SMM™ Smart Motor Manager

Click to enlarge - 825-2_9-1
Smart Motor Manager
Cat. No. 825-MÄ


Bulletin 825 SMM™ Smart Motor Manager


The Bulletin 825 SMM™ Smart Motor Manager provides the tools necessary to obtain optimal utilization of motors that operate critical processes. The Smart Motor Manager can minimize unplanned shutdowns with its comprehensive protective, monitoring, warning, and diagnostic capabilities. Protective features include: thermal overload, phase loss, phase reversal, phase imbalance, rapid trip/mechanical jam, ground (earth) fault, short circuit, over-temperature (thermistor input), underload, stator and bearing RTD monitoring, start time monitoring, stall during start, and multiple starts. Some of these features require the installation of an option card.

Thermal Overload

Two-Body Simulation

Most thermal overload protective devices employ a one-body thermal simulation model. This model assumes that a motor’s thermal response is uniform throughout. The Smart Motor Manager uses a two-body simulation to calculate a more precise representation of a motor’s thermal condition during all modes of operation. A twobody simulation incorporates the temperature rise characteristics of both the stator

windings and the iron mass of the motor into the thermal image.

Starting: In a two-body simulation, the fast rise in the winding temperature and the much slower conduction of heat to the iron during starting are correctly simulated.

Running: While the motor is running, both the iron and current imbalance losses are entered into the model. The optional addition of the ambient temperature into the simulation improves the level of motor use, even in cases where the temperature is subject to considerable fluctuations.

Stopped: The different cooling rates of a self-cooled motor while running and at rest are taken into account by two separate time constants. The simulation includes the faster cooling of the windings relative to the temperature of the iron mass after switching off the motor, as well as the slower cooling of the motor as a whole.


Thermal Capacity Utilization

Thermal capacity utilization is the motor I2t value that the Smart Motor Manager calculates with the two-body simulation. This value can be accessed via the front panel keypad/LCD under the Actual Values menu. When the value reaches 100%, a thermal (overload) trip occurs.

Adjustable Settings

To allow maximum utilization of a motor, the Smart Motor Manager provides the following adjustable settings that allow the installer to match the electronic thermal overload protection to the time-current response of the motor:


The thermal capacity of the iron is particularly important at low-level overloads; allowance for it in the thermal image enables the overload reserves of the motor to be used without risking a premature trip.

Adjustable Ratio of Cooling Time Constants

The ratio of the cooling time constant when the motor is stationary to the cooling time constant when the motor is running allows for the different cooling rates in each of these states. The factory-programmed default value is 2.5; this value is correct for the majority of self-cooled motors. For forced-cooled and special motors, especially those that respond either very quickly or slowly, it may be necessary to modify this value.

Tripping Time Display

In conditions when an overload is likely to occur, the time to trip is continuously displayed on the Smart Motor Manager’s front-panel LCD. This allows corrective action to be taken so that production may continue uninterrupted.

Reset Time Display

Following a thermal trip, the Smart Motor Manager cannot be reset until the temperature in the thermal image has fallen to the reset level, which has a factory-programmed default value of 50% of thermal utilization.

Thermal Warning

The Smart Motor Manager provides the capability to alert in the event of an impending overload trip. The thermal warning level has an adjustable range of 50…99% of thermal utilization, and the warning can be assigned to any of the available auxiliary relays.

Motor Temperature Monitoring

Direct motor temperature monitoring can provide enhanced protection against influences that are independent of current, such as ambient temperature and obstructed motor ventilation. Doing so requires a motor with temperature sensors embedded in the windings. The Smart Motor Manager offers two options for direct temperature monitoring.

Thermistor Input: The option card (Cat. No. 825-MST) allows connection of a maximum of six positive temperature coefficient (PTC) thermistors in series. The resistance of a thermistor increases immediately when its rated response temperature is exceeded. The Smart Motor Manager provides an instantaneous trip when the measures thermistor response resistance level is achieved.

RTD Input: The option card (Cat. No. 825-MMV) allows connection of six 100 W platinum resistant temperature detectors (RTDs) for monitoring motor winding and bearing temperature. A seventh input for monitoring the ambient temperature is also available. User-adjustable settings are provided for programming separate warning and trip temperature values. The monitored temperatures are displayed through the Actual Values menu.


Ground Fault

Motor insulation breakdown usually results in a leakage current to the grounded parts of the machine or, in the case of a power cable, the protective conduit. In grounded power systems, the fault current that develops can rise rapidly to a very high value. The Smart Motor Manager offers the following ground fault sensing options.

