Catalogs > Industrial Controls Catalog > Motor Control, IEC > Overload Relays > Bulletin 193-T Bimetallic Overload Relays
Bulletin 193-T Bimetallic Overload Relays
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
Thermal Overload Relays
| For Use With¬ | Setting Range [A]T | Cat. No. |
| 100-C09…100-C37 | 0.1…0.16 | 193-TAA16 |
| 0.16…0.24 | 193-TAA24 | |
| 0.24…0.4 | 193-TAA40 | |
| 0.4…0.6 | 193-TAA60 | |
| 0.6…1.0 | 193-TAB10 | |
| 1.0…1.6 | 193-TAB16 | |
| 1.6…2.4 | 193-TAB24 | |
| 2.4…4 | 193-TAB40 | |
| 4…6 | 193-TAB60 | |
| 6…10 | 193-TAC10 | |
| 100-C12…100-C37 | 10…16 | 193-TAC16 |
| 100-C23…100-C37 | 16…24 | 193-TAC24 |
| 100-C30…100-C43 | 18…30 | 193-TBC30 |
| 100-C37…100-C43 | 30…45 | 193-TBC45 |
| 100-C60…100-C85 | 18…30 | 193-TCC30 |
| 30…45 | 193-TCC45 | |
| 45…60 | 193-TCC60 | |
| 100-C72…100-C85 | 60…75 | 193-TCC75 |
| Separate Mounting Required | 70…90 | 193-TDC90 |
| ¬ Bulletin 193-T overload relays should not be direct mounted with DC coil contactors. | ||
| T To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58. | ||
| For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current. | ||