Catalogs > Industrial Controls Catalog > Motor Control, IEC > Overload Relays > Bulletin 193 E1 Plus Solid-State Overload Relays
Bulletin 193 E1 Plus Solid-State Overload Relays
| Introduction | Standards Compliance and Certifications | Product Overview | Catalog Number Explanation |
| Product Selection | Accessories | Specifications | Approximate Dimensions |
3-Pole Terminal Blocks
| Cat. No. 100-DTB180 | Cat. No. 100-DTB420 |
| (A) 6…1/0 AWG, 16…50 mm2 (B) 6 AWG…250 MCM, 16…120 mm2 90…110 lbin., 10…12 Nm |
(2) 4 AWG…600 MCM, 25…240 mm2 180…220 lbin., 20…25 Nm |
Terminal Lug Kits
| Cat. No. 100-DLE110 | Cat. No. 100-DL180 | Cat. No. 100-DL420 | Cat. No. 100-DL630 | Cat. No. 100-DL860 |
| Lug: 6…2/0 AWG, 16…70 mm2 90…110 lbin., 10…12 Nm Terminal: 13/32 in., 10 mm 150 lbin., 17 Nm |
Lug: 6 AWG…250 MCM, 16…120 mm2 90…110 lbin., 10…12 Nm Terminal: 1/2 in., 13 mm 275 lbin., 16 Nm |
Lug: 2 AWG…350 MCM, 375 lbin., 42 Nm Terminal: 11/16 in., 17 mm 140 lbin., 16 Nm |
Lug: 2/0 AWG…500 MCM, 70…240 mm2 400 lbin., 45 Nm Terminal: 3/4 in., 19 mm 600 lbin., 68 Nm |
Lug: 2/0 AWG…500 MCM, 70…240 mm2 400 lbin., 45 Nm Terminal: 3/4 in., 19 mm 600 lbin., 68 Nm |
| Environmental Ratings | ||
| Ambient Temperature | Storage Operating |
-40…+85 °C (-40…+185 °F) -20…+60 °C (-4…+140 °F) |
| Humidity | Operating Damp Heat |
5…95% Non-condensing per IEC 68-2-3 and IEC 68-2-30 |
| Vibration (per IEC 68-2-6) | 3 G | |
| Shock (per IEC 68-2-27) | 30 G | |
| Max. Altitude | 2000 m | |
| Pollution Environment | Pollution Degree 3 | |
| Degree of Protection | IP20 | |
| Protection | ||
| Type of Relay | Ambient Compensated, Time Delay, Phase Loss Sensitive | |
| Nature of Relay | Solid-State | |
| Trip Rating | 120% FLA | |
| Trip Class | Type ED | 10 |
| Type EE | 10, 15, 20, 30 | |
| Reset Mode | Type ED | Manual |
| Type EE | Automatic or Manual | |
| Electromagnetic Compatibility | ||
| Electrostatic Discharge Immunity | Test Level | 8 kV Air Discharge, 6 kV Contact Discharge |
| Performance Level | 1 T | |
| RF Immunity | Test Level | 10 V/m |
| Performance Level | 1 T | |
| Electrical Fast Transient/Burst Immunity | Test Level | 4 kV |
| Performance Level | 1 T | |
| Surge Immunity | Test Level | 2 kV (L-E), 1 kV (L-L) |
| Performance Level | 1 T | |
| Performance Criteria 1 requires the device under test (DUT) to experience no degradation or loss of performance. | ||
| T Environment 2. | ||
General
| Cat. No. 193-ED1_B, 193-EE_B | Cat. No. 193-EE_D | Cat. No. 193-EE_E | |
| Standards | UL508, CSA C22.2 No. 14, NEMA ICS 2-1993 Part 4, EN 60947-4-1, EN 60947-5-1 | ||
| Certifications | CE, cULus, ATEX (pending), C-Tick, CCC | ||
| Approximate Weights (unpackaged) |
0.25 kg (0.55 lb) |
0.25 kg (0.55 lb.) |
0.52 kg (1.06 lb.) |
External Current Transformers (for use with cat. nos. 193-EE_Z)
The user shall provide one current transformer (CT) for each motor phase,and shall connect the CTs secondary leads to the appropriate E1 Plus overload relay power terminals, as shown in current transformers wiring diagrams. The CT shall have the appropriate ratio (refer to the product nameplate or product description). Additionally, the CT shall be selected to be capable of providing the required VA to the secondary load, which includes the E1 Plus overload relay burden at the rated secondary current and the wiring burden. Finally, the CT shall be rated for protective relaying to accomodate the high inrush currents associated with motor startup, and shall have an accuracy of <±2% over its normal operating range. Typical CT ratings include (Instrument Transformers, Inc. — Model #23 or equivalent):
| ANSI (USA) | Class C5B0.1 |
| CSA (Canada) | Class 10L5 |
| IEC (Europe) | 5 VA Class 5P10 |
Wiring Schematic
|
|
|
Trip Curves
Typical reset time for 193-EE devices set to automatic reset mode is 120 seconds.
Trip Class 10
|
Trip Class 15
|
Trip Class 20
|
Trip Class 30
|
Trip Curve Legend: Cold Trip ———————
Hot Trip