Catalogs > Industrial Controls Catalog > Motor Control, IEC > Enclosed Starters > Bulletin 103H/107H/140M Enclosed Combination Starters and Motor Protectors
Bulletin 103H/107H/140M Enclosed Combination Starters and Motor Protectors
| Introduction | Features | Standards Compliance and Certifications | Product Selection | Modifications | Wiring Diagram | Enclosure Dimensions |
Reversing and Non-reversing Starters
|
|
|
Type E and Type F Combination Motor Controllers (UL/CSA)
Most of the 140M-C/D motor protection circuit breakers used in the 103H/107H starters are UL Listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass is to perform 6000 electrical ops. and an additional 4000 mechanical ops. after a short circuit.
By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits.
A combination of a Bulletin 140M manual self-protected combination motor controller and 100-C contactor can be listed as a Type E self-protected combination motor controller. In this case, the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require oversizing of the 140M motor protection circuit breaker or the 100-C contactor to achieve weld-free performance and meet the additional life requirements.
Product Selection and Coordination Ratings (UL/CSA as a UL508 Type F Combination Motor Controller)
| Motor Current Adjustment Range [A] | Hp Ratings as a UL508 Type F Combination Motor Controller⋆ | Max. Short-Circuit Current [kA] | Non-Reversing Starter Cat. No. |
Enclosure Size | Reversing Starter Cat. No. |
Enclosure Size | ||||||
| Type 1 Coordination | Type 2 Coordination | |||||||||||
| 200V | 230V | 460V | 575V | 480Y/277V | 600Y/347V | 480Y/277V | 600Y/347V | |||||
| 25 A Frame Size | ||||||||||||
| 0.10…0.16 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA16X | A | 107H-AFµÄ3-CA16X | B |
| 0.16…0.25 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA25X | A | 107H-AFµÄ3-CA25X | B |
| 0.25…0.40 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA40X | A | 107H-AFµÄ3-CA40X | B |
| 0.40…0.63 | — | — | — | — | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CA63X | A | 107H-AFµÄ3-CA63X | B |
| 0.63…1.00 | — | — | 1/2 | 3/4 | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CB10X | A | 107H-AFµÄ3-CB10X | B |
| 1.00…1.60 | — | — | 1/2…1 | 3/4...1 | 65 | 47 | 65 | 47 | 103H-AFµÄ2-CB16X | A | 107H-AFµÄ3-CB16X | B |
| 1.60…2.50 | 1/2 | 1/2...3/4 | 3/4…1-1/2 | 1…2 | 65 | 30 | 65 | 10 | 103H-AFµÄ2-DB25X | A | 107H-AFµÄ3-DB25X | B |
| 2.50…4.00 | 1/2…1 | 3/4...1 | 1-1/2…3 | 2…3 | 65 | 30 | 65 | — | 103H-AFµÄ2-DB40X | A | 107H-AFµÄ3-DB40X | B |
| 2.50…4.00 | 1/2…1 | 3/4...1 | 1-1/2…3 | 2…3 | 65 | 30 | 65 | 30 | 103H-DFµÄ2-DB40X | A | 107H-DFµÄ3-DB40X | B |
| 4.00…6.30 | 1…1-1/2 | 1…2 | 3…5 | 5 | 65 | 30 | 65 | — | 103H-AFµÄ2-DB63X | A | 107H-AFµÄ3-DB63X | B |
| 4.00…6.30 | 1…1-1/2 | 1…2 | 3…5 | 5 | 65 | 30 | 65 | 30 | 103H-EFµÄ2-DB63X | C | 107H-EFµÄ3-DB63X | C |
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 65 | — | 103H-BFµÄ2-DC10X | A | 107H-BFµÄ3-DC10X | B |
