Catalogs > Industrial Controls Catalog > Motor Control, IEC > Overload Relays > SMM™ Smart Motor Manager
SMM™ Smart Motor Manager
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
|
Controls
| 1 | Values Actual Set Recorded |
Mode Selection Display current operating data Setting mode (set, change, save, and store parameters) Display recorded data |
5 | Reset | Reset trips |
| 2 | Select | Select functions and enter/change operating parameters | 6 | LCD | Single Line (two lines of text are displayed alternately) |
| 3 | Settings Change Enter |
Entry Enable entry Save entry |
7 | Fault Indicator Blinking Continuous |
LED Warning Trip |
| 4 | Test | Test functions (Alarm, trip, trip time) |
|||
Settings
The following parameters must be programmed for every application. The other parameters (e.g., high overload, asymmetry) have factory-set values, which are correct for most applications.
| Main Settings | Setting Range | Factory Setting |
| Rated motor current or operating current Ie Use of a primary current transformer Current ratio of primary current transformer Locked-rotor current Locked-rotor time⋆ |
0.5...2000 A No/Yes 1...2000 2.5...12 Ie 1...600 s |
20 A No 1 6 Ie 10 s |
| ⋆ If, instead of the permissible locked-rotor time, the maximum starting time is known, the approximate locked-rotor time is calculated as follows: Locked rotor time = Starting time ÷ 1.4 | ||
| Special Settings | Setting Range | Factory Setting |
| Connection of main relay (MR) Connection of alarm relay (AL) Reset of thermal trip Reset at...% thermal utilization Reset PTC trip Cooling constant motor ON/OFF ratio Motor insulation class |
Electrically held/non-fail-safe Non-fail-safe/electrically held Manual/automatic 10...100% Manual/automatic 1...5 B/E/F |
Electrically held Non-fail-safe Manual 50% Manual 2.5 B |
Function Overview
| Function | Setting | Tripping Delay | Relays§ | ||||
| Factory Setting | Range | Factory Setting | Range | Factory Setting | Selection | Factory Setting | |
| Protective Functions | |||||||
| Bulletin 825-M basic unit Thermal overload Asymmetry/Phase loss High overload/Stalling Underload Underload delay Earth fault (Holmgreen) Start time monitoring Limited number of starts per hour |
On On On Off On On Off Off |
— 5...80% 1...6 Ie 25...100% — 10...100% — 1...10 |
— 35% 2.4 Ie 75% — 50% — 2 |
— 1...5 s 0.5...25 s 1...60 s 0...240 s 0.1...5 s 1...240 s — |
— 2.5 s 0.5 s 10 s 0 s 0.5 s 10 s — |
MR All All All — All All All |
MR MR MR MR — MR MR MR |
| Option 825-MST Short circuit Earth fault (core balance transformer) Stalling during start⋆ PTC Thermistor input |
Off Off Off Off |
4...12 Ie 5 mA...50 A — — |
10 Ie 1 A — — |
20...990 ms 0.1...5 s — — |
50 ms 0.5 s — 800 ms |
#1 All All⋆ All |
#1 MR MR⋆ MR |
| Option 825-MLV Phase sequence (motor supply) Phase loss (motor supply) |
Off Off |
— — |
— — |
— — |
1 s 2 s |
All All |
MR MR |
| Option 825-MMV 100 W Platinum RTD inputs #1...#6 (stator, bearings) 100 W Platinum RTD input #7 |
Off Off |
50...200 °C — |
50 °C — |
— — |
<8 s — |
MR, AL#1...3 — |
MR — |
| Alarm Functions | |||||||
| Bulletin 825-M basic unit Thermal utilisation (% D J load) Asymmetry (% Ie) High overload (% IIe) Underload |
Off Off Off Off |
