DC T  01 + 22 = 23 ‡  T  T  ‡ 
100-KFB22 Click to enlarge - 100-KFB22_Dia AC/DC 10 + 22 = 32 00 + 22 = 22 00 + 22 = 22 ‡ 
100-KFC22 Click to enlarge - 100-KFC22_Dia AC/DC 10 + 22 = 32 T  ‡  00 + 22 = 22 00 + 22 = 22 ‡ 
100-KFA31Z Click to enlarge - 100-KFA31Z_Dia AC/DC T  §  T  § 
100-KFC31 Click to enlarge - 100-KFC31_Dia AC/DC 10 + 31 = 41 §  00 + 31 = 31 § 
100-KFA40E Click to enlarge - 100-KFA40E_Dia AC/DC T  01 + 40 = 41 T  T  T 
100-KFC40 Click to enlarge - 100-KFC40_Dia AC/DC 10 + 40 = 50 T  00 + 40 = 40 00 + 40 = 40 00 + 40 = 40
  
¬ For other operating limits, please contact our technical consultant.
T Combination possible but not recommended, due to repeating or not consecutive sequence numbering
‡ Tamb. max. +40 °C
§ Tamb. max. +40 °C and only allowed for coil voltage 24V DC or 230V AC

Bulletin 100-K/104-K Accessories

Auxiliary Contact Blocks

  Description Connection Diagrams Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a For Use With Pkg. Qty. Cat. No.
N.O. N.C.
Click to enlarge - 100-KF_2p_4c Front-Mounted Auxiliary Contacts
Auxiliary contact blocks
2- and 4-pole versions
Choice of contact configurations
Snap on, no tools required
Electronically-compatible bifurcated contacts for signals down to 15V/2 mA
Mirror Contact performance per IEC 60947-4-1
Click to enlarge - 100-KFC02_Dia 0 2 100-K05…K12Ä10 1 100-KFC02
Click to enlarge - 100-KFC11_Dia 1 1 100-K05…K12Ä10 1 100-KFC11
Click to enlarge - 100-KFC20_Dia 2 0 100-K05…K12Ä10 1 100-KFC20
Click to enlarge - 100-KF_4p_4c Click to enlarge - 100-KFC04_Dia 0 4 100-K05…K12Ä10 1 100-KFC04
Click to enlarge - 100-KFC13_Dia 1 3 100-K05…K12Ä10 1 100-KFC13
Click to enlarge - 100-KFC31_Dia 3 1 100-K05…K12Ä10 1 100-KFC31
Click to enlarge - 100-KFC22_Dia 2 2 100-K05…K12Ä10 1 100-KFC22
Click to enlarge - 100-KFC40_Dia 4 0 100-K05…K12Ä10 1 100-KFC40
Click to enlarge - 100-KF_2p_4c Click to enlarge - 100-KFA02E_Dia 0 2 100/104-K, 700-K 1 100-KFA02E
Click to enlarge - 100-KFA11E_Dia 1 1 100/104-K, 700-K 1 100-KFA11E
Click to enlarge - 100-KFA20E_Dia 2 0 100/104-K, 700-K 1 100-KFA20E
Click to enlarge - 100-KF_4p_4c Click to enlarge - 100-KFA04E_Dia 0 4 100/104-K, 700-K 1 100-KFA04E
Click to enlarge - 100-KFA13E_Dia 1 3 100/104-K, 700-K 1 100-KFA13E
Click to enlarge - 100-KFA22Z_Dia 2 2 100/104-K, 700-K 1 100-KFA22Z
Click to enlarge - 100-KFA31Z_Dia 3 1 100/104-K, 700-K 1 100-KFA31Z
Click to enlarge - 100-KFA40E_Dia 4 0 100/104-K, 700-K 1 100-KFA40E
  

Control Modules

  Description Connection
Diagrams
For Use With Pkg. Qty. Cat. No.
Click to enlarge - 100-KMCH_4c Mechanical Interlock
For interlocking of two adjacent contactors
No added width to contactor assembly
Front mount Plug-In type
Optional auxiliary contact blocks and suppressor modules mount onto the interlock
Click to enlarge - 100-KMHC_Dia 100-K, 700-K (AC & DC Control) 1 100-KMCH
Click to enlarge - 100-KFS_4c Surge Suppressor
Plug-in Type
Limits surge voltage on coil drop-off
RC Suppressor 24…48V AC Click to enlarge - 100-KFSC_Dia 100/104-K, 700-K 1 ¬  100-KFSC50
110…280V AC 1 ¬  100-KFSC280
380…480V AC 1 ¬  100-KFSC480
MOV Suppressor 12…55V AC, 12…77V DC Click to enlarge - 100-KFSV_Dia 100/104-K, 700-K 1 ¬  100-KFSV55
56…136V AC, 78…180V DC 1 ¬  100-KFSV136
137…277V AC, 181…250V DC 1 ¬  100-KFSV277
Diode Suppressor 12…250V DC Click to enlarge - 100-KFSD_Dia 100/104-K, 700-K 1 ¬  100-KFSD250
  
¬ May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

Connecting Components

  Description For Use With Pkg. Qty. Cat. No.
Click to enlarge - 140M-C-PEK12_C ECO Connecting Module — 12 and 25 A
  • For DOL and reversing starters

  • Eco-starters mount on single DIN Rail (140M on DIN Rail)

  • Electrical and mechanical interconnection of 140M MPCB and 100-K contactors
  • Connects:
    140M-C circuit breakers with 100-K contactors
    140M-C to 100-K 1 ¬  140M-C-PEK12
    Click to enlarge - 100-KPR_002_4c Power Wiring Kit
    For Reversing and Star/Delta combinations.
    Star-point bridge not included.
    Min. interruption time 50 ms
    Click to enlarge - 100-KPR_Dia 100-K 1 100-KPR
    Click to enlarge - 100-KWT_4c Feeder Terminal for Compact Bus Bars
    Max. current 34 A
    Supply of compact bus bars 100-K 1 100-KWT
    Click to enlarge - 100-KW454_4c Three-Phase Compact Bus Bars
    Max. current 34 A
    For 100-K, 5…12 A contactors
    45 mm spacing (3 connections)T 
    100-K 1 100-KW453
    For 100-K, 5…12 A contactors
    45 mm spacing (4 connections)T 
    100-K 1 100-KW454
      
    ¬ May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 140M-C-PEK12M.
    T Combinations possible. Example: For 6 contactor connections use one cat. no. 100-KW453 and one cat. no. 100-KW454.