Residual Method (Holmgreen)

The Smart Motor Manager uses the Holmgreen method with the basic unit as standard. This method calculates the ground fault current by summing the individual phase currents. In a "healthy" motor where there is no residual current flowing to ground, the three-phase currents sums to zero. The Holmgreen method is best suited for use on either solidly grounded power systems or those grounded through a low impedance. The trip setting has an adjustable range of 10…100% of the motor’s full load current rating.

Zero Sequence Method (Core Balance)

The option card (Cat. No. 825-MST) allows the user to connect a core balance transformer (Cat. No. 825-CBCT), which measures the ground fault current directly from the three-phase motor conductors passing through it. This method is best suited for use on high-impedance grounded power systems. It is also preferred when a sensitive measurement is required. Both trip and warning settings are available with adjustable ranges from 5 mA…50 A.

Imbalance/Phase Loss

The Smart Motor Manager continuously monitors and calculates the current imbalance of an operational motor. The measured current imbalance is entered into the thermal image calculation to simulate the resulting increased motor heating.
User-adjustable trip and warning settings for current imbalance are available with a preset range of 5…80% of full-load current.
Phase loss, a severe form of imbalance, is one of the primary causes of motor failure. A phase loss can occur as a result of a blown fuse or a poor electrical connection. Under a phase loss condition, the current draw of the remaining two powered phases increases by as much as 1.73 times the normal operating current.
The Smart Motor Manager offers two options for obtaining phase loss protection.
Basic Unit: With the basic unit, phase loss protection is gained by using the current imbalance (asymmetry) settings.
Cat. No. 825-MLV: This option card provides terminals for connection to the threephase power system. With the connection made before the motor-starting contactor, a phase loss condition is recognized even while the motor is stopped. The Smart Motor Manager’s phase loss protection provides a preset delay of 2 s prior to a trip.


Rapid Trip/Mechanical Jam

When a driven load is jammed, causing the motor to stall, undue stress is applied to the transmission elements (gears, bearings, motor shaft, etc.). Additionally, as the motor stalls, its current draw begins to increase to the level of its locked rotor current rating.
The Smart Motor Manager provides the capability to quickly take a motor off line in the event of a mechanical jam, thereby reducing the potential for mechanical damage. It can also monitor and warn of impending jam situations. User-adjustable trip and warning settings are available with a range of 1…6 times the motor full-load current.


Underload

A sudden drop in motor current can signal conditions such as:


In these instances rapid fault detection can help minimize damage and aid in reducing production downtime.
Additionally, monitoring for underload can provide enhanced protection for motors that are cooled by the medium being handled (e.g., submersible water pumps). Such motors can become overheated despite being underloaded. This can result from an absence or insufficient amount of the medium (due to clogged filters, closed valves, etc.).
The adjustment range of the underload trip and warning settings is 25…100% of the motor’s full load current rating.


Short Circuit

In the event of a short circuit (phase-to-phase or phase-to-ground), excessive currents, typically much greater than a motor’s locked rotor current rating, are generated. Given the magnitude of this current, it is generally preferable or necessary to interrupt three-phase power to the motor through the branchprotecting circuit breaker rather than the motor-starting contactor due to the differences in the short-circuit withstand rating.
In the event of a short circuit, the Smart Motor Manager trips output relay #1 of the option card (Cat. No. 825-MST) regardless of other protective functions, actuating the circuit breaker with adequate breaking capacity. To prevent the contactor from opening under short-circuit conditions, its main relay is blocked from operating at currents greater than or equal to 12 times the motor’s full-load current rating. Tripping is delayed by 50 ms.


Start Time Monitoring

The Smart Motor Manager furnishes a setting for the installer to define the time that the motor should accelerate the load to full speed. The adjustment is 1…240 s. Start time monitoring begins when the motor’s starting inrush current is recognized (current is greater than 110% of the motor’s full-load current rating). Acceleration to full speed is deemed to have been completed when the starting inrush current has fallen below 110% of the motor’s full-load current rating.
Start time monitoring is independent of thermal overload protection.


Speed Switch Input

The Cat. No. 825-MST option card provides input terminals for connection of a speed switch. This enables the Smart Motor Manager to detect a stalled motor during start and react immediately to take the motor off-line; this reduces the risk of damage to either the motor or the driven load.

Two-Speed Motor Protection

In the case of two-speed motors, the Smart Motor Manager provides a second motor current rating setting. Activating control input #2 of the option card signals the Smart Motor Manager to begin protection based on this second setting.