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 65 | 30 | 103H-EFµÄ2-DC10X | C | 107H-EFµÄ3-DC10X | C |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 65 | — | 103H-CFµÄ2-DC16X | A | 107H-CFµÄ3-DC16X | B |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 65 | 30 | 103H-EFµÄ2-DC16X | C | 107H-EFµÄ3-DC16X | C |
| 14.5…20.0 | 5 | 5 | 10 | — | 65 | & | 65 | & | 103H-DFµÄ2-DC20X | A | 107H-DFµÄ3-DC20X | B |
| 18.0…23.0 | 5 | 7-1/2 | 15 | — | 65 | & | 65 | & | 103H-DFµÄ2-DC25X | A | 107H-DFµÄ3-DC25X | C |
| 45 A Frame Size | ||||||||||||
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC10X | C | 107H-EFµÄ3-FC10X | C |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC16X | C | 107H-EFµÄ3-FC16X | C |
| 14.5…20.0 | 5 | 5…7-1/2 | 15 | 15…20 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC20X | C | 107H-EFµÄ3-FC20X | C |
| 18.0…25.0 | 7-1/2 | 7-1/2...10 | 15...20 | 20 | 65 | 30 | 65 | 10 | 103H-EFµÄ2-FC25X | C | 107H-EFµÄ3-FC25X | C |
| 23.0…32.0 | 7-1/2...10 | 10 | 20...25 | 30 | 65 | 30 | 65 | 10 | 103H-FFµÄ2-FC32X | C | 107H-FFµÄ3-FC32X | C |
| 32.0…43.0 | 10 | 15 | 30 | — | 65 | & | 65 | & | 107H-GFµÄ3-FC45X | C | 107H-GFµÄ3-FC45X | C |
| µ Line Voltage Codes — see µ Line Voltage Codes | ||||||||||||
| Ä Coil Voltage Codes — see Ä Coil Voltage Codes | ||||||||||||
| ⋆ Hp ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current. & This starter is not valid for application at this horsepower and voltage. |
||||||||||||
Product Selection and Coordination Ratings (UL/CSA as a UL508 Self-Protected Type E Combination Motor Controller)
| Motor Current Adjustment Range [A] | UL/CSA Hp and Coordination Ratings (60 Hz) | Non-Reversing Starter Cat. No. |
Enclosure Size | Reversing Starter Cat. No. |
Enclosure Size | |||||
| Hp Ratings as a UL508 Self-Protected Type E Combination Motor Controller⋆ | Max. Short-Circuit Current [kA] | |||||||||
| 200V | 230V | 460V | 575V | 480Y/277V | 600Y/347V | |||||
| 25 A Frame Size | ||||||||||
| 0.10…0.16 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA16X | A | 107H-AFµÄ3-CA16X | B |
| 0.16…0.25 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA25X | A | 107H-AFµÄ3-CA25X | B |
| 0.25…0.40 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA40X | A | 107H-AFµÄ3-CA40X | B |
| 0.40…0.63 | — | — | — | — | 65 | 47 | 103H-AFµÄ2-CA63X | A | 107H-AFµÄ3-CA63X | B |
| 0.63…1.00 | — | — | 1/2 | 3/4 | 65 | 47 | 103H-AFµÄ2-CB10X | A | 107H-AFµÄ3-CB10X | B |
| 1.00…1.60 | — | — | 1/2…1 | 3/4...1 | 65 | 47 | 103H-AFµÄ2-CB16X | A | 107H-AFµÄ3-CB16X | B |
| 1.60…2.50 | 1/2 | 1/2...3/4 | 3/4…1-1/2 | — | 65 | & | 103H-AFµÄ2-DB25X | A | 107H-AFµÄ3-DB25X | B |
| 1.60…2.50 | 1/2 | 1/2...3/4 | 3/4…1-1/2 | 1…2 | 65 | 30 | 103H-DFµÄ2-DB25X | A | 107H-DFµÄ3-DB25X | B |
| 2.50…4.00 | — | — | — | — | & | & | 103H-AFµÄ2-DB40X | A | 107H-AFµÄ3-DB40X | B |
| 2.50…4.00 | 1/2…1 | 3/4...1 | 1-1/2…3 | 2…3 | 65 | 30 | 103H-DFµÄ2-DB40X | A | 107H-DFµÄ3-DB40X | B |
| 4.00…6.30 | — | — | — | — | & | & | 103H-AFµÄ2-DB63X | A | 107H-AFµÄ3-DB63X | B |
| 4.00…6.30 | 1…1-1/2 | 1…2 | 3…5 | 5 | 65 | 30 | 103H-EFµÄ2-DB63X | C | 107H-EFµÄ3-DB63X | C |