    Marking Systems

      Description Pkg. Qty. Cat. No.
    Click to enlarge - 700CF-192-3 Label Sheet
    105 self-adhesive paper labels each, 6 x 17 mm
    10 100-FMS
    Click to enlarge - 1492-M7X12a_bw Snap-In Marker Card 5 1492-M6X12
      

    Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications

      100/104-K 100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
    Coil Type : Conventional X X X X X X X X X X X X X
      Electronic — EI
    AC-1 Active Power Load (50 Hz);
    Ambient temperature 40 °C
        Ie £ 500V [A] 20 20 20 32 32 32 32 (40)¬  65 65 75 75 85 100
    690V [A] 20 20 20 32 32 32 32 (40)¬  65 65 75 75 85 100
    1000V [A]
    230V [kW] 8 8 8 13 13 13 13 26 26 30 30 34 40
    240V [kW] 8.3 8.3 8.3 13 13 13 13 27 27 31 31 35 42
    400V [kW] 14 14 14 22 22 22 22 45 45 52 52 59 69
    415V [kW] 14 14 14 23 23 23 23 47 47 54 54 61 72
    500V [kW] 17 17 17 28 28 28 28 56 56 65 65 74 87
    690V [kW] 24 24 24 38 38 38 38 78 78 90 90 102 120
    1000V [kW]
    Ambient temperature 60 °C
        Ie £ 500V [A] 16 16 16 32 32 32 32 65 65 60 60 80 100
    690V [A] 16 16 16 32 32 32 32 65 65 60 60 80 100
    1000V [A]
    230V [kW] 6.4 6.4 6.4 13 13 13 13 26 26 24 24 25 40
    240V [kW] 6.7 6.7 6.7 13 13 13 13 27 27 25 25 26 42
    400V [kW] 11 11 11 22 22 22 22 45 45 42 42 44 69
    415V [kW] 12 12 12 23 23 23 23 47 47 43 43 45 72
    500V [kW] 14 14 14 28 28 28 28 56 56 52 52 55 87
    690V [kW] 19 19 19 38 38 38 38 78 78 72 72 75 120
    1000V [kW]
    Switching of 3-phase Motors; (50 Hz)
    Ambient temperature 60 °C, AC-2, AC-3
      230V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
    240V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
    400V [A] 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
    415V [A] 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
    500V [A] 3.9 6.8 9.2 7 10 14 20 25 30 29 30 38 55
    690V [A] 2.8 4.9 6.7 5 7 9 12 18 21 9 21 25 34
    1000V [A]
    230V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
    240V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
    400V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 18.5 18.5 22 32
    415V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 20 20 22 32
    500V [kW] 2.2 4 5.5 4 5.5 7.5 13 15 20 18.5 20 25 37
    690V [kW] 2.2 4 5.5 4 5.5 7.5 10 15 18.5 7.5 18.5 22 32
    1000V [kW]
    Load Carrying Capacity per UL/CSA
    General Purpose Current (enclosed)
      [A] 12 15 18 25 25 30 30 55 60 60 60 75 90
    Rated power (enclosed)
        1-phase 115V [A] 9.8 9.8 13.8 9.8 9.8 16 24 24 34 34 34 34 56
    230V [A] 8 10 12 10 12 17 17 28 28 28 28 40 50
    115V [Hp] 0.5 0.5 0.75 0.5 0.5 1 2 2 3 3 3 3 5
    230V [Hp] 1 1.5 2 1.5 2 3 3 5 5 5 5 7.5 10
        3-phase 200V [A] 6.9 7.8 11 7.8 11 17.5 17.5 25.3 32.2 32.2 32.2 32.2 48.3
    230V [A] 6 6.8 9.6 6.8 9.6 15.2 22 28 28 28 28 42 54
    460V [A] 4.8 7.6 11 7.6 11 14 21 27 34 34 34 40 52
    575V [A] 3.9 6.1 9 9 11 17 17 27 32 17 32 32 52
    200V [Hp] 1.5 2 3 2 3 5 5 7.5 10 10 10 10 15
    230V [Hp] 1.5 2 3 2 3 5 7.5 10 10 10 10 15 20
    460V [Hp] 3 5 7.5 5 7.5 10 15 20 25 25 25 30 40
    575V [Hp] 3 5 7.5 7.5 10 15 15 25 30 15 30 30 50
      