50...99% 5...80% 1...6 Ie 25...100% |
75% 20% 2 Ie 75% |
— — — — |
— — — — |
AL,#1...5 AL,#1...5 AL,#1...5 AL,#1...5 |
AL AL AL AL |
| Option 825-MST Earth fault (core balance transformer) |
Off | 5 mA...50 A | 500 mA | — | — | AL,#1...5 | AL |
| Option 825-MMV 100 W Platinum RTD inputs #1...#6 (stator, bearings) |
Off | 50...200 °C | 50 °C | — | — | AL,#1...5 | AL |
| ⋆ Via external speed switch (control input #1); output relays and time delay as with high overload. Includes ambient temperature in the thermal image. § Only one relay can be selected per function; MR = main relay, AL = alarm relay, auxiliary relays #1...#5. |
|||||||
Function Overview, Continued
| Function | Setting | Tripping Delay | Relays§ | ||||
| Factory Setting | Range | Factory Setting | Range | Factory Setting | Selection | Factory Setting | |
| Control Functions | |||||||
| Bulletin 825-M basic unit Warm start (% of cold trip) Emergency start |
Off Off |
50...100% Jumper Terminals |
70% Y11- Y12 |
4...60 min. — |
60 min. — |
— — |
— — |
| Option 825-MST Analog output assigned to: - Thermal utilisation - PT100 max. Temperature - I Motor |
On | 4...20 mA 0...100% 5...200 °C Ie0...200% |
— | — | — | — | — |
| Control Auxiliary Relays #2, #3 via communication |
— | — | — | — | — | — | — |
| Control Input #1: (24V AC/DC; 8 mA) Alternatively, one of two functions may be selected: Pick-up delay, relay #2 Drop-out delay, relay #2 Disabling of protective functions: - Asymmetry/phase loss - High overload/stalling - Earth fault - Short circuit - Underload - Limited starts per hour - Thermistor PTC - 100 W Platinum RTD |
Off Off Off Off Off Off Off Off Off Off |
— — — — — — — — — — |
— — — — — — — — — — |
0...240 s 0...240 s — — — — — — — — |
1 s 2 s — — — — — — — — |
— — — — — — — — — — |
#2 #2 — — — — — — — — |
| Control Input #2: (24V AC/DC; 8 mA) Alternatively, one of three functions can be selected: Pick-up delay, relay #3 Drop-out delay, relay #3 Set 2nd rated current Disabling protective functions: - Asymmetry/phase loss - High overload/stalling - Earth fault - Short circuit - Underload - Limited starts per hour - Thermistor PTC - 100 W Platinum RTD |
Off Off Off Off Off Off Off Off Off Off |
— — 0.5...2000 A — — — — — — — — |
— — 20 A — — — — — — — — |
0...240 s 0...240 s — — — — — — — — — |
1 s 2 s — — — — — — — — — |
— — — — — — — — — — — |
#3 #3 — — — — — — — — — |
| Option 825-MLV Star-Delta starting |
Off | Y-D: 1.1 · Ie |
Y-D: 1...240 s |
10 s | Y: #4 D: #5 |
||
| § Only one relay can be selected per function; MR = main relay, AL = alarm relay, relays #1...#5 | |||||||
Specifications
Bulletin 825-M Basic Unit and Bulletin 825-M Converter Module
| Ambient Conditions | |
| Temperature Operation Storage Transport |
5...+60 °C 40...+60 °C 40...+60 °C |
| Climatic Withstand Damp heat IEC 68-2-3 Climatic cycling IEC 68-2-30 |
40 °C, 92% relative humidity, 56 days 25/40 °C, 21 Cycles |
| Protection Class Bulletin 825, enclosed in panel Terminals |
IP65 IP20 |
| Vibration Resistance per IEC 68-2-6 |
10...150 Hz, 3 G |
| Shock Resistance per IEC 68-2-27 |
30 G, shock duration 18 ms, half of a sin wave in x, y, z directions |
Bulletin 825-M Basic Unit and Bulletin 825-M Converter Module, Continued
