Bulletin 103H/107H/140M Enclosed Combination Starters and Motor Protectors
|
|
| Bulletin 103H starter in enclosure size A | Bulletin 107H starter in enclosure size C |
Bulletin 103H/107H/140M Enclosed Combination Starters and Motor Protectors
Bulletin 103H/107H enclosed combination starters consist of a Bulletin 140M motor protection circuit breaker and a Bulletin 100C/104C contactor in a metallic Type 3/4/12 enclosure.
Bulletin 140M enclosed motor protection circuit breakers consist of a Bulletin 140M motor protection circuit breaker in a metallic Type 3/4/12 enclosure.
Features
- Current range 0.1…45 A
- cULus Listed for control and protection of motor loads
- Motor disconnect
- Short-circuit and overload protection
- Motor switching (magnetic)
- Motor disconnect
- Factory-installed options include
- Pushbuttons, selector switches, and pilot lights
- Control transformer
- Auxiliary and trip indication contacts
- Pushbuttons, selector switches, and pilot lights
Standards Compliance and Certifications
Standards Compliance
UL 508
CSA 22.2 No. 14
Certifications
cULus Listed (File No. E 125316, Guide NKJH, NKJH7)
Product Selection
Reversing and Non-reversing Starters
|
|
|
Type E and Type F Combination Motor Controllers (UL/CSA)
Most of the 140M-C/D motor protection circuit breakers used in the 103H/107H starters are UL Listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass is to perform 6000 electrical ops. and an additional 4000 mechanical ops. after a short circuit.
By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits.
A combination of a Bulletin 140M manual self-protected combination motor controller and 100-C contactor can be listed as a Type E self-protected combination motor controller. In this case, the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require oversizing of the 140M motor protection circuit breaker or the 100-C contactor to achieve weld-free performance and meet the additional life requirements.
Product Selection and Coordination Ratings (UL/CSA as a UL508 Type F Combination Motor Controller)
| Motor Current Adjustment Range [A] | Hp Ratings as a UL508 Type F Combination Motor Controller⋆ | Max. Short-Circuit Current [kA] | Non-Reversing Starter Cat. No. |
Enclosure Size | Reversing Starter Cat. No. |
Enclosure Size | ||||||
| Type 1 Coordination | Type 2 Coordination | |||||||||||
| 200V | 230V | 460V | 575V | 480Y/277V | 600Y/347V | 480Y/277V | 600Y/347V | |||||
| 25 A Frame Size | ||||||||||||
| 0.10…0.16 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA16X | A | 107H-AFµÄ3-CA16X | B |
| 0.16…0.25 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA25X | A | 107H-AFµÄ3-CA25X | B |
| 0.25…0.40 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA40X | A | 107H-AFµÄ3-CA40X | B |
| 0.40…0.63 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA63X | A | 107H-AFµÄ3-CA63X | B |
| 0.63…1.00 | — | — | 1/2 | 3/4 | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CB10X | A | 107H-AFµÄ3-CB10X | B |
| 1.00…1.60 | — | — | 1/2…1 | 3/4...1 | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CB16X | A | 107H-AFµÄ3-CB16X | B |
| 1.60…2.50 | 1/2 | 1/2...3/4 | 3/4…1-1/2 | 1…2 | 65 | 30 | 65 | 10 | 103H-AFµÄ2-DB25X | A | 107H-AFµÄ3-DB25X | B |
| 2.50…4.00 | 1/2…1 | 3/4...1 | 1-1/2…3 | 2…3 | 65 | 30 | 65 | — | 103H-AFµÄ2-DB40X | A | 107H-AFµÄ3-DB40X | B |