    ¬ Values in ( ) with increased cross-section and cable lug

      100/104-C, 100S/104S-C 100/104-D, 100S-D
      72 85 90*200 90*400 95 110 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X X X
    Electronic — EI X X X X X X X X X X
    AC-1 Active Power Load (50 Hz);
    Ambient temperature 40 °C
    Electronic — EI AC-1 Active Power Load (50 Hz);
    Ambient temperature 40 °C
        Ie £ 500V [A] 100 100 130 130 160 160 250 250 250 250 350 350 450 540 800 1000
    690V [A] 100 100 130 130 160 160 250 250 250 250 350 350 450 540 800 1000
    1000V [A] 160 160 250 250 250 250 350 350 450 540
    230V [kW] 40 40 52 52 64 64 100 100 100 100 139 139 179 199 319 398
    240V [kW] 42 42 54 54 67 67 104 104 104 104 145 145 187 208 333 416
    400V [kW] 69 69 90 90 111 111 173 173 173 173 242 242 312 346 554 693
    415V [kW] 72 72 93 93 115 115 180 180 180 180 252 252 323 359 575 719
    500V [kW] 87 87 113 113 139 139 217 217 217 217 303 303 390 433 693 866
    690V [kW] 120 120 155 155 191 191 299 299 299 299 418 418 538 598 956 1195
    1000V [kW] 277 277 433 433 433 433 606 606 779 866
    Ambient temperature 60 °C Electronic — EI Ambient temperature 60 °C
        Ie £ 500V [A] 100 100 110 110 135 135 210 210 210 210 300 300 380 425
    690V [A] 100 100 110 110 135 135 210 210 210 210 300 300 380 425
    1000V [A] 135 135 210 210 210 210 300 300 380 425
    230V [kW] 40 40 44 44 54 54 84 84 84 84 120 120 151 169
    240V [kW] 42 42 46 46 56 56 87 87 87 87 125 125 158 177
    400V [kW] 69 69 76 76 94 94 145 145 145 145 208 208 263 294
    415V [kW] 72 72 79 79 97 97 151 151 151 151 216 216 273 305
    500V [kW] 87 87 95 95 117 117 182 182 182 182 260 260 329 368
    690V [kW] 120 120 131 131 161 161 251 251 251 251 359 359 454 508
    1000V [kW] 234 234 364 364 364 364 520 520 658 736
    Switching of 3-phase Motors; (50 Hz)
    Ambient temperature 60 °C, AC-2, AC-3
    Electronic — EI Switching of 3-phase Motors; (50 Hz)
    Ambient temperature 60 °C, AC-2, AC-3
    230V [A] 72 85 85 85 95 110 140 140 180 180 210 250 300 420 630 860
    240V [A] 72 85 85 85 95 110 140 140 180 180 210 250 300 420 630 860
    400V [A] 72 85 85 85 95 110 140 140 180 180 210 250 300 420 630 860
    415V [A] 72 85 85 85 95 110 (130)‡  140 (155)‡  140 (155)‡  180 (189)‡  180 (189)‡  210 (227)‡  250 (258)‡  300 (315)‡  420 630 860
    500V [A] 67 80 80 80 95 110 115 140 140 180 210 250 300 420 630 753
    690V [A] 42 49 22 49 95 110 115 140 140 180 210 250 300 420 492
    1000V [A] 33 40 55 55 65 65 80 95 115 160
    230V [kW] 22 25 25 25 30 34 45 45 57 57 67 80 97 135 200 250
    240V [kW] 22 25 25 25 31 36 47 47 60 60 70 83 101 141 200 250
    400V [kW] 40 45 45 45 53 61 78 78 101 101 118 140 170 238 355 500
    415V [kW] 40 45 45 45 55 63 (75)‡  82 (90)‡  82 (90)‡  105 (110)‡  105 (110)‡  122 (132)‡  145 (150)‡  176 (185)‡  250 355 500
    500V [kW] 45 55 55 55 66 76 80 98 98 126 147 177 213 298 450 560
    690V [kW] 40 45 18.5 45 92 106 111 135 135 176 205 250 293 424 500
    1000V [kW] 45 55 75 75 90 90 110 132 160 225
    Load Carrying Capacity per UL/CSA Electronic — EI Load Carrying Capacity per UL/CSA
    General Purpose Current (enclosed) General Purpose Current (enclosed)
        [A] 90 100 125 130 160 160 220 220 220 220 300 300 340 420 630 860
    Rated power (enclosed) Rated power (enclosed)
        1-phase 115V [A] 56 80 80 80 80 100 135 135
    230V [A] 68 68 68 68 68 110 136 136 176 176 216
    115V [Hp] 5 7.5 7.5 7.5 7.5 10 15 15
    230V [Hp] 15 15 15 15 15 25 30 30 40 40 50
        3-phase 200V [A] 62.1 78.2 78.2 78.2 78.2 120 120 120 150 150 177 221 285 414 552 692
    230V [A] 68 80 80 80 80 104 130 130 154 154 192 248 312 420 602 720
    460V [A] 65 77 65 77 77 96 124 124 180 180 180 240 302 414 590 702
    575V [A] 62 62 22 52 77 99 125 125 144 144 192 242 289 382 562 651
    200V [Hp] 20 25 25 25 25 40 40 40 50 50 60 75 100 150 200 250
    230V [Hp] 25 30 30 30 30 40 50 50 60 60 75 100 125 175 250 300
    460V [Hp] 50 60 50 60 60 75 100 100 150 150 150 200 250 350 500 600
    575V [Hp] 60 60 20 50 75 100 125 125 150 150 200 250 300 400 600 700
         
    ¬ Values in ( ) with increased cross-section and cable lug ‡ 415 V: values in ( ) AC-3 and AC-4 lifespan -25 %