Control Functions

Contactor Operation

The Smart Motor Manager allows control relays #2 and #3 on the Cat. No. 825-MST option card to be operated over an automation network (e.g., DeviceNet via the Cat. No. 825-MDN communication card). The relays will actuate the motorstarting contactor(s).

Wye-Delta Control

With the Cat. No. 825-MLV option card installed, the Smart Motor Manager can control the transition from wye to delta. The command to transition is issued when the starting current has dropped to the motor’s full-load current rating, thus minimizing the associated current transients.

Emergency Restart

If a critical process requires the restart of the motor, the Smart Motor Manager provides two terminals that, when bridged, return the stored thermal capacity utilization to zero so that an emergency restart can be initiated.

Outputs

Output Relays

The basic unit provides a main relay and an alarm relay. The main relay can be operated either as electrically held or non-fail-safe. The Cat. No. 825-MST option card offers three additional auxiliary relays. Two additional auxiliary relays are available with the Cat. No. 825-MLV option card.

Isolated Analog Output

The Cat. No. 825-MST option card provides an isolated 4…20 mA analog output signal. This can be set to indicate one of the following:


Monitoring and Diagnostic Display

The Smart Motor Manager provides the following useful operating motor data via the Actual Values and Recorded Values menus.

Actual Values


Recorded Values


Communications

The Smart Motor Manager provides a dedicated communication expansion slot for connection to the following automation networks:


This can enhance process operation by allowing the user to do the following via the network:


Basic and Optional Features

Features⋆  Basic
Bulletin 825
Option Cards
Cat. No. 825-MST Cat. No. 825-MLV Cat. No. 825-MMV
Thermal Overload ⋆ 
Phase Imbalance (Asymmetry) ⋆ 
Jam (High Overload/Stalling) ⋆ 
Underload ⋆ 
Ground (Earth) Fault (Holmgreen) ⋆ 
Starting Time Monitor ⋆ 
Limited Starts Per Hour ⋆ 
Emergency Start ⋆ 
Short Circuit ⋆ 
Ground (Earth) Fault (Core Balance CT) ⋆ 
Stalling During Start ⋆ 
Thermistor Input (PTC) ⋆ 
Analog Output for Thermal Utilization ⋆ 
Two-Speed Motor Protection ⋆ 
Wye-Delta (Star-Delta) Starting ⋆ 
Phase Reversal (Sequence) ⋆ 
Phase Failure ⋆ 
100 W Platinum RTD Inputs #1…#6
(Stator/Bearings)
⋆ 
100 W Platinum RTD Input #7
(Ambient Temp.)
⋆ 
  
⋆ Available

Possible Combinations of Option Cards with Basic Unit

Basic
Bulletin 825Ä
Option Cards‡ 
Cat. No. 825-MST Cat. No. 825-MLV Cat. No. 825-MMV
⋆  ⋆  ⋆ 
⋆  ⋆  ⋆ 
⋆  ⋆ 
⋆  ⋆ 
⋆  ⋆ 
⋆ 
 
⋆ The features and protective functions provided by each option card can be monitored through the communication network with any of the communication cards.
‡ A single communication card can be used with any combination of option cards.
§ Available in shown combination.

Standards Compliance and Certifications

Standards Compliance


Certifications


Product Selection

Your order must include: Cat. no. of the Smart Motor Manager selected with supply Voltage Suffix Code, Cat. no. of Converter Module selected, and, If required, Cat. no. of any option cards or accessories.

Product Selection — Smart Motor Manager Basic Unit

Click to enlarge - 825-2_9-1 Description Cat. No.
Basic Unit
Programmable electronic motor overload protection relay with communication capability
Thermal Overload
Phase Imbalance
Jam (High Overload)
Underload
Ground (Earth) Fault
Starting Time Monitor
Limited Starts per Hour
825-MÄ
  

Ä Control Voltage Suffix Code

The cat. no. as listed is incomplete. Select a control Voltage Suffix Code from the table below to complete the cat. no. Example: Cat. No. 825-MÄ for 120V power supply becomes Cat. No. 825-MD.

Voltage AC 24V 120…220V 220…240V 380…415V 440V Voltage DC 24…48V
50/60 Hz KD D AJ N GB Code Z48
  

Converter Module

  Description Current Range Cat. No.
Click to enlarge - 825-2_12-2 Converter Module
Connection to the Smart
Motor Manager is made by a
cable wire plug provided as
standard with the converter
module.
0.5…2.5 A 825-MCM2
2.5…20 A⋆  825-MCM20
Cat. No. 825-MCM180 20…180 A 825-MCM180
Click to enlarge - 825-2_12-3 160…434 A 825-MCM630
Cat. No. 825-MCM630 160…630 A 825-MCM630N
  
⋆ Up to 2000 A when using primary current transformers.

