Product Overview

Description

The Bulletin 825-P Modular Protection System for motors offers a compact, modular design that uniquely allows an installer to configure a device’s functional capabilities to match the application requirements. Flexibility is also afforded by accommodating future expansion of the system as the application requirements grow. Finally, ease of installation is provided through pluggable options and accessories.

Comprehensive Protection

The 825-P Modular Protection System offers in-depth motor protection coverage by monitoring the critical elements of motor current, line voltage and temperature. High resolution settings allow the installer to configure a precise envelope of protection to achieve maximum motor utilization while avoiding damage and downtime.

ANSII No. Function ANSII No. Function
Current Elements Temperature Elements
51 Thermal Overload 49 PTC Thermistor
46 Current Imbalance/Phase Loss 49 Stator RTD
50G/51G Ground Fault 38 Bearing RTD
37 Undercurrent (Load Loss) Ambient and Other RTD
48 Overcurrent (Load Jam) Power Elements
50 Short Circuit 37 Underpower
47 Phase Reversal 55/78 Power Factor
81 Frequency Reactive Power
86 Overload Lockout
Voltage Elements Motor Starting Elements
27 Undervoltage 66 Starts/Hour
59 Overvoltage Stall - Acceleration Time Monitoring
47 Phase Reversal 14 Speed Switch Monitoring
81 Frequency 19 Reduced Voltage Starting
48 Incomplete Start
  
Note:Voltage, power, and energy elements are only available with the installation of the voltage input option card.

Full Function Metering

Current Elements Voltage Elements Power Elements Energy Elements Thermal Elements
Phase Currents Line-Line Voltages Real Power (kW) Real Energy (kWh) % Thermal Capacity Utilization
Average Current Avg. Line-Line Voltage Reactive Power (kVAR) Reactive Energy Forward (kVARh) RTD Values
% Motor Load Line-Neutral Voltages Apparent Power (kVA) Reactive Energy Reverse (kVARh)
Current Imbalance Avg. Line-Neutral Voltage Power Factor Apparent Energy (kVAh)
Ground Fault Current Voltage Imbalance
System Frequency System Frequency
  
Note:Voltage and power elements are only available with the installation of the voltage input option card.

Product Overview, Continued

Statistical Values

The 825-P Modular Protection System provides the following valuable statistical values of motor operation:

  • Elapsed time of operation


  • Stopped time


  • Percent of time running


  • Number of starts


  • Number of emergency starts


  • Date and time of last trip reset


  • Historical Data

    The 825-P Modular Protection System saves records for the five most recent trip events. Each trip event is summarized with record of the following prior to trip data capture:

  • Event day and time


  • Trip identification


  • Phase and ground current values


  • Voltage values


  • Function Overview

    Description Trip Level Setting Range Trip Delay Setting Time Warning Level Setting Range
    Motor FLA Ie 0.5…5000 A
    Locked Rotor Current 2.5…12 x Ie 50…100% TCU
    Locked Rotor Time 1…600 s
    Short Circuit 4…12 x Ie 0…5.00 s 4…12 x Ie
    Ground Fault (Residual) 0.1…1.0 x Ie 0…5.00 s 0.1…1.0 x Ie
    Ground Fault (Core balance) 0.01…25 A 0…5.00 s 0.01…25 A
    Jam 1.0…6.0 x Ie 0…5.00 s 1.0…6.0 x Ie
    Undercurrent 0.1…1.0 x Ie 0…120 s 0.1…1.0 x Ie
    Current Imbalance 5…80% 0…240 s 5…80%
    Start Monitoring 0…240 s
    RTD Temp 0…250 °C 0…250 °C
    Phase Reversal Disable, Enable
    Undervoltage 0.60…1.00 x Vnom 0…120 s 0.60…1.00 x Vnom
    Overvoltage 1.00…1.20 x Vnom 0…120 s 1.00…1.20 x Vnom
    Underpower 1…25000 kW 0…240 s 1…25000 kW
    Power Factor 0.05…0.99 0…240 s 0.05…0.99
    VAR 1…25000 kVAR 0…240 s 1…25000 kVAR
    Frequency 45…55/55…65 Hz 0…240 s 45…55/55…65 Hz
    Start Inhibit (Starts/hour) 1…15
    Speed Switch 0…240 s
      