     
    100/104-K

    100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 43 60
    Coil Type : Conventional X X X X X X X X X X X
    Electronic — EI
    Switching of 3-phase Motors, (50Hz); Ambient temperature 60 °C, AC-4
      230V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
    240V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
    400V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
    415V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
    500V [A] 3.9 6.8 9.2 7 10 14 20 25 30 38 55
    690V [A] 2.8 4.9 6.7 5 7 9 12 18 21 25 34
    1000V [A]
    230V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
    240V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
    400V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 22 32
    415V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 22 32
    500V [kW] 2.2 4 5.5 4 5.5 7.5 13 15 20 25 37
    690V [kW] 2.2 4 5.5 4 5.5 7.5 10 15 18.5 22 32
    1000V [kW]
    Electronic — EI
    AC-4 at approximately 200,000 operations 230V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
    240V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
    400/415V [A] 2 3.6 3.6 4.3 6.6 9 9 12 14 16.5 25.5
    500V [A] 1.9 3.2 3.2 4.3 6.6 9 9 12 14 16.5 25.5
    690V [A] 4.3 6.6 9 9 12 14 16.5 25.5
    1000V [A]
    230V¬  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 3.7 4 6.3
    240V¬  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 4 4 7.5
    400V¬  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
    415V¬  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
    500V¬  [kW] 0.75 1.5 1.5 2.2 3.7 5.5 5.5 7.5 7.5 10 15
    690V¬  [kW] 3 5.5 7.5 7.5 10 11 15 22
    1000V¬  [kW]
    Max. switching frequency Ops/h 250 250 250 250 250 220 200 200 200 200 120
    Wye-Delta (60 Hz)
      200V [Hp] 2.2 3 5 5 5 7½ 7½ 10 15 20 30
    230V [Hp] 2.2 3 5 5 7½ 10 10 15 20 25 40
    460V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
    575V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
    UL/CSA Elevator DutyT 
      200V [A] 7.8 11.0 11.0 17.5 25.3 25.3 32.2 32.2
    230V [A] 6.8 9.6 15.2 15.2 22.0 28.0 28.0 42.0
    460V [A] 7.6 11.0 14.0 21.0 27.0 27.0 34.0 40.0
    575V [A] 6.1 9.0 11.0 17.0 22.0 27.0 32.0 41.0
    200V [Hp] 2 3 3 5 7½ 7½ 10 10
    230V [Hp] 2 3 5 5 7½ 10 10 15
    460V [Hp] 5 7½ 10 15 20 20 25 30
    575V [Hp] 5 7½ 10 15 20 25 30 40
    Star-Delta Starting (50 Hz)
      £ 230V [A] 11.3 20 20 21 26 35 46 61 66 76 107
    £ 240V [A] 11.3 20 20 21 26 35 46 61 66 76 107
    400V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
    415V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
    500V [A] 6.8 12.4 12.4 12 17 24 35 43 52 66 95
    690V [A] 4.9 8.9 8.9 8.6 12 16 21 31 36 43 59
    1000V [A]
    230V¬  [kW] 3 5.5 5.5 5.5 7.5 10 13 17 20 22 32
    240V¬  [kW] 3 5.5 5.5 5.5 7.5 10 13 18.5 20 22 32
    400V¬  [kW] 4 7.5 10 7.5 10 13 20 25 32 40 55
    415V¬  [kW] 4 7.5 11 7.5 11 15 22 25 37 40 55
    500V¬  [kW] 4 7.5 7.5 7.5 11 15 22 25 32 45 63
    690V¬  [kW] 4 7.5 7.5 7.5 10 13 18.5 25 32 40 55
    1000V¬  [kW]
      
    ¬ Power ratings at 50 Hz: Preferred values according to IEC 60072-1 T Approval pending on Cat. No. 100-D210…D860.

      100/104-C, 100S/104S-C 100/104-D, 100S-D
    72 85 95 110 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X
    Electronic — EI X X X X X X X X X X
    Switching of 3-phase Motors, (50Hz)
    Ambient temperature 60°C, AC-4
    Electronic — EI Switching of 3-phase Motors, (50Hz); Ambient temperature 60 °C, AC-4
    230V [A] 72 85 95 110 140 140 180 180 210 250 300 420
    240V [A] 72 85 95 110 140 140 180 180 210 250 300 420
    400V [A] 72 85 95 110 140 140 180 180 210 250 300 420
    415V [A] 72 85 95 110 (130)T  140 (155)T  140 (155)T  180 (189)‡  180 (189)‡  210 (227)T  250 (258)T  300 (315)T  420
    500V [A] 67 80 85 105 115 140 140 170 210 250 300 360
    690V [A] 42 49 85 105 115 140 140 170 210 250 300 360
    1000V [A] 33 40 55 55 65 65 80 95 115 160
    230V [kW] 22 25 30 34 45 45 57 57 67 80 97 135
    240V [kW] 22 25 31 36 47 47 60 60 70 83 101 141
    400V [kW] 40 45 53 61 78 78 100 100 118 140 170 238
    415V [kW] 40 45 55 63 (75)T  82 (90)T  82 (90)T  105 (110)T  105 (110)T  125 (132)T  145 (150)T  176 (185)T  250
    500V [kW] 45 55 59 73 80 98 98 119 147 177 213 255
    690V [kW] 40 45 81 102 110 135 135 167 205 250 293 356
    1000V [kW] 45 55 75 75 90 90 110 132 160 225
    AC-4 at approximately 200,000 operations Electronic — EI Electronic — EI
    230V [A] 31 38 43 50 60 60 67 67 85 105 140 170
    240V [A] 31 38 43 50 60 60 67 67 85 105 140 170
    400/415V [A] 31 38 43 50 60 60 67 67 85 105 140 170
    500V [A] 31 38 43 50 60 60 67 67 85 105 140 170
    690V [A] 31 38 43 50 60 60 67 67 85 105 140 170
    1000V [A] 19 23 37 37 43 43 60 72 85 105
    230V¬  [kW] 7.5 11 13 15 17 17 20 20 25 32 45 55
    240V¬  [kW] 7.5 11 13 15 18.5 18.5 22 22 25 32 45 55
    400V¬  [kW] 15 20 22 25 32 32 37 37 45 55 75 90
    415V¬  [kW] 17 20 22 25 32 32 37 37 50 55 80 100
    500V¬  [kW] 20 25 25 32 40 40 45 45 55 75 100 110
    690V¬  [kW] 25 32 40 45 55 55 63 63 80 100 132 160
    1000V¬  [kW] 22 30 50 50 55 55 80 100 110 150
    Max. switching frequency Ops/h 120 120 120 120 120 120 100 100 120 100 70 70
    Wye-Delta (60 Hz) Electronic — EI Electronic — EI
    200V [Hp] 40 50 40 60 60 60 75 75 100 125 175 250
    230V [Hp] 50 60 50 60 75 75 100 100 125 175 200 250
    460V [Hp] 100 125 100 125 175 175 200 200 250 350 450 600
    575V [Hp] 100 125 125 150 200 200 250 250 300 450 500 650
    UL/CSA Elevator DutyT  Electronic — EI UL/CSA Elevator DutyT 
    200V [A] 48.3 62.1 62.1 78 92 92 120 120 150 150 177 221
    230V [A] 54.0 68.0 68.0 80 104 104 130 130 130 154 192 248
    460V [A] 52.0 65.0 65.0 77 96 96 124 124 156 180 180 240
    575V [A] 52.0 62.0 62.0 77 77 77 99 99 125 144 192 242
    200V [Hp] 15 20 20 25 30 30 40 40 50 50 60 75
    230V [Hp] 20 25 25 30 40 40 50 50 50 60 75 100
    460V [Hp] 40 50 50 60 75 75 100 100 125 150 150 200
    575V [Hp] 50 60 60 75 75 75 100 100 125 150 200 250
    Electronic — EI Star-Delta Starting (50 Hz)
    £ 230V [A] 125 147 165 191 242 242 312 312 364 433 520 727
    £ 240V [A] 125 147 165 191 242 242 312 312 364 433 520 727
    400V [A] 125 147 165 191 242 242 312 312 364 433 520 727
    415V [A] 125 147 165 191 (225)T  242 (268)T  242 (268)T  312 (332)‡  312 (332)‡  364 (393)T  433 (447)T  520 (546)T  727
    500V [A] 116 139 165 191 199 242 312 312 364 433 520 727
    690V [A] 73 85 165 191 199 242 312 312 364 433 520 727
    1000V [A] 57 69 95 95 113 113 139 165 200 277
    230V¬  [kW] 37 45 45 55 75 75 90 90 110 132 160 220
    240V¬  [kW] 40 50 50 63 80 80 100 100 125 150 160 250
    400V¬  [kW] 63 80 80 100 132 132 160 160 200 250 300 425
    415V¬  [kW] 63 80 80 (90)T  100 (132)T  132 (160)T  132 (160)T  160 160 220 250 315 (335)T  425
    500V¬  [kW] 80 90 100 132 132 160 200 200 250 315 375 530
    690V¬  [kW] 63 80 132 160 200 220 300 300 355 425 530 750
    1000V¬  [kW] 75 90 132 132 160 160 200 220 280 400
         
