Bulletin 193 E1 Plus Solid-State Overload Relays
|
E1 Plus Solid-State Overload Relays
- Self-powered
- Phase loss protection
- Wide adjustment range (5:1)
- Over-molded power connections
- 1 N.O. and 1 N.C. isolated auxiliary contacts (B600 Rated)
- Low energy consumption (150 mW)
- Ambient temperature compensation
- Visible trip indication
193-ED version offers:
- 0.1…45 A current range
- Fixed Trip Class 10
- Manual reset
193-EE version offers:
- 0.1…800 A current range
- Selectable Trip Class (10, 15, 20, or 30)
- Selectable manual/auto-manual reset
- Single- and three-phase devices
- Optional cage clamp control terminals (Bul. 193R-EE only)
Your order must include 1) the Cat. No. of overload relay selected, and 2) if required, Cat. No. of any accessories.
Standards Compliance and Certifications
Standards Compliance
-
IEC/EN 60947-4-1
IEC/EN 60947-5-1
CSA 22.2 No. 14
UL 508
Certifications
-
CE¬cULus Listed
ATEX (pending)
C-Tick
CCC
Product Overview
Accurate, Reliable Performance
Current measurement-based protection
While electromechanical overload relays pass motor current through heating elements to provide an indirect simulation of motor heating, the E1 Plus Overload Relay directly measures motor current. Current measurement-based overload protection more accurately models a motors thermal condition. Furthermore, ambient temperature does not impact the performance of current measurement-based designs over the specified temperature operating range.
Electronic design
Thermal modeling is performed electronically with precision solid-state components, where at the heart of the E1 Plus Overload Relay is an application-specific integrated circuit (ASIC). The ASIC continually processes motor current data to accurately maintain the time-current status of the motor thermal capacity utilization value.
Thermal memory
A thermal memory circuit allows the E1 Plus Overload Relay to model the heating and cooling effects of motor on and off periods. This ensures accurate protection for both hot and cold motors.
Enhanced phase loss protection
A separate phase loss detection circuit incorporated into the E1 Plus Overload Relay allows it to respond quickly to phase loss conditions; typical reaction time is 3 seconds.
Easy to Select and Apply
Straightforward installation
The self-powered design means that the E1 Plus Overload Relay installs in the same manner as traditional overload relays. Device setup is accomplished by simply dialing the setting potentiometer to the motor FLA rating. The low energy consumption of the electronic design minimizes temperature rise issues inside control cabinets.
Wide adjustment range
A wide 5:1 adjustment range results in the need for half as many catalog numbers as the bimetallic alternative in order to cover the same current range. This helps to reduce inventory carrying costs and affords greater installation flexibility for dual voltage machines. Evenly spaced setting tick marks enhance the ease of installation setup.
Rugged Construction
Over-molded power connections
The unique line-side over-molded power connections make for a sturdy two-component starter assembly that is unmatched in the industry. The pre-formed power connections allow easy starter assembly — every time.
Current transformers
The current transformers are secured separately in the overload housing to ensure the greatest degree of resistance to shock and vibration conditions. Varnished laminations ensure consistent performance and provide additional protection against corrosion.
Latching relay
The robust design of the bi-polar latching relay provides reliable trip and reset performance for the most demanding of applications. The self-enclosed relay offers additional environmental protection for use in industrial applications.
Application Flexibility
Isolated Contacts
The isolated contact configuration allows the N.C. and N.O. contacts to be applied in circuits operating at different voltage levels and without polarity restrictions. The B600 contact rating affords application in circuits rated to 600V.
DIP switch settings
193-EE devices offer DIP switch settings to select the trip class (10, 15, 20 or 30) and the reset mode (manual or automatic), making these devices extremely versatile.
Side-Mount Expansion Modules
Through the use of optional side-mounted accessory modules, functionality of the E1 Plus overload relays can be cost effectively expanded and machine operation and protection enhanced. Direct mounting to the left side of the 193-EE and 592-EE E1 Plus overload relays means that only 18 mm is added to the overall product width. The side-mounted modules electronically interface with the E1 Plus overload relay so that all control circuit connections are made at the E1 Plus overload relay terminals.