| 2.50…4.00 | 1/2…1 | 3/4...1 | 1-1/2…3 | 2…3 | 65 | 30 | 65 | 30 | 103H-DFµÄ2-DB40X | A | 107H-DFµÄ3-DB40X | B |
| 4.00…6.30 | 1…1-1/2 | 1…2 | 3…5 | 5 | 65 | 30 | 65 | — | 103H-AFµÄ2-DB63X | A | 107H-AFµÄ3-DB63X | B |
| 4.00…6.30 | 1…1-1/2 | 1…2 | 3…5 | 5 | 65 | 30 | 65 | 30 | 103H-EFµÄ2-DB63X | C | 107H-EFµÄ3-DB63X | C |
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 65 | — | 103H-BFµÄ2-DC10X | A | 107H-BFµÄ3-DC10X | B |
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 65 | 30 | 103H-EFµÄ2-DC10X | C | 107H-EFµÄ3-DC10X | C |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 65 | — | 103H-CFµÄ2-DC16X | A | 107H-CFµÄ3-DC16X | B |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 65 | 30 | 103H-EFµÄ2-DC16X | C | 107H-EFµÄ3-DC16X | C |
| 14.5…20.0 | 5 | 5 | 10 | — | 65 | & | 65 | & | 103H-DFµÄ2-DC20X | A | 107H-DFµÄ3-DC20X | B |
| 18.0…23.0 | 5 | 7-1/2 | 15 | — | 65 | & | 65 | & | 103H-DFµÄ2-DC25X | A | 107H-DFµÄ3-DC25X | C |
| 45 A Frame Size | ||||||||||||
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC10X | C | 107H-EFµÄ3-FC10X | C |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC16X | C | 107H-EFµÄ3-FC16X | C |
| 14.5…20.0 | 5 | 5…7-1/2 | 15 | 15…20 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC20X | C | 107H-EFµÄ3-FC20X | C |
| 18.0…25.0 | 7-1/2 | 7-1/2...10 | 15...20 | 20 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC25X | C | 107H-EFµÄ3-FC25X | C |
| 23.0…32.0 | 7-1/2...10 | 10 | 20...25 | 30 | 65 | 30 | 65 | 10 | 103H-FFµÄ2-FC32X | C | 107H-FFµÄ3-FC32X | C |
| 32.0…43.0 | 10 | 15 | 30 | — | 65 | & | 65 | & | 107H-GFµÄ3-FC45X | C | 107H-GFµÄ3-FC45X | C |
| µ Line Voltage Codes — see µ Line Voltage Codes | ||||||||||||
| Ä Coil Voltage Codes — see Ä Coil Voltage Codes | ||||||||||||
| ⋆ Hp ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current. & This starter is not valid for application at this horsepower and voltage. |
||||||||||||
Product Selection and Coordination Ratings (UL/CSA as a UL508 Self-Protected Type E Combination Motor Controller)
| Motor Current Adjustment Range [A] | UL/CSA Hp and Coordination Ratings (60 Hz) | Non-Reversing Starter Cat. No. |
Enclosure Size | Reversing Starter Cat. No. |
Enclosure Size | |||||
| Hp Ratings as a UL508 Self-Protected Type E Combination Motor Controller⋆ | Max. Short-Circuit Current [kA] | |||||||||
| 200V | 230V | 460V | 575V | 480Y/277V | 600Y/347V | |||||
| 25 A Frame Size | ||||||||||
| 0.10…0.16 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA16X | A | 107H-AFµÄ3-CA16X | B |
| 0.16…0.25 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA25X | A | 107H-AFµÄ3-CA25X | B |
| 0.25…0.40 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA40X | A | 107H-AFµÄ3-CA40X | B |
| 0.40…0.63 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA63X | A | 107H-AFµÄ3-CA63X | B |
| 0.63…1.00 | — | — | 1/2 | 3/4 | 65 | 47 | 103H-AFµÄ2-CB10X | A | 107H-AFµÄ3-CB10X | B |
| 1.00…1.60 | — | — | 1/2…1 | 3/4...1 | 65 | 47 | 103H-AFµÄ2-CB16X | A | 107H-AFµÄ3-CB16X | B |
| 1.60…2.50 | 1/2 | 1/2...3/4 | 3/4…1-1/2 | — | 65 | & | 103H-AFµÄ2-DB25X | A | 107H-AFµÄ3-DB25X | B |
| 1.60…2.50 | 1/2 | 1/2...3/4 | 3/4…1-1/2 | 1…2 | 65 | 30 | 103H-DFµÄ2-DB25X | A | 107H-DFµÄ3-DB25X | B |
| 2.50…4.00 | — | — | — | — | & | & | 103H-AFµÄ2-DB40X | A | 107H-AFµÄ3-DB40X | B |
| 2.50…4.00 | 1/2…1 | 3/4...1 | 1-1/2…3 | 2…3 | 65 | 30 | 103H-DFµÄ2-DB40X | A | 107H-DFµÄ3-DB40X | B |