      T 415V: Values in ( ) AC-3 and AC-4 lifespan -25%

     
    100/104-K

    100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 43 60
    Coil Type : Conventional X X X X X X X X X X X
    Electronic — EI
    Switching of Power Transformers,
    AC-6a (50 Hz)
    Inrush Current = n  
    Rated transformer current  
        n = 30 £ 230V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 240V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 400V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 415V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 500V [A] 1.8 3.2 3.2 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 690V [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 1000V [A]
    230V [kVA] 1.2 2 2 4.3 4.3 4.3 4.3 8 8 9.2 16
    240V [kVA] 1.2 2 2 4.5 4.5 4.5 4.5 8.3 8.3 10 17
    400V [kVA] 1.7 2.8 3.4 7.5 7.5 7.5 7.5 14 14 16 28
    415V [kVA] 1.7 2.8 3.4 7.8 7.8 7.8 7.8 14 14 17 29
    500V [kVA] 1.7 2.8 3.4 9.4 9.4 9.4 9.4 17 17 20 35
    690V [kVA] 2 4 5 13 13 13 13 24 24 27 49
    1000V [kVA]
        n = 20 £ 690V [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
        n = 15 £ 690V [A] 22 22 22 22 40 40 46 82
    60 Hz Peak Inrush/peak rated transformer current
      n = 30 [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
    200V [kVA] 3.8 3.8 3.8 3.8 6.9 6.9 8.0 14.1
    208V [kVA] 3.9 3.9 3.9 3.9 7.2 7.2 8.3 14.7
    240V [kVA] 4.5 4.5 4.5 4.5 8.3 8.3 9.6 17.0
    480V [kVA] 9.1 9.1 9.1 9.1 16.6 16.6 19.1 33.9
    600V [kVA] 11.3 11.3 11.3 11.3 20.8 20.8 23.9 42.4
    660V [kVA] 12.5 12.5 12.5 12.5 22.9 22.9 26.3 46.6
    60 Hz Peak Inrush/peak rated transformer current
      n = 20 [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
    200V [kVA] 5.6 5.6 5.6 5.6 10.4 10.4 12.0 21.2
    208V [kVA] 5.9 5.9 5.9 5.9 10.8 10.8 12.4 22.1
    240V [kVA] 6.8 6.8 6.8 6.8 12.5 12.5 14.3 25.5
    480V [kVA] 13.6 13.6 13.6 13.6 24.9 24.9 28.7 51.0
    600V [kVA] 16.9 16.9 16.9 16.9 31.2 31.2 35.9 63.7
    660V [kVA] 18.6 18.6 18.6 18.6 34.3 34.3 39.4 70.1
    60 Hz Peak Inrush/peak rated transformer current
      n=15 [A] 22 22 22 22 40 40 46 82
    200V [kVA] 7.5 7.5 7.5 7.5 13.9 13.9 15.9 28.4
    208V [kVA] 7.8 7.8 7.8 7.8 14.4 14.4 16.6 29.5
    240V [kVA] 9.0 9.0 9.0 9.0 16.6 16.6 19.1 34.1
    480V [kVA] 18.1 18.1 18.1 18.1 33.3 33.3 38.2 68.2
    600V [kVA] 22.6 22.6 22.6 22.6 41.6 41.6 47.8 85.2
    660V [kVA] 24.9 24.9 24.9 24.9 45.7 45.7 52.6 93.7
      