    Product Selection

      Description Cat. No.
    Click to enlarge - 825P_Front2 Basic Unit
    Note: The minimum requirements for a complete basic system are one basic unit and one converter module.
    120…240V AC/DC 825-PD¬ 
    24…48V DC 825-PZ¬ 
    Click to enlarge - 825_MCM20 Converter Module 0.5…2.5 A 825-MCM2
    1.0…5.0 825-MCM5
    2.5…20 A 825-MCM20
    9…100 A 825-MCM180
    160…420 825-MCM420
    160…630 A 825-MCM630N
    Click to enlarge - 825-CBCT_GS Core Balance Ground Fault Sensor 100:1 825-CBCT
    Click to enlarge - RTD_Scanner RTD Scanner Module
    12 RTD input channels with individual programming for 10 W copper, 100 W nickel, 120 W nickel, or 100 W platinum. Fiber optic connection to Basic Unit. Class I, Division 2, Group T48.
    120 / 240V AC 825-PR12D
    Click to enlarge - CircuitBoards Voltage Input Card
    Monitoring of VA, VB, VC, and VN
    300V AC Line to Neutral Max. 825-PVS¬ 
    Expansion I/O Card
    (3) Inputs
    (4) Output relays
    (1) 4…20 mA analog output
    120V AC Rated Inputs 825-PIOD¬ 
    24V DC Rated Inputs 825-PIOR¬ 
    DeviceNet Communication Card
    DeviceLogix™ technology, Node address selection switches, ODVA conformance tested.
    825-PDN¬ 
    Modbus RTU Communication Card 825-PMB¬ 
    MPS Explorer Software ‡  Windows-based configuration tool  
    Operation Instructions T  Quick Start Guide 825-QS001_-EN-P
    Basic Unit User Manual 825-UM004_-EN-P
    DeviceNet Card 825-UM005_-EN-P
      
    ¬ Factory modification available. For conformal coating add CC to the cat. no. Example: Cat. No. 825-PZ becomes Cat. No. 825-PZ-CC.
    ‡ Please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
    T Detailed operation instructions ship separately from the product. Please contact your local Rockwell Automation sales office or Allen-Bradley distributor to obtain printed copies.
    Note:A no-charge download can be found at www.ab.com/industrialcontrols/products/iec_motor_controls/overload_relays/825p.html

    Accessories

      Description Cat. No.
    Click to enlarge - CEFB_P17 Bus Bars for 825-MCM180
    Three-piece set includes terminals and screws
    M8 connections
    Set of three
    4 x 16 x 102 mm (1/8 x 5/8 x 4-1/64 in.) (125 A max.)
    Universally applicable
    Weight: 230 g
    825-MVM
    M8 connections
    Set of three
    4 x 20 x 117 mm (1/8 x 25/32 x 4-39/64 in.) (180 A max.)
    Universally applicable
    825-MVM2
    Click to enlarge - CEFB_P19 M6 lower connections
    Set of three
    For mounting on Bul. 100-D95 and 100-D110 contactors with conventional coil
    825-MVS
    Click to enlarge - CEFB_P20 M8 lower connections
    Set of three
    For mounting on Bul. 100-D140, 100-D180 conventional and Bul. 100-D95E…100-D180E contactors with electronic coil
    825-MVS2
    Click to enlarge - CEFB_P12 Terminal Shields
    Set of two
    Protection class IP10 per IEC 60529 and DIN 40 050
    For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies
    100-D95, 100-D110 100-DTS110
    100-D140, 100-D180, 100-D95-E…100-D180-E 100-DTS180
    100-D210...100-D420 100-DTS420
    Click to enlarge - CEFB_P14 Terminal Lugs
    Set of two
    Protection class IP2X per IEC 60529 and DIN 40 050
    100-D95, 100-D110 100-DTB110
    100-D140, 100-D180, 100-D95E…D180E, 193-EC_F, 193-EE_F 100-DTB180
    100-D210...100-D420, 193-EC_G, 193-EF2C, 193-EE_G 100-DTB420
    Click to enlarge - 825-2_13-3 Thermal Utilization Meter For display of percent thermal capacity utilized
    Requires the use of an Expansion I/O Card
    825-MTUM
    Connection Cable (Replacement)
    Bul. 825-P to Bul. 825-MCM connection
    825-MCA
      