E1 Plus DeviceNet™ Communication Module
The Bul. 193-EDN DeviceNet Communication Side-Mount Module provides a cost-effective, seamless deployment of motor starters onto the Integrated Architecture™ as an accessory for the E1 Plus electronic overload relay. The DeviceNet module provides Integrated I/O (2 inputs and 1 output) providing local connection of motor starter-related I/O. The DeviceNet module offers expanded protective functions including overload warning, jam protection, and underload warning. The DeviceNet module also allows access to average motor current (percentage of FLA setting), percentage of thermal capacity usage, device status, trip & warning identification, and trip history which allows continual monitoring of motor performance.
E1 Plus Remote Reset Module
The Bul. 193-ERR Remote Reset Module is available for applications that require remote reset of the E1 Plus overload relays after a trip occurs.
E1 Plus Jam Protection Module with Remote Reset
The Bul. 193-EJM Jam Protection Module provides front-accessible DIP switches which offers flexibility to provide jam protection to match application requirements. Selections are available for enabling or disabling the jam protection function and remote reset operation. Jam trip level settings are available at 150%, 200%, 300%, and 400% of full load current setting. Trip delay settings of 1/2, 1, 2, and 4 seconds are available to minimize nuisance tripping in applications where intermittent short-duration overloading is permissible.
E1 Plus Ground Fault Module with Remote Reset
The Bul. 193-EGF Ground Fault Protection Module offers front-accessible DIP switches providing flexibility to configure ground fault protection to match application requirements. Selections are available for enabling or disabling the ground fault protection function and remote reset operation. Ground fault trip level settings are available in four ranges: 20…100 mA (resistive loads only, for motor loads consult your local Allen‑Bradley distributor), 100…500 mA, 0.2…1 A, and 1…5 A. Within each range, the specific ground fault trip level can be set (20%, 35%, 50%, 65%, 80%, 90%, or 100% of the maximum ground fault setting). Trip delay is fixed at 50 ms ± 20 ms.
E1 Plus Ground Fault/Jam Module with Remote Reset
The Bul. 193-EGJ Ground Fault/Jam Protection Module offers front-accessible DIP switches to provide flexibility to configure ground fault and jam protection to match application requirements. The ground fault selections are the same as the Bul. 193-EGF Ground Fault Protection Module. In addition to ground fault, this module offers selectable fixed jam protection. The user can enable or disable jam protection from the DIP switches. The jam protection is fixed at 400% of the full load current setting with a 0.5 second trip delay.
E1 Plus PTC Module with Remote Reset
The Bul. 193-EPT PTC Side-Mount Module provides two terminals for the connection of positive temperature coefficient (PTC) thermistor sensors. PTC sensors are commonly embedded in the motor stator windings to monitor winding temperature. PTC sensors react to actual temperature, so enhanced motor protection can be provided to address conditions like obstructed cooling and high ambient temperature.