      100/104-C, 100S/104S-C 100/104-D, 100S-D
    72 85 95 110 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X
    Electronic — EI X X X X X X X X X X
    Switching of Power Transformers,
    AC-6a (50 Hz)
    Electronic — EI Switching of Power Transformers,
    AC-6a (50 Hz)
    Inrush Current 230V = n Inrush Current
    Rated transformer current 230V Rated transformer current
        n = 30 £ 230V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
    £ 240V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
    £ 400V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
    £ 415V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
    £ 500V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
    £ 690V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
    £ 1000V [A] 53 60 70 70 85 85 105 125 150 210
    230V [kVA] 16 16 21 24 28 28 34 34 42 50 60 84
    240V [kVA] 17 17 22 25 29 29 35 35 44 52 62 87
    400V [kVA] 28 28 37 42 48 48 59 59 73 87 104 145
    415V [kVA] 29 29 38 43 50 50 61 61 75 90 108 151
    500V [kVA] 35 35 46 52 61 61 74 74 91 108 130 182
    690V [kVA] 49 49 64 72 84 84 102 102 125 149 179 251
    1000V [kVA] 92 104 121 121 147 147 182 217 260 364
        n = 20 £ 690V [A] 61.3 61.3 80 90 105 105 128 128 158 188 225 315
        n = 15 £ 690V [A] 82 82 107 120 140 140 170 170 210 250 300 420
    60 Hz Peak Inrush/peak rated transformer current Electronic — EI 60 Hz Peak Inrush/peak rated transformer current
      n = 30 [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
    200V [kVA] 14.4 14.4 18.4 20.8 24.2 24.2 29.4 29.4 36.4 43.3 52.0 72.7
    208V [kVA] 14.7 14.7 19.1 21.6 25.2 25.2 30.6 30.6 37.8 45.0 54.0 75.7
    240V [kVA] 17.0 17.0 22.0 24.9 29.1 29.1 35.3 35.3 43.6 52.0 62.4 87.3
    480V [kVA] 33.9 33.9 44.1 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
    600V [kVA] 42.4 42.4 55.1 62.4 72.7 72.7 88.3 88.3 109 130 156 218
    660V [kVA] 46.6 46.6 60.6 68.6 80.0 80.0 97.2 97.2 120 143 171 240
    60 Hz Peak Inrush/peak rated transformer current Electronic — EI 60 Hz Peak Inrush/peak rated transformer current
      n = 20 [A] 61.3 61.3 80 90 105 105 128 128 158 188 225 315
    200V [kVA] 21.2 21.2 27.7 31.2 36.4 36.4 44.3 44.3 54.7 65.1 77.9 109
    208V [kVA] 22.1 22.1 28.8 32.4 37.8 37.8 46.1 46.1 56.9 67.7 81.1 113
    240V [kVA] 25.5 25.5 33.3 37.4 43.6 43.6 53.2 53.2 65.7 78.2 93.5 131
    480V [kVA] 51.0 51.0 66.5 74.8 87.3 87.3 106 106 131 156 187 262
    600V [kVA] 63.7 63.7 83.1 93.5 109 109 133 133 164 195 234 327
    660V [kVA] 70.1 70.1 91.5 103 120 120 146 146 131 215 257 360
    60 Hz Peak Inrush/peak rated transformer current Electronic — EI 60 Hz Peak Inrush/peak rated transformer current
      n=15 [A] 82 82 107 120 140 140 170 170 210 250 300 420
    200V [kVA] 28.4 28.4 37.1 41.6 48.5 48.5 58.9 58.9 72.7 86.6 104 145
    208V [kVA] 29.5 29.5 38.5 43.2 50.4 50.4 61.2 61.2 75.7 90.1 108 151
    240V [kVA] 34.1 34.1 44.5 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
    480V [kVA] 68.2 68.2 89.0 99.8 116 116 141 141 175 208 249 349
    600V [kVA] 85.2 85.2 111 125 145 145 177 177 218 260 312 436
    660V [kVA] 93.7 93.7 122 137 160 160 194 194 240 286 343 480
         

      100/104-K 100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
    Coil Type : Conventional X X X X X X X X X X X X X
    Electronic — EI
    Switching of 3-phase Capacitors, AC-6b (50 Hz)¬ 
    Single capacitor 40 °C 230V [kVar] 8 8 8.5 9 14 14 24 28
    240V [kVar] 8 8 8.5 9 14 14 25 29
    400V [kVar] 8 8 10 12.5 20 24 35 48
    415V [kVar] 8 8 10 12.5 20 25 35 50
    500V [kVar] 8 8 10 12.5 20 25 35 50
    690V [kVar] 8 8 10 12.5 20 25 35 50
    1000V [kVar]
        60 °C 230V [kVar] 8 8 8.5 9 12.5 12.5 18 28
    240V [kVar] 8 8 8.5 9 12.5 12.5 18 29
    400V [kVar] 8 8 10 12.5 20 21.5 30 42
    415V [kVar] 8 8 10 12.5 20 22 30 42
    500V [kVar] 8 8 10 12.5 20 25 30 42
    690V [kVar] 8 8 10 12.5 20 25 30 42
    1000V [kVar]
    Group capacitors 40 °C 230V [kVar] 5 5 8 9 12.5 14 20 28
    240V [kVar] 5 5 8 9 12.5 14 20 29
    400V [kVar] 5 5 8 10 15 20 25 40
    415V [kVar] 5 5 8 10 15 20 25 40
    500V [kVar] 5 5 8 10 15 20 25 40
    690V [kVar] 5 5 8 10 15 20 25 40
    1000V [kVar]
        60 °C 230V [kVar] 5 5 8 9 12.5 12.5 18 28
    240V [kVar] 5 5 8 9 12.5 12.5 18 29
    400V [kVar] 5 5 8 10 15 20 25 40
    415V [kVar] 5 5 8 10 15 20 25 40
    500V [kVar] 5 5 8 10 15 20 25 40
    690V [kVar] 5 5 8 10 15 20 25 40
    1000V [kVar]
    60 Hz Single Capacitor — 40 °C
      200V [kVar] 5 5 8 9 12.5 14 20 28
    230V [kVar] 5 5 8 9 12.5 14 20 29
    460V [kVar] 5 5 8 10 15 20 25 40
    600V [kVar] 5 5 8 10 15 20 25 40
    60 Hz Group Capacitors — 40 °C
      200V [kVar] 5 5 8 9 12.5 12.5 18 28
    230V [kVar] 5 5 8 9 12.5 12.5 18 29
    460V [kVar] 5 5 8 10 15 20 25 40
    600V [kVar] 5 5 8 10 15 20 25 40
    Switching of Lamps
    Gas discharge lamps AC-5a, 40 °C open [A] 18 18 18 22.5 25 28 29 40.5 45 65 65 77 81
      enclosed [A] 14.5 14.5 14.5 22.5 25 28 29 37 41 54 54 57 77
    Individually compensated:
    Max. capacitance at expected
    Short-circuit current of 10 kA [mF] 750 750 750 1 000 1 000 1 000 1 000 2 700 2 700 3 200 4 000
    20 kA [mF] 400 400 400 500 500 500 500 1 350 1 350 1 600 2 000
    50 kA [mF] 200 200 200 200 540 540 640 800
    Filament AC-5b 230/240V [A] 5 9 9 12 16 18 22 30 37 18 25 43 60
    Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)
    AC-7a 230V [A] 20 20 20 32 32 32 32 45 45 63
    400V [A] 20 20 20 32 32 32 32 45 45 63
    440V [A] 32 32 32 32 45 45 63
    Switching of Motor Load for Home Appliances (50 Hz)
    AC-7b 230V [A] 6 11 11 10.5 14 19 23 30
    400V [A] 6 11 11 9 12 16 20 30
    440V [A] 7.5 10 13.5 18 27
      
