Bulletin 193-T Bimetallic Overload Relays
|
Bulletin 193-T — Bimetallic Overload Relays
- Phase failure sensitivity
- Temperature compensation
- Auxiliary switch (1 N.O. and 1 N.C. contact)
- Test/Stop button
- Manual/Auto reset button
- Individual mounting
- Protection of EEX electric motors (PTB)
- Trip Free construction
Bulletin 193-T thermal overload relays are designed for use with Bulletin 100-C contactors and Bulletin 104-C reversing contactors. These class 10 ambient compensated thermal overload relays use integral heater elements; therefore, additional heater elements are not required. Further, the design includes a differential mechanism for sensitivity to single-phase conditions. The trip setting is adjustable over the listed motor full load current range. The overload relay can be operated in a manual or automatic reset mode. An isolated normally open contact is standard. An anti-tamper shield is available and snaps on the front of the overload relay to discourage field adjustments of the trip setting and reset mode.
Standards Compliance and Certifications
Standards Compliance
IEC 60947-4
BS 5424
VDE 0660
IEC 60947-4 Type 2
Coordination
Certifications
UL Listed
CSA Certified
CE
Product Selection
Thermal Overload Relays
| For Use With¬ | Setting Range [A]T | Cat. No. |
| 100-C09…100-C37 | 0.1…0.16 | 193-TAA16 |
| 0.16…0.24 | 193-TAA24 | |
| 0.24…0.4 | 193-TAA40 | |
| 0.4…0.6 | 193-TAA60 | |
| 0.6…1.0 | 193-TAB10 | |
| 1.0…1.6 | 193-TAB16 | |
| 1.6…2.4 | 193-TAB24 | |
| 2.4…4 | 193-TAB40 | |
| 4…6 | 193-TAB60 | |
| 6…10 | 193-TAC10 | |
| 100-C12…100-C37 | 10…16 | 193-TAC16 |
| 100-C23…100-C37 | 16…24 | 193-TAC24 |
| 100-C30…100-C43 | 18…30 | 193-TBC30 |
| 100-C37…100-C43 | 30…45 | 193-TBC45 |
| 100-C60…100-C85 | 18…30 | 193-TCC30 |
| 30…45 | 193-TCC45 | |
| 45…60 | 193-TCC60 | |
| 100-C72…100-C85 | 60…75 | 193-TCC75 |
| Separate Mounting Required | 70…90 | 193-TDC90 |
| ¬ Bulletin 193-T overload relays should not be direct mounted with DC coil contactors. | ||
| T To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58. | ||
| For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current. | ||
Accessories
Add-On Modules
Ä Coil Voltage Code
The catalog number as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no.
Example: 120V, 60Hz: Cat. No. 193-ER1Ä becomes Cat. No. 193-ER1D.
Standard Control Voltages
| [V] | 24 | 48 | 115 | 120 | 240 | |
| 50 Hz | J | — | — | D | A | |
| 60 Hz | J | — | — | D | A | |
| DC | Z24 | Z48 | Z01 | — | — | |
Labels
- Uniform labeling materials for contactors, motor starting equipment, timing relays and circuit breakers
Specifications
Thermal Overload Relays
Circuit Diagrams
|
|
|
Trip Characteristics
These trip characteristics refer to IEC 60947 and are average values from cold start at an ambient temperature of 20 °C. Trip time is pictured as a function of operating current. With the device at normal operating temperature, the trip time decreases to approximately 25% of the shown value.