Core Balance Current Transformer

  Description Current Ratio Cat. No.
Click to enlarge - 825-2_12-4 Measure from earth current 0.5...10 A 100:1 825-CBCT
  
⋆ Up to 2000 A when using primary current transformers.

Accessories

Click to enlarge - 825-2_13-1 Description Cat. No.
MST option — Features
Short Circuit
Ground (Earth) Fault (Core Balance CT)
Stalling During Start
Thermistor Input (PTC)
Analog Output
Two-speed Motor Protection
825-MST
MLV option ‡  — Features
Wye-Delta (Star-Delta) Starting
Phase Reversal (Sequence)
Phase Failure (Motor Supply)
825-MLV
MMV option ‡ — Features
100 W Platinum RTD Inputs #1…#6 (Stator/Bearings)
100 W Platinum RTD Input #7 (Ambient Temperature)
825-MMV
DeviceNet Communication Card
DeviceNet Conformance Tested (Passed)
825-MDN
Click to enlarge - 825-2_13-2 M8 connections
Set of three
4 x 16 x 102 mm (1/8 x 5/8 x 4-1/64 in.) (125 A max.)
Universally applicable
Weight: 230 g
825-MVM
Click to enlarge - 825-2_13-3 Thermal Utilization Meter 825-MTUM
  
⋆ Option cards include a connector set.
‡ Cat. Nos. 825-MLV and 825-MMV occupy the same slot, therefore only one of the option cards may be used at one time.

Click to enlarge - 825-2_14-1   Description Cat. No.
Cat. No. 825-FPM Panel Mounting Frame 825-FPM
Connector Sets Provided as Standard with option card For use with Cat. No. 825-MÄ 825-CSB
Click to enlarge - 825-2_14-2 Cat. No. 825-PTS Cat. No. 825-MST 825-CSST
Cat. No. 825-MMV 825-CSMV
Cat. No. 825-MLV 825-CSLV
Click to enlarge - 825-2_14-6 Cat. No. 825-MPS Connection Cable (Replacement) Bul. 825-P to Bul. 825-MCM Connection 825-MCA
Power Supply Module (replacement) 825-MPSÄ
  

Ä Control Voltage Suffix Code

The cat. no. as listed is incomplete. Select a control Voltage Suffix Code from the table below to complete the Cat. No. Example: Cat. No. 825-MPSÄ for 120V power supply becomes Cat. No. 825-MPSD.

Voltage AC 24V 120…220V 220…240V 380…415V 440V Voltage DC 24…48V
50/60 Hz KD D AJ N GB Code Z48
  
⋆ Maximum Cable Lengths for Various Transmission Rates

Specifications

Click to enlarge - 825-2_14-7


Controls

1 Values
Actual
Set

Recorded
Mode Selection
Display current operating data
Setting mode
(set, change, save, and store parameters)
Display recorded data
5 Reset Reset trips
2 Select Select functions and enter/change operating parameters 6 LCD Single Line
(two lines of text are displayed alternately)
3 Settings
Change
Enter
Entry
Enable entry
Save entry
7 Fault Indicator
Blinking
Continuous
LED
Warning
Trip
4 Test Test functions
(Alarm, trip, trip time)
 
  

Settings

The following parameters must be programmed for every application. The other parameters (e.g., high overload, asymmetry) have factory-set values, which are correct for most applications.

Main Settings Setting Range Factory Setting
Rated motor current or operating current Ie
Use of a primary current transformer
Current ratio of primary current transformer
Locked-rotor current
Locked-rotor time⋆ 
0.5...2000 A
No/Yes
1...2000
2.5...12 Ie
1...600 s
20 A
No
1
6 Ie
10 s
  
⋆ If, instead of the permissible locked-rotor time, the maximum starting time is known, the approximate locked-rotor time is calculated as follows: Locked rotor time = Starting time ÷ 1.4

Special Settings Setting Range Factory Setting
Connection of main relay (MR)
Connection of alarm relay (AL)
Reset of thermal trip
Reset at...% thermal utilization
Reset PTC trip
Cooling constant motor ON/OFF ratio
Motor insulation class
Electrically held/non-fail-safe
Non-fail-safe/electrically held
Manual/automatic
10...100%
Manual/automatic
1...5
B/E/F
Electrically held
Non-fail-safe
Manual
50%
Manual
2.5
B
  