    ¬ Inductance of leads between capacitors in parallel: min. 6 mH (100-C09…C30 contactors: min 30 mH)

      100/104-C, 100S/104S-C 100/104-D, 100S-D
    72 85 90*200 90*400 95 110 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X X X
    Electronic — EI X X X X X X X X X X
    Switching of 3-phase Capacitors, AC-6b (50 Hz) Electronic — EI Switching of 3-phase Capacitors, AC-6b (50 Hz)
    Single capacitor 40°C 230V [kVar] 28 28 45 45 70 70 70 70 98 98 125 139
    240V [kVar] 29 29 47 47 73 73 73 73 102 102 131 145
    400V [kVar] 48 48 78 78 121 121 121 121 170 170 218 242
    415V [kVar] 50 50 81 81 126 126 126 126 176 176 226 252
    500V [kVar] 55 60 97 97 152 152 152 152 212 212 273 303
    690V [kVar] 55 60 134 134 209 209 209 209 293 293 376 418
    1000V [kVar] 194 194 303 303 303 303 424 424 546 606
        60 °C 230V [kVar] 28 28 38 38 59 59 59 59 84 84 106 119
    240V [kVar] 29 29 39 39 61 61 61 61 87 87 111 124
    400V [kVar] 48 48 65 65 102 102 102 102 145 145 184 206
    415V [kVar] 50 50 68 68 106 106 106 106 151 151 191 214
    500V [kVar] 50 55 82 82 127 127 127 127 182 182 230 258
    690V [kVar] 50 55 113 113 176 176 176 176 251 251 318 356
    1000V [kVar] 164 164 255 255 255 255 364 364 461 515
    Group capacitors 40°C 230V [kVar] 28 28 42 45 70 70 70 70 98 98 125 139
    240V [kVar] 29 29 43 47 73 73 73 73 102 102 131 145
    400V [kVar] 48 48 44 56 76 76 111 111 170 170 218 242
    415V [kVar] 50 50 44 56 76 76 112 112 170 176 226 252
    500V [kVar] 50 50 44 56 76 76 113 113 172 212 273 303
    690V [kVar] 50 50 45 57 78 78 114 114 174 247 356 418
    1000V [kVar] 46 58 79 79 116 116 177 251 361 606
        60°C 230V [kVar] 28 28 38 38 59 59 59 59 84 84 106 119
    240V [kVar] 29 29 39 39 61 61 61 61 87 87 111 124
    400V [kVar] 48 48 44 56 76 76 102 102 145 145 184 206
    415V [kVar] 50 50 44 56 76 76 106 106 151 151 191 214
    500V [kVar] 50 50 44 56 76 76 113 113 172 182 230 258
    690V [kVar] 50 50 45 57 78 78 114 114 174 247 318 356
    1000V [kVar] 46 58 79 79 116 116 177 251 361 515
    60 Hz Single Capacitor — 40 °C Electronic — EI 60 Hz Single Capacitor — 40 °C
      200V [kVar] 28 28 39 39 61 61 61 61 85 85 109 121
    230V [kVar] 29 29 45 45 70 70 70 70 98 98 125 139
    460V [kVar] 50 50 89 89 139 139 139 139 195 195 251 279
    600V [kVar] 50 50 116 116 182 182 182 182 255 255 327 364
    60 Hz Group Capacitors — 40 °C Electronic — EI 60 Hz Group Capacitors — 40 °C
      200V [kVar] 28 28 39 39 61 61 61 61 85 85 109 121
    230V [kVar] 29 29 42 45 70 70 70 70 98 98 125 139
    460V [kVar] 50 50 44 56 76 76 112 112 171 195 251 279
    600V [kVar] 50 50 45 57 77 77 114 114 173 246 327 364
    Switching of Lamps Electronic — EI Switching of Lamps
    Gas discharge lamps AC-5a, 40 °C open [A] 85 90 115 115 144 144 225 225 225 225 315 315 405 450
    enclosed [A] 81 90 95 95 122 122 189 189 189 189 270 270 342 383
    Individually compensated: 460V [A] Individually compensated:
    Max. capacitance at expected 575V [A] Max. capacitance at expected
    Short-circuit current of 10 kA [mF] 4 000 4 700
    20 kA [mF] 2 000 2 350
    50 kA [mF] 800 940
    Filament AC-5b 230/240V [A] 70 76 60 75 107 120 140 140 170 170 210 250 300 420
    Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz) Electronic — EI Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)
    AC-7a 230V [A]
    400V [A]
    440V [A]
    Switching of Motor Load for Home Appliances (50 Hz) Electronic — EI Switching of Motor Load for Home Appliances (50 Hz)
    AC-7b 230V [A]
    400V [A]
    440V [A]
         