| 4.00…6.30 | — | — | — | — | & | & | 103H-AFµÄ2-DB63X | A | 107H-AFµÄ3-DB63X | B |
| 4.00…6.30 | 1…1-1/2 | 1…2 | 3…5 | 5 | 65 | 30 | 103H-EFµÄ2-DB63X | C | 107H-EFµÄ3-DB63X | C |
| 6.30…10.0 | — | — | — | — | & | & | 103H-BFµÄ2-DC10X | A | 107H-BFµÄ3-DC10X | B |
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 103H-EFµÄ2-DC10X | C | 107H-EFµÄ3-DC10X | C |
| 10.0…16.0 | — | — | — | — | & | & | 103H-CFµÄ2-DC16X | A | 107H-CFµÄ3-DC16X | B |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 103H-EFµÄ2-DC16X | C | 107H-EFµÄ3-DC16X | C |
| 14.5…20.0 | — | — | — | — | & | & | 103H-DFµÄ2-DC20X | A | 107H-DFµÄ3-DC20X | B |
| 14.5…20.0 | 5 | 5 | 10 | — | 65 | & | 103H-EFµÄ2-DC20X | C | 107H-EFµÄ3-DC20X | C |
| 18.0…23.0 | — | — | — | — | & | & | 103H-DFµÄ2-DC25X | A | 107H-DFµÄ3-DC25X | C |
| 18.0…23.0 | 5 | 7-1/2 | 15 | — | 65 | & | 103H-EFµÄ2-DC25X | C | 107H-EFµÄ3-DC25X | C |
| 45 A Frame Size | ||||||||||
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 103H-EFµÄ2-FC10X | C | 107H-EFµÄ3-FC10X | C |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 103H-EFµÄ2-FC16X | C | 107H-EFµÄ3-FC16X | C |
| 14.5…20.0 | 5 | 5…7-1/2 | 15 | 15…20 | 65 | 30 | 103H-EFµÄ2-FC20X | C | 107H-EFµÄ3-FC20X | C |
| 18.0…25.0 | 7-1/2 | 7-1/2...10 | 15...20 | 20 | 65 | 30 | 103H-EFµÄ2-FC25X | C | 107H-EFµÄ3-FC25X | C |
| 23.0…32.0 | 7-1/2...10 | 10 | 20...25 | 30 | 65 | 30 | 103H-FFµÄ2-FC32X | C | 107H-FFµÄ3-FC32X | C |
| 32.0…43.0 | 10 | 15 | 30 | — | 65 | & | 103H-GFµÄ2-FC45X | C | 107H-GFµÄ3-FC45X | C |
| µ Line Voltage Codes — see µ Line Voltage Codes | ||||||||||
| Ä Coil Voltage Codes — see Ä Coil Voltage Codes | ||||||||||
| ⋆ Hp ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current. & This starter is not valid for application at this horsepower and voltage. |
||||||||||
Enclosed Motor Protectors
- Self-protected UL Type E manual combination motor controller
- 65 kA at 480V
- 30 kA at 600V
- AC control
|
|
| Rated Operational Current [A] | Motor Current Adjustment Range [A] | Magnetic Trip Current [A] | Maximum Hp, 3-phase | Cat. No. | Enclosure Size | |||
| 200V | 230V | 460V | 575V | |||||
| 25 A Frame Size | ||||||||
| 0.16 | 0.10…0.16 | 2.1 | — | — | — | — | 140M-F-CA16X | A |
| 0.25 | 0.16…0.25 | 3.3 | — | — | — | — | 140M-F-CA25X | A |
| 0.4 | 0.25…0.40 | 5.2 | — | — | — | — | 140M-F-CA40X | A |
| 0.63 | 0.40…0.63 | 8.2 | — | — | — | — | 140M-F-CA63X | A |
| 1 | 0.63…1.0 | 13 | — | — | 0.5 | 0.75§ | 140M-F-CB10X | A |
| 1.6 | 1.0…1.6 | 21 | — | — | 1 | 1§ | 140M-F-CB16X | A |
| 2.5 | 1.6…2.5 | 33 | 0.5 | 0.75 | 1.5 | 2 | 140M-F-DB25X | A |
| 4 | 2.5…4.0 | 52 | 1 | 1 | 3 | 3 | 140M-F-DB40X | A |
| 6.3 | 4.0…6.3 | 82 | 1.5 | 2 | 5 | 5 | 140M-F-DB63X | A |
| 10 | 6.3…10 | 130 | 3 | 3 | 7.5 | 10 | 140M-F-DC10X | A |
| 16 | 10…16 | 208 | 3 | 5 | 10 | 15 | 140M-F-DC16X | A |
| 20 | 14.5…20 | 260 | 5 | 7.5 | 15 | — | 140M-F-DC20X | A |
| 45 A Frame Size | ||||||||
| 10 | 6.3…10 | 130 | 3 | 3 | 7.5 | 10 | 140M-F-FC10X | C |
| 16 | 10…16 | 208 | 3 | 5 | 10 | 15 | 140M-F-FC16X | C |
| 20 | 14.5…20 | 260 | 5 | 7.5 | 15 | 20 | 140M-F-FC20X | C |
| 25 | 18…25 | 325 | 7.5 | 10 | 20 | 25 | 140M-F-FC25X | C |
| 32 | 23…32 | 416 | 10 | 10 | 25 | 30 | 140M-F-FC32X | C |
| 45 | 32…45 | 585 | 15 | 15 | 30 | — | 140M-F-FC45X | C |
| ⋆ 30 kA § 47 kA |
||||||||
Modifications
Bulletin 103H/107H Factory Installed Modifications
Note:For modifications add (option code ♣ ) for desired features to cat. no.