Catalog Number Explanation
| 193 | | EE | C | B | ||
| a | b | c | d |
| a | b | c | d | |||||||
| Bulletin Number | Type | Adjustment Range (A) | Bulletin 100 Contactor Size | |||||||
| Three-Phase | Code | Description | ||||||||
| Code | Description | Code | Description | Code | Description | B | C09…C23 | |||
| 193 | IEC Three-Phase | ED1 | Fixed Trip Class 10 | A | 0.1…0.5 | D | C30…C43 | |||
| 193R | IEC Three-Phase, Cage Clamp | EE | Selectable Trip Class | B | 0.2…1.0 | E | C60…C85 | |||
| 193S | IEC Single-Phase | C | 1.0…5.0 | F | D95…D180 | |||||
| 592 | NEMA Three-Phase | D | 3.2…16 | G | D210…D420 | |||||
| 592S | NEMA Single-Phase | E | 5.4…27 | H | D630…D860 | |||||
| F | 9…45 | Bulletin 500 NEMA Contactor Size | ||||||||
| G | 18…90 | Code | Description | |||||||
| H | 30…150 | T | Size 00 | |||||||
| J | 40…200 | C | Size 0…2 | |||||||
| K | 60…300 | D | Size 3 | |||||||
| L | 100…500 | Panel/DIN Rail Mount | ||||||||
| M | 120…600 | Code | Description | |||||||
| N | 160…800 | P | Integrated panel mount and pass-through wiring | |||||||
| Single-Phase | Z | Panel mount with external current transformers | ||||||||
| Code | Description | |||||||||
| P | 1.0…5.0 | |||||||||
| R | 3.2…16 | |||||||||
| S | 5.4…27 | |||||||||
| T | 9…45 | |||||||||
| U | 18…90 | |||||||||
Product Selection
Bulletin 193-ED Three-Phase Devices
- Fixed Trip Class 10
- Manual reset
- Screw-type control terminals
| Mounts to Contactor | Adjustment Range [A] | Cat. No. |
| 100-C09…100-C23 | 0.1…0.5 | 193-ED1AB |
| 0.2…1.0 | 193-ED1BB | |
| 1.0…5.0 | 193-ED1CB | |
| 3.2…16 | 193-ED1DB | |
| 5.4…27 | 193-ED1EB | |
| 100-C30…100-C43 | 5.4…27 | 193-ED1ED |
| 9…45 | 193-ED1FD | |
| Integrated panel/DIN Rail mount and pass-thru wiring | 1.0…5.0 | 193-ED1CP |
| 3.2…16 | 193-ED1DP | |
| 5.4…27 | 193-ED1EP | |
Bulletin 193-EE Three-Phase Devices
- Selectable Trip Class (10, 15, 20, 30)
- Selectable manual/auto-manual reset
- Screw-type control terminals
| Mounts to Contactor | Adjustment Range [A] | Cat. No. | |
| 100-C09…100-C23 | 0.1…0.5 | | 193-EEAB |
| 0.2…1.0 | | 193-EEBB | |
| 1.0…5.0 | | 193-EECB | |
| 3.2…16 | | 193-EEDB | |
| 5.4…27 | | 193-EEEB | |
| 100-C30…100-C43 | 5.4…27 | | 193-EEED |
| 9…45 | | 193-EEFD | |
| 100-C60…100-C85 | 18…90 | | 193-EEGE |
| 100-D95…100-D180 | 18…90 | T | 193-EEGF |
| 30…150 | T | 193-EEHF | |
| 40…200 | T | 193-EEJF | |
| 55…110 | T | 193-EEVF | |
| 100-D210…100-D420 | 40…200 | T | 193-EEJG |
| 60…300 | T | 193-EEKG | |
| 100…500 | T | 193-EELG | |
| 100-D630…100-D860 | 120…600 | T | 193-EEMH |
| 160…800 | T | 193-EENH | |
| Integrated panel/DIN Rail mount and pass-thru wiring | 1.0…5.0 | | 193-EECP |
| 3.2…16 | | 193-EEDP | |
| 5.4…27 | | 193-EEEP | |
| Package Quantity = 1 | |||
| Spring Clamp Control Terminals To order, change the Bulletin number in the listed cat. no. from 193 to 193R (Example: Cat. No. 193-EEFD becomes Cat. No. 193R-EEFD). | |||
| T Does not include terminal lugs. See Accessories. | |||
Bulletin 193S-EE Single-Phase Devices
- Selectable Trip Class (10, 15, 20, 30)
- Selectable manual/auto-manual reset
- Screw-type control terminals
| Mounts to Contactor | Adjustment Range [A] | Cat. No. |
| 100-C09…100-C23 | 1.0…5.0 | 193S-EEPB |
| 3.2…16 | 193S-EERB | |
| 5.4…27 | 193S-EESB | |
| 100-C30…100-C43 | 9…45 | 193S-EETD |
| 100-C60…100-C85 | 18…90 | 193S-EEUE |
| Integrated panel/DIN Rail mount and pass-thru wiring | 1.0…5.0 | 193S-EEPP |
| 3.2…16 | 193S-EERP | |
| 5.4…27 | 193S-EESP | |
Bulletin 193 Panel Mount Devices for use with External Current Transformers § §
- Selectable Trip Class (10, 15, 20, 30)
- Selectable manual/auto-manual reset
| CT Ratio | Adjustment Range [A] | Cat. No. |
| 150:5 | 30…150 | 193-EEHZ |
| 200:5 | 40…200 | 193-EEJZ |
| 300:5 | 60…300 | 193-EEKZ |
| 400:5 | 80…400 | 193-EEWZ |
| 500:5 | 100…500 | 193-EELZ |
| 600:5 | 120…600 | 193-EEMZ |
| 800:5 | 160…800 | 193-EENZ |
§ Current Transformers supplied by customer, refer to Specifications for proper current transformer selection.