Function Overview

  Function Setting Tripping Delay Relays§ 
  Factory Setting Range Factory Setting Range Factory Setting Selection Factory Setting
Protective Functions
Bulletin 825-M basic unit
Thermal overload
Asymmetry/Phase loss
High overload/Stalling
Underload
Underload delay
Earth fault (Holmgreen)
Start time monitoring
Limited number of starts per hour
On
On
On
Off
On
On
Off
Off

5...80%
1...6 Ie
25...100%

10...100%

1...10

35%
2.4 Ie
75%

50%

2

1...5 s
0.5...25 s
1...60 s
0...240 s
0.1...5 s
1...240 s

2.5 s
0.5 s
10 s
0 s
0.5 s
10 s
MR
All
All
All

All
All
All
MR
MR
MR
MR

MR
MR
MR
Option 825-MST
Short circuit
Earth fault (core balance transformer)
Stalling during start⋆ 
PTC Thermistor input
Off
Off
Off
Off
4...12 Ie
5 mA...50 A

10 Ie
1 A

20...990 ms
0.1...5 s

50 ms
0.5 s

800 ms
#1
All
All⋆ 
All
#1
MR
MR⋆ 
MR
Option 825-MLV
Phase sequence (motor supply)
Phase loss (motor supply)
Off
Off



1 s
2 s
All
All
MR
MR
Option 825-MMV
100 W Platinum RTD inputs #1...#6 (stator, bearings)
100 W Platinum RTD input #7‡ 
Off
Off
50...200 °C
50 °C

<8 s
MR, AL#1...3
MR
Alarm Functions
Bulletin 825-M basic unit
Thermal utilisation (% D J load)
Asymmetry (% Ie)
High overload (% IIe)
Underload
Off
Off
Off
Off
50...99%
5...80%
1...6 Ie
25...100%
75%
20%
2 Ie
75%






AL,#1...5
AL,#1...5
AL,#1...5
AL,#1...5
AL
AL
AL
AL
Option 825-MST
Earth fault (core balance transformer)
Off 5 mA...50 A 500 mA AL,#1...5 AL
Option 825-MMV
100 W Platinum RTD inputs #1...#6 (stator, bearings)
Off 50...200 °C 50 °C AL,#1...5 AL
  
⋆ Via external speed switch (control input #1); output relays and time delay as with high overload.
‡ Includes ambient temperature in the thermal image.
§ Only one relay can be selected per function; MR = main relay, AL = alarm relay, auxiliary relays #1...#5.

Function Overview, Continued

  Function Setting Tripping Delay Relays§ 
  Factory Setting Range Factory Setting Range Factory Setting Selection Factory Setting
Control Functions
Bulletin 825-M basic unit
Warm start (% of cold trip)
Emergency start
Off
Off
50...100%
Jumper
Terminals
70%
Y11- Y12
4...60 min.
60 min.


Option 825-MST
Analog output
assigned to:
- Thermal utilisation
- PT100 max. Temperature
- I Motor
On 4...20 mA
0...100%
5...200 °C
Ie0...200%
Control Auxiliary Relays #2, #3
via communication
Control Input #1: (24V AC/DC; 8 mA)
Alternatively, one of two functions may be selected:
•     Pick-up delay, relay #2
•     Drop-out delay, relay #2
•     Disabling of protective functions:
- Asymmetry/phase loss
- High overload/stalling
- Earth fault
- Short circuit
- Underload
- Limited starts per hour
- Thermistor PTC
- 100 W Platinum RTD



Off
Off
Off
Off
Off
Off
Off
Off
Off
Off



























0...240 s
0...240 s










1 s
2 s






















#2
#2







Control Input #2: (24V AC/DC; 8 mA)
Alternatively, one of three functions can be selected:
•     Pick-up delay, relay #3
•     Drop-out delay, relay #3
•     Set 2nd rated current
• Disabling protective functions:
- Asymmetry/phase loss
- High overload/stalling
- Earth fault
- Short circuit
- Underload
- Limited starts per hour
- Thermistor PTC
- 100 W Platinum RTD



Off
Off
Off
Off
Off
Off
Off
Off
Off
Off





0.5...2000 A












20 A










0...240 s
0...240 s











1 s
2 s
























#3
#3








Option 825-MLV
Star-Delta starting
Off   Y-D:
1.1 · Ie
Y-D:
1...240 s
10 s   Y: #4
D: #5
  
§ Only one relay can be selected per function; MR = main relay, AL = alarm relay, relays #1...#5