| Rated Voltage Ue | |||
| Primary Control Circuit |
825-MCM2 |
825-MCM20 |
825-MCM630 825-MCM630N 825-MCM180 |
| Motor Circuit per IEC, SEV, VDE 0660 per CSA, UL |
400V AC 240V AC |
660V AC 600V AC |
1,000V AC 600V AC |
| Control Circuit Main relay (MR) 95...98, supply A1, A2 Phase-sequence protection L1, L2, L3 per IEC 947 per SEV per CSA, UL Alarm relay (AL) 13/14, Auxiliary Relays #1, #4, #5 per IEC 947 per SEV per CSA, UL Auxiliary Relays #2, #3 Control Inputs #1, #2 |
400V AC 380V AC 240V AC 400V AC 250V AC 240V AC 120V AC/30V DC 24V AC/DC |
||
| Electrical Ratings | |||
| Test Voltage |
825-MCM2 |
825-MCM20 |
825-MCM630 825-MCM630N 825-MCM1808 |
| Motor Circuit per IEC 947-4 |
Uimp 2.5 kV | Uimp 6 kV | Uimp 8 kV |
| Control Circuit Control circuits against each other and against all other sets⋆ Main relay (MR) 95...98, supply A1, A2 Phase sequence protection L1, L2, L3 Alarm relay (AL) 13/14, Auxiliary relays #1, #4, #5 per IEC 947-4 Core-balance transformer k, I Auxiliary relays #2, #3 Control inputs #1, #2 per IEC 947-4 |
Uimp 4 kV Uimp 2.5 kV |
||
| EMC Standard | |||
| Noise emission Noise proof |
per EN 50 081-1 and EN 50 081-2 per EN 50 082-1 and EN 50 082-2 |
||
| Standards | IEC 947-4, CSA C22.2 No. 14, UL 508 | ||
| Approvals | CE, UL-Listed, CSA | ||
| Supply | |||
| Nominal supply voltage Us Permissible voltage fluctuation Power consumption Short-circuit protection |
50/60 Hz: 22...24, 33...36, 44...48, 110...120, 220...240, 380...415, 440V AC 24...48, 72...120V DC AC 0.85...1.1 Us, DC 0.80...1.1 Us AC 13 VA, DC 10 W max. With the appropriate supply cable rating, the supply module is short-circuit proof |
||
| Terminals | |||
| Bulletin 825-M Plug-in Terminals per UL per VDE |
Range of gauges: Nominal gauge: |
[mm2] [mm2] [AWG No.] [mm2] |
0.5...2.5, single-wire 0.5...1.5, double-wire 22...14 1.5 |
| Main circuit 825-MCM2, 825-MCM20 |
Terminals: |
[mm2] [AWG No.] |
2 x 2.5/1 x 4 2 x 20...14/1 x 20...12 |
| 825-MCM180 825-MCM630(N) |
Aperture: or bus bars: Bus bars |
[mm] [mm] [mm] |
Æ max. 19 20/16 x 4 25 x 8 |
| ⋆ The measuring inputs PT100 and PTC, 4...20 mA analog output and the RS 485 communication interface are not isolated from one another. | |||
Bulletin 825-M Basic Unit and Bulletin 825-MCM Converter Module, Continued
| Relays | ||||||
| Contact Data of Output Relays, Main Relay (MR) 95...96 | ||||||
| Contacts | 1 N.O. and 1 N.C. contact, electrically insulated | |||||
| Nominal operating voltage per UL, CSA: pilot duty 240V | [V] | 24 | 110...125 | 220...250 | 380...440 | |
| Continuous thermal current | [A] | 4 | ||||
| Rated operating current | AC-15 | [A] | 3 | 3 | 1.2 | |
| Maximum permissible switching current (cos f = 0.3) | AC-15 | [A] | 30 | 30 | 12 | |
| Rated operating current (L/R = 300 ms), no protection network necessary |
DC-13 | [A] | 2 | 0.3 | 0.2 | — |
| Max. rated current of back-up fuse | [A] | fast (D) 16; slow (DT) 10, 500V Type gG | ||||
| Alarm relay (AL), Auxiliary relays #1, #4, #5 | ||||||
| Contacts | 1 N.O. contact each | |||||
| Continuous thermal current | [A] | 4 | ||||
| Maximum permissible switching voltage | [V] | 400 AC, 125 DC | ||||
| Nominal operating current cos f= 1 cos f= 0.4, L/R = 7 ms |