| 6.30…10.0 | — | — | — | — | & | & | 103H-BFµÄ2-DC10X | A | 107H-BFµÄ3-DC10X | B |
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 103H-EFµÄ2-DC10X | C | 107H-EFµÄ3-DC10X | C |
| 10.0…16.0 | — | — | — | — | & | & | 103H-CFµÄ2-DC16X | A | 107H-CFµÄ3-DC16X | B |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 103H-EFµÄ2-DC16X | C | 107H-EFµÄ3-DC16X | C |
| 14.5…20.0 | — | — | — | — | & | & | 103H-DFµÄ2-DC20X | A | 107H-DFµÄ3-DC20X | B |
| 14.5…20.0 | 5 | 5 | 10 | — | 65 | & | 103H-EFµÄ2-DC20X | C | 107H-EFµÄ3-DC20X | C |
| 18.0…23.0 | — | — | — | — | & | & | 103H-DFµÄ2-DC25X | A | 107H-DFµÄ3-DC25X | C |
| 18.0…23.0 | 5 | 7-1/2 | 15 | — | 65 | & | 103H-EFµÄ2-DC25X | C | 107H-EFµÄ3-DC25X | C |
| 45 A Frame Size | ||||||||||
| 6.30…10.0 | 1-1/2…3 | 2...3 | 5…7-1/2 | 7-1/2…10 | 65 | 30 | 103H-EFµÄ2-FC10X | C | 107H-EFµÄ3-FC10X | C |
| 10.0…16.0 | 3…5 | 5 | 7-1/2…10 | 10…15 | 65 | 30 | 103H-EFµÄ2-FC16X | C | 107H-EFµÄ3-FC16X | C |
| 14.5…20.0 | 5 | 5…7-1/2 | 15 | 15…20 | 65 | 30 | 103H-EFµÄ2-FC20X | C | 107H-EFµÄ3-FC20X | C |
| 18.0…25.0 | 7-1/2 | 7-1/2...10 | 15...20 | 20 | 65 | 30 | 103H-EFµÄ2-FC25X | C | 107H-EFµÄ3-FC25X | C |
| 23.0…32.0 | 7-1/2...10 | 10 | 20...25 | 30 | 65 | 30 | 103H-FFµÄ2-FC32X | C | 107H-FFµÄ3-FC32X | C |
| 32.0…43.0 | 10 | 15 | 30 | — | 65 | & | 103H-GFµÄ2-FC45X | C | 107H-GFµÄ3-FC45X | C |
| µ Line Voltage Codes — see µ Line Voltage Codes | ||||||||||
| Ä Coil Voltage Codes — see Ä Coil Voltage Codes | ||||||||||
| ⋆ Hp ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current. & This starter is not valid for application at this horsepower and voltage. |
||||||||||
Enclosed Motor Protectors
- Self-protected UL Type E manual combination motor controller
- 65 kA at 480V
- 30 kA at 600V
- AC control
|
|
| Rated Operational Current [A] | Motor Current Adjustment Range [A] | Magnetic Trip Current [A] | Maximum Hp, 3-phase | Cat. No. | Enclosure Size | |||
| 200V | 230V | 460V | 575V | |||||
| 25 A Frame Size | ||||||||
| 0.16 | 0.10…0.16 | 2.1 | — | — | — | — | 140M-F-CA16X | A |
| 0.25 | 0.16…0.25 | 3.3 | — | — | — | — | 140M-F-CA25X | A |
| 0.4 | 0.25…0.40 | 5.2 | — | — | — | — | 140M-F-CA40X | A |
| 0.63 | 0.40…0.63 | 8.2 | — | — | — | — | 140M-F-CA63X | A |
| 1 | 0.63…1.0 | 13 | — | — | 0.5 | 0.75§ | 140M-F-CB10X | A |
| 1.6 | 1.0…1.6 | 21 | — | — | 1 | 1§ | 140M-F-CB16X | A |
| 2.5 | 1.6…2.5 | 33 | 0.5 | 0.75 | 1.5 | 2 | 140M-F-DB25X | A |
| 4 | 2.5…4.0 | 52 | 1 | 1 | 3 | 3 | 140M-F-DB40X | A |
| 6.3 | 4.0…6.3 | 82 | 1.5 | 2 | 5 | 5 | 140M-F-DB63X | A |
| 10 | 6.3…10 | 130 | 3 | 3 | 7.5 | 10 | 140M-F-DC10X | A |
| 16 | 10…16 | 208 | 3 | 5 | 10 | 15 | 140M-F-DC16X | A |
| 20 | 14.5…20 | 260 | 5 | 7.5 | 15 | — | 140M-F-DC20X | A |
| 45 A Frame Size | ||||||||
| 10 | 6.3…10 | 130 | 3 | 3 | 7.5 | 10 | 140M-F-FC10X | C |
| 16 | 10…16 | 208 | 3 | 5 | 10 | 15 | 140M-F-FC16X | C |
| 20 | 14.5…20 | 260 | 5 | 7.5 | 15 | 20 | 140M-F-FC20X | C |
| 25 | 18…25 | 325 | 7.5 | 10 | 20 | 25 | 140M-F-FC25X | C |
| 32 | 23…32 | 416 | 10 | 10 | 25 | 30 | 140M-F-FC32X | C |
| 45 | 32…45 | 585 | 15 | 15 | 30 | — | 140M-F-FC45X | C |
| ⋆ 30 kA § 47 kA |
||||||||