Specifications

Bulletin 825-M Basic Unit and Bulletin 825-M Converter Module

Ambient Conditions
Temperature
Operation
Storage
Transport
–5...+60 °C
–40...+60 °C
–40...+60 °C
Climatic Withstand
Damp heat IEC 68-2-3
Climatic cycling IEC 68-2-30
40 °C, 92% relative humidity, 56 days
25/40 °C, 21 Cycles
Protection Class
Bulletin 825, enclosed in panel
Terminals
IP65
IP20
Vibration Resistance
per IEC 68-2-6
10...150 Hz, 3 G
Shock Resistance
per IEC 68-2-27
30 G, shock duration 18 ms, half of a sin wave in x, y, z directions
  

Bulletin 825-M Basic Unit and Bulletin 825-M Converter Module, Continued

Rated Voltage Ue
Primary Control Circuit
825-MCM2
825-MCM20
825-MCM630
825-MCM630N
825-MCM180
Motor Circuit
per IEC, SEV, VDE 0660
per CSA, UL
400V AC
240V AC
660V AC
600V AC
1,000V AC
600V AC
Control Circuit
Main relay (MR) 95...98, supply A1, A2
Phase-sequence protection L1, L2, L3
•     per IEC 947
•     per SEV
•     per CSA, UL
Alarm relay (AL) 13/14, Auxiliary Relays #1, #4, #5
•     per IEC 947
•     per SEV
•     per CSA, UL
Auxiliary Relays #2, #3
Control Inputs #1, #2
400V AC
380V AC
240V AC

400V AC
250V AC
240V AC
120V AC/30V DC
24V AC/DC
Electrical Ratings
Test Voltage
825-MCM2
825-MCM20
825-MCM630
825-MCM630N
825-MCM1808
Motor Circuit
per IEC 947-4
Uimp 2.5 kV Uimp 6 kV Uimp 8 kV
Control Circuit
Control circuits against each other and against all other sets⋆ 
Main relay (MR) 95...98, supply A1, A2
Phase sequence protection L1, L2, L3
Alarm relay (AL) 13/14, Auxiliary relays #1, #4, #5
•     per IEC 947-4
Core-balance transformer k, I
Auxiliary relays #2, #3
Control inputs #1, #2
•     per IEC 947-4


Uimp 4 kV




Uimp 2.5 kV
EMC Standard
Noise emission
Noise proof
per EN 50 081-1 and EN 50 081-2
per EN 50 082-1 and EN 50 082-2
Standards IEC 947-4, CSA C22.2 No. 14, UL 508
Approvals CE, UL-Listed, CSA
Supply
Nominal supply voltage Us

Permissible voltage fluctuation
Power consumption
Short-circuit protection
50/60 Hz: 22...24, 33...36, 44...48, 110...120,
220...240, 380...415, 440V AC
24...48, 72...120V DC
AC 0.85...1.1 Us, DC 0.80...1.1 Us
AC 13 VA, DC 10 W max.
With the appropriate supply cable rating, the supply module is short-circuit proof
Terminals
Bulletin 825-M Plug-in Terminals

•     per UL
•     per VDE
Range of gauges:


Nominal gauge:
[mm2]
[mm2]
[AWG No.]
[mm2]
0.5...2.5, single-wire
0.5...1.5, double-wire
22...14
1.5
Main circuit
825-MCM2, 825-MCM20
Terminals:
[mm2]
[AWG No.]
2 x 2.5/1 x 4
2 x 20...14/1 x 20...12
825-MCM180
825-MCM630(N)
Aperture:
or bus bars:
Bus bars
[mm]
[mm]
[mm]
Æ max. 19
20/16 x 4
25 x 8
  
⋆ The measuring inputs PT100 and PTC, 4...20 mA analog output and the RS 485 communication interface are not isolated from one another.

Bulletin 825-M Basic Unit and Bulletin 825-MCM Converter Module, Continued

Relays
Contact Data of Output Relays, Main Relay (MR) 95...96
Contacts   1 N.O. and 1 N.C. contact, electrically insulated
Nominal operating voltage per UL, CSA: pilot duty 240V [V] 24 110...125 220...250 380...440
Continuous thermal current [A] 4
Rated operating current AC-15 [A] 3 3 1.2
Maximum permissible switching current (cos f = 0.3) AC-15 [A] 30 30 12
Rated operating current