♣ Add desired option codes. Example: 103H-AND2-CA16X-KY
| Coil Options | |
| JE⋆ | Electronic Interfaces (100-C) |
| R⋆ | Surge Suppressor RC (100-C) |
| V⋆ | Surge Suppressor Varistor (100-C) |
| D⋆ | Surge Suppressor Diode (100-C) |
| Additional Contactor Auxiliaries (Side Mount) | |
| S01⋆ | 1 N.C. |
| S10⋆ | 1 N.O. |
| S11⋆ | 1 N.O. + 1 N.C. |
| S20⋆ | 2 N.O. |
| Additional 140M Auxiliaries (Side Mount) | |
| A02 | 2 N.C. |
| A20 | 2 N.O. |
| A11 | 1 N.O. + 1 N.C. |
| Additional 140M Trip Contacts (Side Mount) | |
| R00 | 1 N.O. Thermal-Mag + 1 N.O. Mag Only |
| R01 | 1 N.O. Thermal-Mag + 1 N.C. Mag Only |
| R10 | 1 N.C. Thermal-Mag + 1 N.O. Mag Only |
| R11 | 1 N.C. Thermal-Mag + 1 N.C. Mag Only |
| M11 | 1 N.O. Mag Only + 1 N.C. Mag Only |
| Control Options | |
| 1 | Push Button — 103H Start-Stop / 107H For-Rev-Stop |
| 1M | Multifunction Push Button — 103H Start-Stop / 107H For-Rev-Stop |
| 14RM | Multifunction Push Button — 103H Start-Stop-Pilot Light |
| 3 | Selector Switch — 103H Hand-Off-Auto / 107H For-Off-Rev |
| 4R | Pilot Light (red, ON) (103H only) |
| 4RW | Pilot Light (red—FOR, White — REV) (107H only) |
| 6P § | Control Transformer§ (not available with enclosure size A) |
| KY | Bulletin 140M External Handle — Red/Yellow |
⋆ 107H - One per contactor, for a total of two per option code.
Starters in enclosure size "A" will change to enclosure size "B" when a control transformer is factory installed.
§ Auxiliary contacy option "A20" is required when seelcting this control transformer.
140M Factory Installed Modifications (Enclosed)
Note:For modifications add (option code ♣ ) for desired features to cat. no.
♣ Add desired option codes. Example: 140M-F-CA16X-UVB
| Modifications | |
| UVÄ | Undervoltage Trip |
| SNÄ | Shunt Trip |
| Additional 140M Auxiliaries (Side Mount) | |
| A02 | 2 N.C. |
| A20 | 2 N.O. |
| A11 | 1 N.O. + 1 N.C. |
| Additional 140M Trip Contacts (Side Mount) | |
| R00 | 1 N.O. Thermal-Mag + 1 N.O. Mag Only |
| R01 | 1 N.O. Thermal-Mag + 1 N.C. Mag Only |
| R10 | 1 N.C. Thermal-Mag + 1 N.O. Mag Only |
| R11 | 1 N.C. Thermal-Mag + 1 N.C. Mag Only |
| M11 | 1 N.O. Mag Only + 1 N.C. Mag Only |
Line and Coil Voltage Codes
µ Line Voltage Codes
The Cat. No. as listed is incomplete. Select a line voltage code from the table below to complete the Cat. No.
Example: 208V 60 Hz: Cat. No. 103H-AFµÄ2-CA16X becomes Cat. No. 103H-AFHÄ2-CA16X.
| Line Voltages [V] | 208 | 230 | 240 | 380 | 400 | 415 | 480 | 600 |
| 60 Hz | H | — | A | — | — | — | B | C |
| 50 Hz | — | F | — | N | KN | G | — | — |
Ä Coil Voltage Codes
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No.
Example: 120V 60 Hz: Cat. No. 103H-AFHÄ-CA16X becomes Cat. No. 103H-AFHD2-CA16X.
| Standard Coil Voltages [V] |
24 | 110 | 120 | 208 | 220…230 | 240…260 | 277 | 380…400 | 415 | 480 | 600 |
| AC, 50 Hz | K | D | P | — | F | — | — | N | B | — | — |
| AC, 60 Hz | J | — | D | H | — | A | T | — | — | B | C |
| AC, 50/60 Hz | KJ | KD | — | — | — | — | — | — | — | — | — |
| Standard Coil Voltages [V] |
24 | |
| DC | Standard | ZJ |
| With integrated diode | KJ | |
Wiring Diagram
Cat. No. 103H-AFBD2-DB40X-1-4R-6P
|
|
Cat. No. 107H-AFBD3-CA16X-1M-4RW-6P
|
|
Enclosure Dimensions
Dimensions in mm. Dimensions are not intended to be used for manufacturing purposes.
Enclosure Style A
|
|
Enclosure Style B
|
|
Enclosure Style C
|
|