|
|
Thermal Overload Relays, Continued
| General | |||||
| Cat. Nos. | 193-TA… | 193-TB… | 193-TC… | 193-TDC90 | |
| Weight | [kg (lbs)] | 0.130 (0.29) | 0.210 (0.46) | 0.210 (0.46) | 1.300 (2.86) |
| Standards | IEC 60947, DIN VDE 0660 | ||||
| Approvals | CE, UL Listed, CSA, PTB, RINA | ||||
| Climatic withstand | humid/warm, constant, per DIN, IEC 68, Part 2-3 humid/warm, cyclic, per DIN, IEC 68, Part 2-30 |
||||
| Ambient temperature | open enclosed |
25…+50°C (13…122°F) | |||
| 25…+40°C (13…104°F) | |||||
| Temperature compensation | continual | ||||
| Shock withstand (Sin impact 10 ms) |
[G] | 10 | |||
| Protection class | IP00 | ||||
| IP2X when attached | |||||
| Contact protection | Finger- and back of hand proof (VDE 0106, Part 100) | ||||
Approximate Dimensions
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Mounted on Bulletin 100-C Contactor
|
| Cat. No. | With Contactor | a | b | b1 | c | c1 | c2 | c5 | ød | d1 | d2 | e1 | e2 |
| 193-TA… | 100-C09…100-C23 | 45 (1-25/32) |
127 (5) |
83 (3-17/64) |
96 (3-25/32) |
91 (3-37/64) |
15 (19/32) |
5 (13/64) |
2 @ 4.5 (2 @ 3/16) |
60 (2-23/64) |
35 (1-25/64)¬ |
16.5 (21/32) |
51 (2) |
| 100-C30…100-C37 | 45 (1-25/32) |
127 (5) |
83 (3-17/64) |
105 (4-9/64) |
99 (3-37/64) |
6.5 (17/64) |
9.5 (3/8) |
2 @ 4.5 (2 @ 3/16) |
60 (2-23/64) |
35 (1-25/64)¬ |
16.5 (21/32) |
51 (2) |
|
| 193-TB… | 100-C30…100-C37 | 60 (2-23/64) |
140 (5-33/64) |
97 (3-13/16) |
105 (4-9/64) |
99 3-37/64) |
6.5 (17/64) |
6.5 (17/64) |
2 @ 4.5 (2 @ 3/16) |
60 (2-23/64) |
35 1-25/64)¬ |
16.5 (21/32) |
57 (2-1/4) |
| 100-C43 | 60 (2-23/64) |
140 (5-33/64) |
97 (3-13/16) |
107 (4-7/32) |
103 (4-3/32) |
6.5 (17/64) |
8.5 (21/64) |
2 @ 4.5 (2 @ 3/16) |
60 (2-23/64) |
45 (1-25/32)¬ |
16.5 (21/32) |
57 (2-1/4) |
|
| 193-TC… | 100-C60…100-C85 | 72 (2-53/64) |
185 (7-9/32) |
120 (4-23/32) |
125 (4-15/16) |
120 (4-23/32) |
8.5 (21/64) |
28.5 (1-1/8) |
4 @ 5.4 (4 @ 7/32) |
100 3-15/16) |
55 (2-11/64)¬ |
16.5 (21/32) |
82 (3-15/64) |
Separately Mounted with DIN/Panel Adapter
|
Separately Mounted
|
| Cat. No. | a | b | b1 | c | c1 | c2 | Æd | d1 | d2 | e1 | e2 |
| 193-TA… | 45 (1-25/32) |
85 (3-11/32) |
44 (1-47/64) |
95 (3-47/64) |
90 (3-35/64) |
5 (13/64) |
2 @ 4.5 (2 @ 3/16) |
60…75 (2-23/64… 2-61/64) |
35 (1-25/64)¬ |
16 (5/8) |
3 (1/8) |
| 193-TC… | 60 (2-23/64) |
90 (3-35/64) |
44 (1-47/64) |
117 (4-49/64) |
112 (4-13/32) |
15 (19/32) |
2 @ 5.4 (2 @ 7/32) |
75 (2-61/64) |
50 (1-31/32)¬ |
16 (5/8) |
0 (0) |
| 193-TDC90 | 100 (3-15/16) |
120 (4-23/32) |
— | 135 (5-5/16) |
— | 5 (13/64) |
4 @ 6.2 (4 @ 1/4) |
74 (2-29/32) |
80 (3-5/32) |
16 (5/8) |
7 (9/32) |
| ¬ Can be mounted on 35 mm DIN Rail EN 50 022-35 | |||||||||||
| T With reset rod, the max. action radius is 9 mm from the center of the reset knob. | |||||||||||
c3 With remote reset: 51 mm (2)
c4 With auxiliary contact block: 39 mm (1-17/32)