(L/R = 300 ms), no protection network necessary
DC-13 [A] 2 0.3 0.2
Max. rated current of back-up fuse [A] fast (D) 16; slow (DT) 10, 500V Type gG
Alarm relay (AL), Auxiliary relays #1, #4, #5
Contacts   1 N.O. contact each
Continuous thermal current [A] 4
Maximum permissible switching voltage [V] 400 AC, 125 DC
Nominal operating current
cos f= 1
cos f= 0.4, L/R = 7 ms
[A]
[A]
4 at 250V AC or 30V DC
2 at 250V AC or 30V DC
Maximum switching power
cos f= 1
cos f= 0.4, L/R = 7 ms
- per UL/CSA
[VA/W]
[VA/W]
[V]
1250/150
500/60
240; 1 A pilot duty
Auxiliary relays #2, #3
Contacts   1 N.O. contact each
Continuous thermal current [A] 4
Maximum permissible switching voltage [V] 48 AC, 30 DC
Maximum switching power
cos f= 1
cos f= 0.4, L/R = 7 ms
[W]
[W]
150
60
  

Main Current Transformers for the Motor Circuit
When Bulletin 825-M is used as a secondary relay with Cat. Nos. 825-MCM2, 825-MCM20
Min. rated operating voltage
Min. rated primary current I1n
Rated secondary current
Class and nominal overcurrent factor
Power rating
Rated frequency
[V]
[A]
[A]

[Hz]
Nominal operating voltage of motors
Nominal operating current of motor
1 or 5
5 P 10 ext. 120%⋆ 
According to power consumption in leads and measuring circuits
50/60
Burden
Power consumption at maximum rated current‡ 
Continuous thermal current
Thermal current during 1 s
Rated frequency
[VA]
[A]
[A]
[Hz]
825-M + 825-MCM2
0.1 per Phase
3
250
50/60
825-M + 825-MCM20
0.4 per Phase
24
600
50/60
General Notes on 825-MCM
No-load An open-circuit secondary is permitted, since the burden is installed in the detection module
  
⋆ Current transformer (P = Protection): ±1% error at rated current (Ie)
±5% error at rated overcurrent (10 · Ie)
Rated thermal current = 120% Ie
For starting current 10 · Ie: Class 5 P 20
The current transformer error is added to the Bulletin 825-M error.
‡ 2.5 A with Cat. No. 825-MCM2, 20 A with Cat. No. 825-MCM20

Core Balance Current Transformer
Recommended Core Balance Current Transformer (cable-type)
Nominal ratio Kn = Minimum detectable earth fault
Pick-up current of Bulletin 825 earth fault protection
Burden: Bulletin 825-M measuring circuit
Power consumption at max. rated current 0.5 A[VA]
Continuous thermal current[VA]
Thermal current during 1 sec[A]
Frequency[Hz]
0.4
0.5
25
50/60
Short-Circuit Protection
Selection of circuit breaker or fuse and associated contactor The line-side circuit breaker or fuse must ensure that the engine will start, while still switching off short-circuit currents fast enough. Because of the latter, the fuse selected should always be as small as possible.
The lowest possible fuse rating depends on the starting current of the motor and the tripping time set on the Bulletin 825-M.
Short-Circuit coordination of the starter must always be considered The contactor receives its tripping signal when the Bulletin 825 trips and must interrupt all currents up to the point of intersection of the time/current characteristics of the Bulletin 825 and circuit breaker or fuse. When starting large motors, the main contacts on the contactor are subjected to high thermal loads so that if the motor starting time exceeds a certain limit, the maximum permissible current has to be reduced.
The fuse or contactor rating must also allow for the prospective short-circuit current. The Bulletin 825-MCM converter modules are short-circuit proof. The contactor coordination diagrams are available upon request.
  

Bulletin 825-M Basic Unit and Bulletin 825-MCM Converter Module

Response During Supply Voltage Failure
If the supply voltage fails, the setting data is retained
Supply voltage failure > 30 ms •     All attracted output relays drop out
•     LED extinguishes
•     The timer for duration of supply failure starts (max. 8 h)
•     The current and recorded data are memorized
•     LCD extinguishes
Recovery of the supply voltage •     Start of initialization routine
•     The time of occurrence and the duration of the supply voltage failure are recorded
•     Thermal image is calculated and updated
•     All output relays return to the state they were in before the supply failure
•     LCD and LED are active
Automatic Recognition of the Converter Module
In the event of a fault, the output relay MR trips and the type of fault appears on the LCD
Bulletin 825-M devices regularly check •     The Bulletin 825-M <-> 825-MCM link
•     Agreement between the rated current set and the current range of the Bulletin 825-MCM
•     The supervisory circuits
Bulletin 825-MTUM Device for Indicating Thermal Utilisation, PT 100 max., Imotor
Display range
Utilisation[%]
Wire[mm2]
Front[mm]
Panel cutout[mm]
Mounting depth[mm]
0...100 (DJIe at rated current Ie)
2 x 2.5
96 x 96
91.5 x 91.5 (–0/+ 0.5)
55
Power Supply Module
Permissible voltage fluctuation[ Us]
Power consumption[VA/W]
Short-circuit protection
AC 0.85...1.1, DC 0.80...1.1
AC 13/DC 10
The power supply module is short-circuit proof
  