§ Order panel adapter, Cat. No. 193-EPB, separately.
Accessories
Side-Mount Expansion Modules¬
| Function | E1 Plus (Cat. No. 193/592-EE_) |
E1 Plus w/ Jam Module (Cat. No. 193-EJM) |
E1 Plus w/ Ground Fault Module¬ (Cat. No. 193-EGF) |
E1 Plus w/ Ground Fault/Jam Module¬ (Cat. No. 193-EGJ) |
E1 Plus w/ PTC Module (Cat. No. 193-EPT) |
E1 Plus w/ Remote Reset Module (Cat. No. 193-ERR) |
|
| Manual/Automatic Reset | X | X | X | X | X | X | |
| Selectable Trip Class | 10 | X | X | X | X | X | |
| 15 | X | X | X | X | X | ||
| 20 | X | X | X | X | X | ||
| 30 | X | X | X | X | X | ||
| Jam Protection | On or Off | — | X | — | X | — | — |
| Trip Level | — | Adjustable 150/200/300/400% | — | Fixed @ 400% | — | — | |
| Trip Delay | — | Adjustable 0.5/1.0/2.0/4.0 s | — | Fixed @ 0.5 s | — | — | |
| Inhibit | — | Dynamic Inhibit | — | Dynamic Inhibit | — | — | |
| Ground Fault Protection | Type | — | — | Core-Balanced Ground Fault Protection¬ | Core-Balanced Ground Fault Protection¬ | — | — |
| On or Off | — | — | X | X | — | — | |
| Trip Level | — | — | Adjustable 20 mA…5 A§ | Adjustable 20 mA…5 A§ | — | — | |
| Trip Delay | — | — | Fixed @ 50 ms ± 20 ms |
Fixed @ 50 ms ± 20 ms |
— | — | |
| Inhibit | — | — | Dynamic Inhibit | Dynamic Inhibit | — | — | |
| PTC Protection | PTC Overtemperature Trip | — | — | — | — | X | — |
| PTC Open Circuit | — | — | — | — | X | — | |
| PTC Short Circuit | — | — | — | — | X | — | |
| Remote Reset Capability | — | X | X | X | X | X | |
| Fault Indication | — | — | X | X | X | — | |
| Dynamic Inhibit: Protective function is enabled after the motor current goes above 150% and then falls to below 125%. | |||||||
| ¬ Requires use of an external ground fault sensor, Cat. No. 193-CBCT_. | |||||||
| § From 20…100 mA for resistive loads only. | |||||||
Marking Systems
Uniform labeling materials for contactors, motor starting equipment, timing relays and circuit breakers
Specifications
3-Pole Terminal Blocks
| Cat. No. 100-DTB180 | Cat. No. 100-DTB420 |
| (A) 6…1/0 AWG, 16…50 mm2 (B) 6 AWG…250 MCM, 16…120 mm2 90…110 lbin., 10…12 Nm |
(2) 4 AWG…600 MCM, 25…240 mm2 180…220 lbin., 20…25 Nm |
Terminal Lug Kits
| Cat. No. 100-DLE110 | Cat. No. 100-DL180 | Cat. No. 100-DL420 | Cat. No. 100-DL630 | Cat. No. 100-DL860 |
| Lug: 6…2/0 AWG, 16…70 mm2 90…110 lbin., 10…12 Nm Terminal: 13/32 in., 10 mm 150 lbin., 17 Nm |
Lug: 6 AWG…250 MCM, 16…120 mm2 90…110 lbin., 10…12 Nm Terminal: 1/2 in., 13 mm 275 lbin., 16 Nm |
Lug: 2 AWG…350 MCM, 375 lbin., 42 Nm Terminal: 11/16 in., 17 mm 140 lbin., 16 Nm |
Lug: 2/0 AWG…500 MCM, 70…240 mm2 400 lbin., 45 Nm Terminal: 3/4 in., 19 mm 600 lbin., 68 Nm |
Lug: 2/0 AWG…500 MCM, 70…240 mm2 400 lbin., 45 Nm Terminal: 3/4 in., 19 mm 600 lbin., 68 Nm |