[A] [A] |
4 at 250V AC or 30V DC 2 at 250V AC or 30V DC |
||||
| Maximum switching power cos f= 1 cos f= 0.4, L/R = 7 ms - per UL/CSA |
[VA/W] [VA/W] [V] |
1250/150 500/60 240; 1 A pilot duty |
||||
| Auxiliary relays #2, #3 | ||||||
| Contacts | 1 N.O. contact each | |||||
| Continuous thermal current | [A] | 4 | ||||
| Maximum permissible switching voltage | [V] | 48 AC, 30 DC | ||||
| Maximum switching power cos f= 1 cos f= 0.4, L/R = 7 ms |
[W] [W] |
150 60 |
||||
| Main Current Transformers for the Motor Circuit | |||
| When Bulletin 825-M is used as a secondary relay with Cat. Nos. 825-MCM2, 825-MCM20 | |||
| Min. rated operating voltage Min. rated primary current I1n Rated secondary current Class and nominal overcurrent factor Power rating Rated frequency |
[V] [A] [A] [Hz] |
Nominal operating voltage of motors Nominal operating current of motor 1 or 5 5 P 10 ext. 120%⋆ According to power consumption in leads and measuring circuits 50/60 |
|
| Burden Power consumption at maximum rated current Continuous thermal current Thermal current during 1 s Rated frequency |
[VA] [A] [A] [Hz] |
825-M + 825-MCM2 0.1 per Phase 3 250 50/60 |
825-M + 825-MCM20 0.4 per Phase 24 600 50/60 |
| General Notes on 825-MCM | |||
| No-load | An open-circuit secondary is permitted, since the burden is installed in the detection module | ||
| ⋆ Current transformer (P = Protection): ±1% error at rated current (Ie) ±5% error at rated overcurrent (10 · Ie) Rated thermal current = 120% Ie For starting current 10 · Ie: Class 5 P 20 The current transformer error is added to the Bulletin 825-M error. 2.5 A with Cat. No. 825-MCM2, 20 A with Cat. No. 825-MCM20 |
|||
| Core Balance Current Transformer | |
| Recommended Core Balance Current Transformer (cable-type) | |
| Nominal ratio Kn = | Minimum detectable earth fault Pick-up current of Bulletin 825 earth fault protection |
| Burden: Bulletin 825-M measuring circuit Power consumption at max. rated current 0.5 A[VA] Continuous thermal current[VA] Thermal current during 1 sec[A] Frequency[Hz] |
0.4 0.5 25 50/60 |
| Short-Circuit Protection | |
| Selection of circuit breaker or fuse and associated contactor | The line-side circuit breaker or fuse must ensure that the engine will start, while still switching off short-circuit currents fast enough. Because of the latter, the fuse selected should always be as small as possible. The lowest possible fuse rating depends on the starting current of the motor and the tripping time set on the Bulletin 825-M. |
| Short-Circuit coordination of the starter must always be considered | The contactor receives its tripping signal when the Bulletin 825 trips and must interrupt all currents up to the point of intersection of the time/current characteristics of the Bulletin 825 and circuit breaker or fuse. When starting large motors, the main contacts on the contactor are subjected to high thermal loads so that if the motor starting time exceeds a certain limit, the maximum permissible current has to be reduced. The fuse or contactor rating must also allow for the prospective short-circuit current. The Bulletin 825-MCM converter modules are short-circuit proof. The contactor coordination diagrams are available upon request. |