Weights
Bulletin 825-M with power supply module   [g] 1000
Bulletin 825-M without power supply module   [g] 710
Power supply module 825-MPS [g] 290
Options 825-MPB [g] 125
  825-MST [g] 90
  825-MLV [g] 90
  825-MMV [g] 90
Converter modules 825-MCM2 [g] 570
  825-MCM20 [g] 570
  825-MCM180 [g] 860
  825-MCM630 [g] 3120
  825-MCM630N [g] 5460
Core balance transformer 825-CBCT [g] 500
Thermal utilisation indicator 825-MTUM [g] 180
Mounting frame 825-FPM [g] 860
PC Option kit 825-VISU [g] 125
T connector 825-PTS [g] 75
Stub cable 825-PTL2 [g] 40
  825-PTL4 [g] 45
Bus cable segment 825-PCB1 [g] 95
Bus termination 825-PCE [g] 20
Bus cable 825-BC [g] 59/m
Bus cable connector 825-CBC9 [g] 15
Bus bar for Cat. No. 825-MCM180      
  825-MVM [g] 230
  825-MVM2 [g] 230
  

Short-Circuit Protection of Medium- and High-Voltage Motors with Option 825-MST

Main Circuit

    3-phase current evaluation

Click to enlarge - 825-2_20-1
Cat. No. 825-M for short-circuit protection


Converter Module U1
825-MCM2
825-MCM20



Main current transformer U2...A/5 A or...A/1 A
See Specifications for selection



Core balance transformer U3
5 mA...50 A
Output to Bulletin 825-M: 5...500 mA


Control Circuit

Click to enlarge - 825-2_20-2
Impulse contact control


QM Circuit breaker
QA Shunt trip coil
K1 Contactor
F1 825-M
S1 ON button
S0 OFF button
Us Control voltage
H1 Indicator: contact closed
H2 Indicator: Bulletin 825 tripped
  (except for short-circuit protection)
H3 Indicator: short-circuit trip
MR Main output relay
#1 Auxiliary relay, short-circuit indicator

Approximate Dimensions

Dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes.

Bulletin 825-M Mounting

Bulletin 825-M devices are suitable for both flush- and surface mounting.

Flush Mounting

Click to enlarge - 825-2_21-1


Surface Mounting

Bulletin 825-M devices can be installed on a mounting frame (Cat. No. 825-FPM). The terminals can then be easily accessed without unmounting the device.

Click to enlarge - 825-2_21-2


Mounting Depth

Click to enlarge - 825-2_21-3


Mounting Position

Click to enlarge - 825-2_21-4


Dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes.

Bulletin 825-MCM Converter Module

Click to enlarge - 825-2_22-1
Cat. No. 825-MCM2...825-MCM180
Cat. No. 825-MCM630


Click to enlarge - 825-2_22-2
Cat. No. 825-MCM630N


Dimensions
Cat. No. a b c c1 ø d d1 d2 d3 ø e ø e1 e2 b1 b2
825-MCM2 120 85 102 66 5.3 5.3 100 55 2 x 2.5
mm2
38.5    
825-MCM20 120 85 102 66 5.3 5.3 100 55 2 x 2.5
mm2
38.5    
825-MCM180 120   102 72 5.3 5.3 100 55 ∆  ∆  38.5 75 § /♣ 
100/118
825-MCM630 155 145 156 118 6.3 6.3 135 88 11 M10 48    
825-MCM630N 155 145 177 118 6.3 6.3 135 88 11 M10 48    
  
⋆ For snapping on to DIN Rail (EN 50 022-35 x 15 or 35 x 7.5).
‡ Cat. No. 825-MCM180; with bus bar or max. ø 19 mm aperture for looping the§  conductors.
§ With Cat. No. 825-MVM.
♣ Cat. No. 825-MVM2
∆ See below for bus bars for Cat. No. 825-MCM180.

Bus Bars

Terminal Dimensions
Cat. No. Bottom Top
825-MVM M8 M8
  

Dimensions are not intended to be used for manufacturing purposes.

Core Balance Current Transformer

Click to enlarge - 825-2_23-1
Cat. No. 825-CBCT