| Environmental Ratings | ||
| Ambient Temperature | Storage Operating |
-40…+85 °C (-40…+185 °F) -20…+60 °C (-4…+140 °F) |
| Humidity | Operating Damp Heat |
5…95% Non-condensing per IEC 68-2-3 and IEC 68-2-30 |
| Vibration (per IEC 68-2-6) | 3 G | |
| Shock (per IEC 68-2-27) | 30 G | |
| Max. Altitude | 2000 m | |
| Pollution Environment | Pollution Degree 3 | |
| Degree of Protection | IP20 | |
| Protection | ||
| Type of Relay | Ambient Compensated, Time Delay, Phase Loss Sensitive | |
| Nature of Relay | Solid-State | |
| Trip Rating | 120% FLA | |
| Trip Class | Type ED | 10 |
| Type EE | 10, 15, 20, 30 | |
| Reset Mode | Type ED | Manual |
| Type EE | Automatic or Manual | |
| Electromagnetic Compatibility | ||
| Electrostatic Discharge Immunity | Test Level | 8 kV Air Discharge, 6 kV Contact Discharge |
| Performance Level | 1 T | |
| RF Immunity | Test Level | 10 V/m |
| Performance Level | 1 T | |
| Electrical Fast Transient/Burst Immunity | Test Level | 4 kV |
| Performance Level | 1 T | |
| Surge Immunity | Test Level | 2 kV (L-E), 1 kV (L-L) |
| Performance Level | 1 T | |
| Performance Criteria 1 requires the device under test (DUT) to experience no degradation or loss of performance. | ||
| T Environment 2. | ||
General
| Cat. No. 193-ED1_B, 193-EE_B | Cat. No. 193-EE_D | Cat. No. 193-EE_E | |
| Standards | UL508, CSA C22.2 No. 14, NEMA ICS 2-1993 Part 4, EN 60947-4-1, EN 60947-5-1 | ||
| Certifications | CE, cULus, ATEX (pending), C-Tick, CCC | ||
| Approximate Weights (unpackaged) |
0.25 kg (0.55 lb) |
0.25 kg (0.55 lb.) |
0.52 kg (1.06 lb.) |
External Current Transformers (for use with cat. nos. 193-EE_Z)
The user shall provide one current transformer (CT) for each motor phase,and shall connect the CTs secondary leads to the appropriate E1 Plus overload relay power terminals, as shown in current transformers wiring diagrams. The CT shall have the appropriate ratio (refer to the product nameplate or product description). Additionally, the CT shall be selected to be capable of providing the required VA to the secondary load, which includes the E1 Plus overload relay burden at the rated secondary current and the wiring burden. Finally, the CT shall be rated for protective relaying to accomodate the high inrush currents associated with motor startup, and shall have an accuracy of <±2% over its normal operating range. Typical CT ratings include (Instrument Transformers, Inc. — Model #23 or equivalent):
| ANSI (USA) | Class C5B0.1 |
| CSA (Canada) | Class 10L5 |
| IEC (Europe) | 5 VA Class 5P10 |
Wiring Schematic
|
|
|
Trip Curves
Typical reset time for 193-EE devices set to automatic reset mode is 120 seconds.