    Package Quantity = 3
    Discount Group MPC

    Specifications

    Electrical Ratings

    Main Circuits
    Rated Operating Voltage Ue 825-MCM2
    825-MCM5
    825-MCM20 825-MCM180
    825-MCM420
    825-MCM630N
      IEC
    CSA/UL
    400V AC
    240V AC
    690V AC
    600V AC
    1000V AC
    600V AC
    Rated Impulse Strength Uimp 2.5 kV 6 kV 8 kV
    Operating Current Range (A) 825-MCM2 825-MCM5 825-MCM20 825-MCM180 825-MCM420 825-MCM630N
    0.5…2.5 1…5 2.5…20 20…180 160…420 160…630
    Rated Continuous Thermal Current (A) 3 6 24 216 504 756
    Rated Saturation Current (A) 30 60 240 1350 3400 4600
    Rated Frequency 50/60 Hz ±3 Hz
    Voltage Input Option Card
    Rated Operating Voltage Ue 250V AC Max
    Operating Range 0.8…1.1 Ue
    Rated Continuous Voltage 300V AC
    Rated Insulation Voltage Ui 300V AC
    Rated Impulse Strength Uimp 4kV
    Rated Frequency 50/60 Hz ±5 Hz
    Control Circuits
    Supply
    Rated Supply Voltage Us 110…240V AC, 110…250V DC 24…48V DC
    Operating Range 0.8…1.1 Ue 0.8…1.1 Ue
    Rated Frequency (V AC) 50/60 Hz ±5 Hz
    Max. Power Consumption 40VA (AC) / 15W (DC) 15 W
    Output Relays
    Type of Contacts Trip Form C SPDT
    Aux1…Aux6 Form A SPST — N.O.
    Rated Insulation Voltage Ui
    300V AC
    Rated Operating Voltage Ue 240V AC
    Rated Impulse Strength Uimp 4kV
    Rated Thermal Current Ithe 5 A
    Rated Operating Current Ie 120V AC 3 A
    240V AC 1.5 A
    Contact Rating Designation B300
    Utilization Category AC15
    Contact Reliability 5 mA @ 17V
    Inputs
    Rated Operating Voltage Ue IN1 and IN2 IN3, IN4, and IN5
    24V AC/DC 120V AC/DC (825-PIOD), 24V AC/DC (825-PIOR)
    Operating Range 0.8…1.1 Ue
    Rated Insulation Voltage Ui 300V AC
    Rated Impulse Strength Uimp 4kV
    Rated Frequency (V AC) 50/60 Hz ±5 Hz
    On-State Voltage 15V 79V
    On-State Current (turn-on) 2 mA 2 mA
    Steady-State Current 15 mA 15 mA
    Off-State Voltage 5V 20V
    Off-State Current 0.5 mA 1 mA
    Transition Voltage 5…15V 20…79V
    PTC Thermistor Input
    Type of Control Unit Mark A
    Max. No. of Sensors in Series 6
    Max. Cold Resistance of PTC Sensor Chain 1500 W
    Trip Resistance 3400 W ± 150 W
    Reset Resistance 1500…1650 W
    Short-Circuit Trip Resistance 25 W ± 10 W

    Specifications, Continued

    Mechanical Ratings

    Environmental
    Ambient Temperature Storage -40…+85 °C (-40…+185 °F)
    Operation (open) -20…+60 °C (-4…+140 °F)
    Humidity (Operating) 5…95%, non-condensing
    Max. Altitude 2000 m
    Vibration (Per IEC 68-2-6) 3 G
    Shock (per IEC 68-2-27) 30 G
    Control Terminals
    Terminal Screw M3
    Cross Section (1 wire, stranded/solid) 0.14…2.5 mm2 (#20…12 AWG)
    Terminal Screw Torque 0.79 N•m (7 lb-in)