      100/104-K 100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
    Coil Type : Conventional X X X X X X X X X X X X X
    Electronic — EI
    Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)
    AC-8a 400V [A] 11 18 18 12 16 22 32 38 45 63 72
    500V [A] 10 15 15 12 16 22 32 38 45 63 72
    690V [A] 8 10 14 20 28 35 42 56
    - automatic reset of overload release
    AC-8b 400V [A] 5.5 7 9.3 12 13 14 16 24
    500V [A] 5.5 7 9.3 12 13 14 16 24
    690V [A] 5.5 7 9.3 12 13 14 16 24
    Switching of DC Loads
    Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C
        1 pole 24V [A] 6 9 9 25 25 32 32 45 45 45 45 50 70
    48/60V [A] 4/1 6/1.5 6/1.5 20 20 20 20 25 25 25 25 30 40
    110V [A] 0.6 1 1 6 6 6 6 8 8 10 10 9 11
    220V [A] 0.2 0.3 0.3 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2
    440V [A] 0.08 0.1 0.1 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.5
        2 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 45 45 50 70
    48/60V [A] 6 8 8 25 25 32 32 45 45 45 45 50 70
    110V [A] 4 6 6 25 25 32 32 45 45 45 45 50 70
    220V [A] 0.8 1.2 1.2 8 8 8 10 10 10 10 10 10 15
    440V [A] 0.2 0.3 0.3 1 1 1 1 1 1 1 1 1 1.5
        3 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 45 63 90
    48/60V [A] 6 9 9 25 25 32 32 45 45 45 63 90
    110V [A] 6 9 9 25 25 32 32 45 45 45 63 90
    220V [A] 3 4 4 25 25 32 32 45 45 45 50 70
    440V [A] 0.4 0.6 0.6 3 3 3 3 3.5 3.5 3.5 4 5
    Shunt-wound Motors
    Starting, reverse current braking, reversing, stepping DC-3, 60 °C
        3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 90
    48/60V [A] 4 6 6 25 25 32 32 45 45 50 70
    110V [A] 2 3 3 20 20 25 25 30 30 35 70
    220V [A] 0.8 1.2 1.2 6 6 6 10 15 15 20 25
    440V [A] 0.15 0.2 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
    Series-wound Motors
    Starting, reverse current braking, reversing, stepping DC-5, 60 °C
        3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 90
    48/60V [A] 2 3 3 25 25 32 32 45 45 50 70
    110V [A] 0.6 1 1 20 20 25 25 30 30 35 70
    220V [A] 0.1 0.1 0.1 6 6 6 10 15 15 20 25
    440V [A] 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
    Short Time Withstand ICW, 60 °C
      10 s [A] 60 96 96 170 170 170 215 300 304 304 304 375 700
    Resistance and Power Dissipation
    Main current circuit resistance [mW] 2.2 2.2 2.2 2.7 2.7 2.7 2 2 2 2 1.5 1.5 0.9
    Power dissipation by all circuits at
    Ie AC-3/400V
    [W] 0.3 0.9 0.9 0.66 1.2 2.1 3.2 5.4 8.2 11.3 8.4 8.3 9.7
    Total power dissipation
    At Ie AC-3/400V AC control [W] 2.1 2.7 2.7 3.3 3.8 4.7 6.2 8.4 11.2 26.1 37.4 11.5 11
    DC control [W] 2.9 3.5 3.5 6.7 7.2 8.1 12.4 14.6 17.4 32.6 43.9 18.4 11
    Lifespan
    Mechanical AC control [Mil. operations] 15 15 15 13 13 13 13 13 13 10 10 12 10
    Mechanical DC control [Mil. operations] 15 15 15 13 13 13 13 13 13 10 10 13 10
    Electrical AC-3 (400 V) [Mil. operations] 0.7 0.7 0.7 1.3 1.3 1.3 1.3 1.3 1.3 1 1
    Weight
    AC Non-Reversing kg (lbs.) 0.16 (0.35) 0.16 (0.35) 0.16 (0.35) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.48 (1.06) 0.49 (1.08) 0.51 (1.12) 1.45 (3.20)
    Reversing kg (lbs.) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 1.08 (2.39) 1.08 (2.39) 1.15 (2.54) 3.14 (6.92)
    DC Non-Reversing kg (lbs.) 0.2 (0.44) 0.2 (0.44) 0.2 (0.44) 0.6 (1.32) 0.6 (1.32) 0.6 (1.32) 0.73 (1.61) 0.85 (1.87) 0.85 (1.87) 1.0 (2.20) 1.47 (3.24)
    Reversing kg (lbs.) 1.27 (2.81) 1.27 (2.81) 1.27 (2.81) 1.53 (3.39) 1.81 (4.0) 1.81 (4.0) 2.13 (4.7) 3.22 (7.1)
      

      100/104-C, 100S/104S-C 100-D, 100S-D
    72 85 90*200 90*400 95 110 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X X X
    Electronic — EI X X X X X X X X X X
    Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz) Electronic — EI Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)
    AC-8a 400V [A] 85 100
    500V [A] 85 100
    690V [A] 67 80
    - automatic reset of overload release Electronic — EI - automatic reset of overload release
    AC-8b 400V [A] 30 35
    500V [A] 30 35
    690V [A] 30 35
    Switching of DC Loads Switching of DC Loads
    Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C Electronic — EI  
        1 pole 24V [A] 80 80 80 80 135 135 210 210 210 210 300 300 380 425
    48/60V [A] 40 40 40 40 135 135 210 210 210 210 300 300 380 425
    110V [A] 11 11 11 11 135 135 210 210 210 210 300 300 380 425
    220V [A] 2 2 1.8 1.8 3 3 3.3 3.3 3.3 3.3 4.9 4.9 4.9 5.2
    440V [A] 0.5 0.5 0.5 0.5 0.6 0.6 0.75 0.75 0.75 0.75 1 1 1 1.2
        2 poles in series