Trip Class 10
|
Trip Class 15
|
Trip Class 20
|
Trip Class 30
|
Trip Curve Legend: Cold Trip ———————
Hot Trip
Approximate Dimensions
Approximate dimensions are shown in millimeters (inches). Dimensions are not to be used for manufacturing purposes.
Bulletin 100-C Contactor Mounted
|
| Overload Cat. No. |
Contactor Cat. No. |
Width A | Height B | Depth C | D | E1 | E2 | F | H1 | H2 |
| 193-ED__B 193-EE__B 193R-EE__B 193S-EE__B |
100-C09, -C12, -C16, -C23 | 45 (1-25/32) |
146.6 (5-25/32) |
85.2 (3-23/64) |
4.5 (3/16) |
13.9 (35/64) |
24.5 (31/32) |
86.5 (3-13/32) |
60 (2-23/64) |
35 (1-3/8) |
| 193-EE__D 193R-EE__D 193S-EE__D |
100-C30, -C37 | 45 (1-25/32 |
146.6 (5-25/32) |
101.2 (3-63/64) |
4.5 (3/16) |
13.9 (35/64) |
24.5 (31/32) |
104 (4-3/32) |
60 (2-23/64) |
35 (1-3/8) |
| 193-EE__D 193R-EE__D 193S-EE__D |
100-C43 | 54 (2-1/8) |
146.6 (5-25/32) |
101.2 (3-63/64) |
4.5 (3/16) |
18.9 (3/4) |
24.5 (31/32) |
104 (4-3/32) |
60 (2-23/64) |
45 (1-25/32) |
| 193-EE__E 193R-EE__E 193S-EE__E |
100-C60, -C72, -C85 |
72 (2-53/64) |
192.3 (7-37/64) |
120.4 (4-3/4) |
5.4 (7/32) |
23.8 (15/16) |
29 (1-9/64) |
125.5 (4-15/16) |
100 (3-15/16) |
55 (2-11/64) |
Bulletin 100-D Contactor Mounted
|
| Overload Cat. No. |
Contactor Cat. No. |
Width A | Height B | Height B1 | Depth C | D | E1 | E2 | |
| Without Terminal Covers | With Terminal Covers | (Reset) | |||||||
| 193-EE__F | 100-D95, -D110 | 120 (4.72) |
336.3 (13.24) |
418 (16.46) |
311.8 (12.27) |
152.7 (6.01) |
156 (6.14) |
3.6 (0.14) |
226.3 (8.91) |
| 193-EE__F | 100-D140, -D180 | 120 (4.72) |
339.8 (13.38) |
418 (16.46) |
317.8 (12.51) |
152.7 (6.01) |
156 (6.14) |
3.6 (0.14) |
226.3 (8.91) |
| 193-EE__G | 100-D210, -D250, -D300, -D420 | 155 (6.10) |
385.8 (15.19) |
487.4 (19.19) |
360.8 (14.2) |
176.5 (6.95) |
180 (7.09) |
3.6 (0.14) |
265.2 (10.44) |
| 193-EE__H | 100-D630, -D860 | 255 (10.04) |
552 (21.73) |
915 (36.02) |
508 (20) |
269.3 (10.6) |
270.7 (10.66) |
3.6 (0.14) |
384.1 (15.12) |
| Overload Cat. No. |
Contactor Cat. No. |
F | G | H | J | K | øM |
| 193-EE__F | 100-D95, -D110 | 45 (1-25/32) |
100 (3.94) |
145 (5.71) |
135 (5.31) |
22.3 (0.88) |
8 - 5.6 (8 - 0.22) |
| 193-EE__F | 100-D140, -D180 | 45 (1-25/32 |
100 (3.94) |
145 (5.71) |
135 (5.31) |
22.3 (0.88) |
8 - 5.6 (8 - 0.22) |
| 193-EE__G | 100-D210, -D250, -D300, -D420 | 54 (2-1/8) |
130 (5.12) |
180 (7.09) |
140 (5.51) |
23.5 (0.93) |
8 - 6.5 (8 - 0.26) |
| 193-EE__H | 100-D630, -D860 | 52.5 (2.07) |
226 (8.90) |
230 (9.06) |
108 (4.25) |
109 (4.29) |
8 - 13 (8 - 0.51) |
Panel Adapter Mounted
Approximate dimensions are shown in millimeters (inches). Dimensions are not to be used for manufacturing purposes.
