Enclosed Starters

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Enclosed Starters > Bulletin 132/133-C IEC Pump Control Panels

Bulletin 132/133-C IEC Pump Control Panels

Introduction Standards Compliance and Certifications Product Selection Bulletin 100 Line Starter Accessories Modifications Bul. 100 Line Starters Approximate Dimensions
Product Selection

Fusible Disconnect Type

Ratings (AC3, AC4) Fuse Clip Rating
Amperes/UL Class
IP32 (Type 3R) Sleet Resistant, Outdoor Sheet Metal Enclosure (Hinged Cover)
Max Ie
[A]
kW Hp
3-Phase 3-Phase
380/415V 200V 230V 460V 575V Cat. No.
9 4 2 2 5 7-1/2 30 A/Class CC 132-C09Mĵ
12 5-1/2 3 3 7-1/2 10 30 A/Class J 132-C12Mĵ
23 11 5 7-1/2 15 15 30 A/Class J 132-C23Mĵ
30 15 7-1/2 10 20 25 60 A/Class J 132-C30Mĵ
43 22 10 15 30 30 60 A/Class J 132-C43Mĵ
60 30 15 20 40 50 100 A/Class J 132-C60Mĵ
72 37 20 25 50 60 100 A/Class J 132-C72Mĵ
  

Ä Coil Voltage Code—see Ä Coil Voltage Code


µ Overload Relay Code—see µ Overload Relay Code


Circuit Breaker Type

Ratings (AC3, AC4) IP32 (Type 3R) Sleet Resistant, Outdoor Sheet Metal Enclosure (Hinged Cover)
Max. Ie
[A]
Hp⋆ 
3Æ
200V 230V 460V 575V Cat. No.
30 1/2 1/2 133-C30Mĵ-33
3/4…1 3/4…1 1/2…1 133-C30Mĵ-35
1/2…1-1/2 133-C30Mĵ-36
1-1/2…3 1-1/2…3 1-1/2…3 2…3 133-C30Mĵ-38
5 133-C30Mĵ-39
7-1/2 5…7-1/2 5…7-1/2 133-C30Mĵ-40
10 5…10 133-C30Mĵ-41
10 133-C30Mĵ-42
20 15…20 133-C30Mĵ-43
25 133-C30Mĵ-44
43 7-1/2…10 10 133-C43Mĵ-41
15 133-C43Mĵ-42
20…25 133-C43Mĵ-44
30 25…30 133-C43Mĵ-45
60 15 133-C60Mĵ-42
15…20 133-C60Mĵ-43
40 40 133-C60Mĵ-46
72 15…20 133-C72Mĵ-43
20…25 133-C72Mĵ-44
40…50 133-C72Mĵ-47
40…60 133-C72Mĵ-48
  

Ä Coil Voltage Code

The Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No. Example: Cat. No. 132-C12Mĵ becomes Cat. No. 132-C12MBµ

Voltage [V] 208 230…240 460…480 575…600
Common Control‡ 
Coil Voltage Suffix Code
60 Hz H A B C
120V Separate Control (without transformer)
Coil Voltage Suffix Code
AD AD CD CD
  

µ Overload Relay Code

The Cat. No. as listed is incomplete. Select an overload relay code from Bulletin 193 E1 Plus electronic overload relay for 3-phase applications:
Selectable Trip Class 10, 15, 20, 30, selectable manual/auto reset
to complete the Cat. No.


⋆ For horsepower ratings less than those shown, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
‡ When selecting a factory-installed control circuit transformer (see Modifications Full Voltage Non-Reversing Starters and Lighting Contactors (Bulletins 109 with metal enclosures, 100L)), use the Common Control Coil Voltage Code to denote the transformer primary voltage. The starter coil and transformer secondary voltage will both be 120V by default. Example: Cat. No. 132-C09MBµ-6P will have a transformer with a 480V primary/120V secondary and a 120V starter coil. If a starter coil voltage other than 120V is desired, a second Coil Voltage Code must be added to denote the coil/transformer secondary voltage. Example: Cat. No. 132-C09MBJµ-6P will have a transformer with a 480V primary/24V secondary and a 24V starter coil.