Catalogs > Industrial Controls Catalog > Motor Control, IEC > Overload Relays > Overload Relay Code Selection for IEC Starters
Overload Relay Code Selection for IEC Starters
Bulletin 193 E1 Plus electronic overload relay for 3-phase applications: Selectable Trip Class 10, 15, 20, 30, selectable manual/auto reset
| For use with: Bulletin 105, 106, 109, 112, 113, 120E, 132, and 133 |
Full Load Current Range [A] | 3-Phase Overload Relay Code | |||||||||
| C30 | C23 | C16 | C12 | C09 | 0.10…0.5 | E1A | |||||
| 0.2…1.0 | E1B | ||||||||||
| 1.0…5.0 | E1C | ||||||||||
| 3.2…16 | E1D | ||||||||||
| 5.4…27 | E1E | ||||||||||
| C43 | C37 | C30 | 5.4…27 | E1E | |||||||
| 9.0…45 | E1F | ||||||||||
| C85 | C72 | C60 | 18…90 | E1G | |||||||
Bulletin 193 E1 Plus electronic overload relay for 3-phase applications:
Trip Class 10 only, manual reset
| For use with: Bulletin 105, 106, 109, 112, 113, 120E, 132, and 133 |
Full Load Current Range [A] | 3-Phase Overload Relay Code | ||||
| C30 | C23 | C16 | C12 | C09 | 0.10…0.5 | D1A |
| 0.2…1.0 | D1B | |||||
| 1.0…5.0 | D1C | |||||
| 3.2…16 | D1D | |||||
| 5.4…27 | D1E | |||||
Bulletin 193 E1 Plus electronic overload relay for 1-phase applications:
Selectable Trip Class 10, 15, 20, 30; selectable manual/auto reset
| For use with: Bulletin 109 |
Full Load Current Range [A] | 1-Phase Overload Relay Code | |||||||||
| C30⋆ | C23 | C16 | C12 | C09 | 0.1…0.5 | E1P | |||||
| 3.2…16 | E1R | ||||||||||
| 5.4…27 | E1S | ||||||||||
| C43 | C37 | C30 | 9.0…45 | E1T | |||||||
| C85 | C72 | C60 | 18…90 | E1U | |||||||
| ⋆ For Bulletin 113 combination starters and Bulletin 133 circuit breaker-type pump control panels only. | |||||||||||
Consult your local Rockwell Automation sales office or Allen-Bradley distributor for availability and dimensions.