|
| Panel Adapter Cat. No. |
Overload Cat. No. |
Width A | Height B | Depth C | D | E1 | E2 | F | H1 | H2 | H3 | J |
| 193-EPB | 193-ED__B 193-EE__B 193R-EE__B 193S-EE__B |
45 (1-25/32 |
116.5 (4-19/16) |
92.7 (3-21/32) |
4.4 (11/64) |
11.4 (0.45) |
57.9 (2-9/32) |
62.5 (2-15/32) |
95 (3-3/4) |
30 (1-3/16) |
75 (2-31/32) |
52.1 (2-3/64) |
| 193-EPD | 193-EE__D 193R-EE__D 193S-EE__D |
45 (1-25/32 |
112.4 (4-7/16) |
108.7 (4-9/32) |
4.4 (11/64) |
11.4 (0.45) |
57.9 (2-9/32) |
62.5 (2-15/32) |
95 (3-3/4) |
30 (1-3/16) |
75 (2-31/32) |
52.1 (2-3/64) |
| 193-EPE | 193-EE__E 193R-EE__E 193S-EE__E |
72 (2-53/64) |
107.4 (4-15/64) |
127 (5/32) |
5.5 (5/32) |
26.4 (1-1/32) |
54.5 (2-9/64) |
48.3 (1-29/32) |
90 (3-23/64) |
60 (2-23/64) |
— | 43.3 (1-45/64) |
DIN Rail / Panel Adapter - Terminal Cross Sections
| Cat. No. 193-EPB T | Cat. No. 193-EPD T | Cat. No. 193-EPE | ||
| Flexible-Stranded with Ferrule | Single Conductor | 1.0…4.0 mm2 | 2.5…16 mm2 | 4.0…35 mm2 |
| Torque | 1.8 Nm | 2.3 Nm | 4.0 Nm | |
| Two Conductor | 1.0…4.0 mm2 | 2.5…10 mm2 | 4.0…25 mm2 | |
| Torque | 1.8 Nm | 2.3 Nm | 4.0 Nm | |
| Coarse-Stranded/Solid | Single Conductor | 1.5…6.0 mm2 | 2.5…25 mm2 | 4.0…50 mm2 |
| Torque | 1.8 Nm | 2.3 Nm | 4.0 Nm | |
| Two Conductor | 1.5…6.0 mm2 | 2.5…16 mm2 | 4.0…35 mm2 | |
| Torque | 1.8 Nm | 2.3 Nm | 4.0 Nm | |
| Stranded/Solid | Single Conductor | 14…8 AWG | 16…6 AWG | 12…1 AWG |
| Torque | 16 lb-in. | 20 lb-in. | 35 lb-in. | |
| Two Conductor | 14…10 AWG | 16…6 AWG | 12…2 AWG | |
| Torque | 16 lb-in. | 20 lb-in. | 35 lb-in. | |
| T For multiple conductor applications, the same size and style wire must be used. | ||||