    Electromagnetic Compatibility

    Electrostatic Discharge Immunity Test Level 8 kV Air Discharge, 6 kV Contact Discharge
    Performance Criteria 1 ‡ T 
    RF Immunity Test Level 10V/m
    Performance Criteria 1 ‡ T 
    Electrical Fast Transient/Burst immunity Test Level 4 kV (Power), 2 kV (Control and Comms)
    Performance Criteria 1 ‡ T 
    Surge Immunity Test Level 2 kV L-E, 1 kV L-L
    Performance Criteria 1 ‡ T 
    Radiated Emissions Class A
    Conducted Emissions Class A
      
    ‡  Performance Criteria 1 requires the DUT to experience no degradation or loss of performance.
    T  Environment 2.

    Specifications, Continued

    RTD Scanner Module

    Supply
    Rated Supply Voltage Us 110/240V AC
    Operating Range 0.80…1.2 Us
    Rated Frequency 50/60 Hz ± 5 Hz
    Max. Power Consumption 5VA
    Rated Insulation Voltage Ui 300V AC
    Rated Impulse Strength Uimp 4 kV
    Pollution Degree 2
    Environmental
    Ambient Temperature Storage -40…+85 °C (-40…+185 °F)
    Operation (open) -20…+60 °C (-4…+140 °F)
    Humidity (Operating) 5…95%, Non-condensing
    Max. Altitude 2000 m
    Vibration (per IEC 68-2-6) 3 G
    Shock (per IEC 68-2-27) 30 G
    Inputs
    No. of Input Channels 12
    Type 3-wire
    Compatibility CU10, NI100, NI120, PT100 (per IEC 60751: 1983)
    Range -50…+250 °C
    Accuracy ± 2 °C
    Open Circuit Detection >250 °C
    Short-Circuit Detection < -50 °C
    Control Terminals
    Terminal Screw M3
    Cross Section (1 wire, stranded/solid) 0.25…2.5 mm2 (#24…12 AWG)
    Torque 0.4…0.6 N•m (3.5…5.3 lb•in.)
    Degree of Protection IP20

    Trip Curves

    Click to enlarge - 1522_IM_0044_ThermalOverlo


    Wiring Schematic¬ 

    Click to enlarge - 825-PModProtSysRelaywiring


    ¬ Open Delta Voltage Connection

    Approximate Dimensions

    Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes.

    Click to enlarge - 1552_IS_0008_RelayMounted_b


    Core Balance Current Transformer

    Click to enlarge - 825-P_CoreBalanceCurrentTr


    Approximate Dimensions, Continued

    Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes.

    Bulletin 825-MCM Converter Module

    Click to enlarge - 825-2_22-1
    Cat. No. 825-MCM2...825-MCM180
    Cat. No. 825-MCM420


    Click to enlarge - 825-2_22-2
    Cat. No. 825-MCM630N


    Dimensions
    Cat. No. a b c c1 ø d d1 d2 d3 ø e ø e1 e2 b1 b2
    825-MCM2,
    -MCM5,
    -MCM20
    120 85 102 66 5.3 5.3 100 55 2 x 2.5
    mm2
    38.5    
    825-MCM180 120   102 72 5.3 5.3 100 55 §  §  38.5 75 ‡ /§ 
    100/118
    825-MCM420 155 145 156 118 6.3 6.3 135 88 11 M10 48    
    825-MCM630N 155 145 177 118 6.3 6.3 135 88 11 M10 48    
      
    z For snapping on to DIN Rail (EN 50 022-35 x 15 or 35 x 7.5).
    T Cat. No. 825-MCM180; with bus bar or max. ø 19 mm aperture for looping the conductors.
    ‡ With Cat. No. 825-MVM.
    § Cat. No. 825-MVM2
    § See below for bus bars for Cat. No. 825-MCM180.

    Bus Bars

    Terminal Dimensions
    Cat. No. Bottom Top
    825-MVM M8 M8
      

    Approximate Dimensions, Continued

    Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

    RTD Scanner