Bulletin 825-M Basic Unit and Bulletin 825-MCM Converter Module
| Response During Supply Voltage Failure If the supply voltage fails, the setting data is retained |
|
| Supply voltage failure > 30 ms | All attracted output relays drop out LED extinguishes The timer for duration of supply failure starts (max. 8 h) The current and recorded data are memorized LCD extinguishes |
| Recovery of the supply voltage | Start of initialization routine The time of occurrence and the duration of the supply voltage failure are recorded Thermal image is calculated and updated All output relays return to the state they were in before the supply failure LCD and LED are active |
| Automatic Recognition of the Converter Module In the event of a fault, the output relay MR trips and the type of fault appears on the LCD |
|
| Bulletin 825-M devices regularly check | The Bulletin 825-M <-> 825-MCM link Agreement between the rated current set and the current range of the Bulletin 825-MCM The supervisory circuits |
| Bulletin 825-MTUM Device for Indicating Thermal Utilisation, PT 100 max., Imotor | |
| Display range Utilisation[%] Wire[mm2] Front[mm] Panel cutout[mm] Mounting depth[mm] |
0...100 (DJIe at rated current Ie) 2 x 2.5 96 x 96 91.5 x 91.5 (0/+ 0.5) 55 |
| Power Supply Module | |
| Permissible voltage fluctuation[ Us] Power consumption[VA/W] Short-circuit protection |
AC 0.85...1.1, DC 0.80...1.1 AC 13/DC 10 The power supply module is short-circuit proof |
| Weights | |||
| Bulletin 825-M with power supply module | [g] | 1000 | |
| Bulletin 825-M without power supply module | [g] | 710 | |
| Power supply module | 825-MPS | [g] | 290 |
| Options | 825-MPB | [g] | 125 |
| 825-MST | [g] | 90 | |
| 825-MLV | [g] | 90 | |
| 825-MMV | [g] | 90 | |
| Converter modules | 825-MCM2 | [g] | 570 |
| 825-MCM20 | [g] | 570 | |
| 825-MCM180 | [g] | 860 | |
| 825-MCM630 | [g] | 3120 | |
| 825-MCM630N | [g] | 5460 | |
| Core balance transformer | 825-CBCT | [g] | 500 |
| Thermal utilisation indicator | 825-MTUM | [g] | 180 |
| Mounting frame | 825-FPM | [g] | 860 |
| PC Option kit | 825-VISU | [g] | 125 |
| T connector | 825-PTS | [g] | 75 |
| Stub cable | 825-PTL2 | [g] | 40 |
| 825-PTL4 | [g] | 45 | |
| Bus cable segment | 825-PCB1 | [g] | 95 |
| Bus termination | 825-PCE | [g] | 20 |
| Bus cable | 825-BC | [g] | 59/m |
| Bus cable connector | 825-CBC9 | [g] | 15 |
| Bus bar for Cat. No. 825-MCM180 | |||
| 825-MVM | [g] | 230 | |
| 825-MVM2 | [g] | 230 | |
Short-Circuit Protection of Medium- and High-Voltage Motors with Option 825-MST
Main Circuit
3-phase current evaluation
|
Converter Module U1
825-MCM2
825-MCM20
Main current transformer U2...A/5 A or...A/1 A
See Specifications for selection
Core balance transformer U3
5 mA...50 A
Output to Bulletin 825-M: 5...500 mA
Control Circuit
|
| QM | Circuit breaker |
| QA | Shunt trip coil |
| K1 | Contactor |
| F1 | 825-M |
| S1 | ON button |
| S0 | OFF button |
| Us | Control voltage |
| H1 | Indicator: contact closed |
| H2 | Indicator: Bulletin 825 tripped |
| (except for short-circuit protection) | |
| H3 | Indicator: short-circuit trip |
| MR | Main output relay |
| #1 | Auxiliary relay, short-circuit indicator |
