Overload Relays

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Overload Relays > Modular Protection System

Modular Protection System

Introduction Standards Compliance and Certifications Product Overview Product Selection Accessories Specifications Approximate Dimensions
Product Overview

Description

The Bulletin 825-P Modular Protection System for motors offers a compact, modular design that uniquely allows an installer to configure a device’s functional capabilities to match the application requirements. Flexibility is also afforded by accommodating future expansion of the system as the application requirements grow. Finally, ease of installation is provided through pluggable options and accessories.

Comprehensive Protection

The 825-P Modular Protection System offers in-depth motor protection coverage by monitoring the critical elements of motor current, line voltage and temperature. High resolution settings allow the installer to configure a precise envelope of protection to achieve maximum motor utilization while avoiding damage and downtime.

ANSII No. Function ANSII No. Function
Current Elements Temperature Elements
51 Thermal Overload 49 PTC Thermistor
46 Current Imbalance/Phase Loss 49 Stator RTD
50G/51G Ground Fault 38 Bearing RTD
37 Undercurrent (Load Loss) Ambient and Other RTD
48 Overcurrent (Load Jam) Power Elements
50 Short Circuit 37 Underpower
47 Phase Reversal 55/78 Power Factor
81 Frequency Reactive Power
86 Overload Lockout
Voltage Elements Motor Starting Elements
27 Undervoltage 66 Starts/Hour
59 Overvoltage Stall - Acceleration Time Monitoring
47 Phase Reversal 14 Speed Switch Monitoring
81 Frequency 19 Reduced Voltage Starting
48 Incomplete Start
  
Note:Voltage, power, and energy elements are only available with the installation of the voltage input option card.

Full Function Metering

Current Elements Voltage Elements Power Elements Energy Elements Thermal Elements
Phase Currents Line-Line Voltages Real Power (kW) Real Energy (kWh) % Thermal Capacity Utilization
Average Current Avg. Line-Line Voltage Reactive Power (kVAR) Reactive Energy Forward (kVARh) RTD Values
% Motor Load Line-Neutral Voltages Apparent Power (kVA) Reactive Energy Reverse (kVARh)
Current Imbalance Avg. Line-Neutral Voltage Power Factor Apparent Energy (kVAh)
Ground Fault Current Voltage Imbalance
System Frequency System Frequency
  
Note:Voltage and power elements are only available with the installation of the voltage input option card.

Product Overview, Continued

Statistical Values

The 825-P Modular Protection System provides the following valuable statistical values of motor operation:

  • Elapsed time of operation


  • Stopped time


  • Percent of time running


  • Number of starts


  • Number of emergency starts


  • Date and time of last trip reset


  • Historical Data

    The 825-P Modular Protection System saves records for the five most recent trip events. Each trip event is summarized with record of the following prior to trip data capture:

  • Event day and time


  • Trip identification


  • Phase and ground current values


  • Voltage values


  • Function Overview

    Description Trip Level Setting Range Trip Delay Setting Time Warning Level Setting Range
    Motor FLA Ie 0.5…5000 A
    Locked Rotor Current 2.5…12 x Ie 50…100% TCU
    Locked Rotor Time 1…600 s
    Short Circuit 4…12 x Ie 0…5.00 s 4…12 x Ie
    Ground Fault (Residual) 0.1…1.0 x Ie 0…5.00 s 0.1…1.0 x Ie
    Ground Fault (Core balance) 0.01…25 A 0…5.00 s 0.01…25 A
    Jam 1.0…6.0 x Ie 0…5.00 s 1.0…6.0 x Ie
    Undercurrent 0.1…1.0 x Ie 0…120 s 0.1…1.0 x Ie
    Current Imbalance 5…80% 0…240 s 5…80%
    Start Monitoring 0…240 s
    RTD Temp 0…250 °C 0…250 °C
    Phase Reversal Disable, Enable
    Undervoltage 0.60…1.00 x Vnom 0…120 s 0.60…1.00 x Vnom
    Overvoltage 1.00…1.20 x Vnom 0…120 s 1.00…1.20 x Vnom
    Underpower 1…25000 kW 0…240 s 1…25000 kW
    Power Factor 0.05…0.99 0…240 s 0.05…0.99
    VAR 1…25000 kVAR 0…240 s 1…25000 kVAR
    Frequency 45…55/55…65 Hz 0…240 s 45…55/55…65 Hz
    Start Inhibit (Starts/hour) 1…15
    Speed Switch 0…240 s