Overload Relays

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Overload Relays > Bulletin 193-EC E3 and E3 Plus Solid-State Overload Relays

Bulletin 193-EC E3 and E3 Plus Solid-State Overload Relays

Introduction Standards Compliance and Certifications Product Overview Catalog Number Explanation
Product Selection Accessories Specifications Approximate Dimensions
Product Selection

Bulletin 193-EC1 Electronic Motor Protection Relays – Direct Contactor Mount


Mounts to Contactor Adjustment Range [A] Cat. No.
100-C09…100-C23 0.4…2 193-EC1PB
1…5 193-EC1AB
3…15 193-EC1BB
5…25 193-EC1CB
100-C30…100-C43 1…5 193-EC1AD
3…15 193-EC1BD
5…25 193-EC1CD
9…45 193-EC1DD
100-C60…100-C85 9…45 193-EC1DE
18…90 193-EC1EE
100-D95…100-D180 28…140 T  193-EC1FF
42…210 T  193-EC1GF
100-D210…100-D420 42…210 T  193-EC1GG
60…302 T  193-EC1HG
84…420 T  193-EC1JG
100-D630…100-D860 125…630 T  193-EC1KH
172…860 T  193-EC1LH
  
Package Quantity = 1
Discount Group MPC
T Does not include terminal lugs. See Accessories, Add-on Accessories.
T Does not include terminal lugs.

Bulletin 193-EC2 Electronic Motor Protection Relay – Direct Contactor Mount


Mounts to Contactor Adjustment Range [A] Cat. No.
100-C09…100-C23 0.4…2 193-EC2PB
1…5 193-EC2AB
3…15 193-EC2BB
5…25 193-EC2CB
100-C30…100-C43 1…5 193-EC2AD
3…15 193-EC2BD
5…25 193-EC2CD
9…45 193-EC2DD
100-C60…100-C85 9…45 193-EC2DE
18…90 193-EC2EE
  

Bulletin 193-EC3 Electronic Motor Protection Relay – Direct Contactor Mount


Mounts to Contactor Adjustment Range [A] Cat. No.
100-C09…100-C23 0.4…2.0 193-EC3PB
1…5 193-EC3AB
3…15 193-EC3BB
5…25 193-EC3CB
100-C30…100-C43 1…5 193-EC3AD
3…15 193-EC3BD
5…25 193-EC3CD
9…45 193-EC3DD
100-C60…100-C85 9…45 193-EC3DE
18…90 193-EC3EE
100-D95…100-D180 28…140 T  193-EC3FF
42…210 T  193-EC3GF
100-D210…100-D420 42…210 T  193-EC3GG
60…302 T  193-EC3HG
84…420 T  193-EC3JG
100-D630…100-D860 125…630 T  193-EC3KH
172…860 T  193-EC3LH
  
T Does not include terminal lugs. See Accessories, Add-on Accessories.
T Does not include terminal lugs.

Bulletin 193-EC4 Current Monitor Relay –
Direct Contactor Mount



Mounts to Contactor Adjustment Range [A] Cat. No.
100-C09…100-C23 0.4…2.0 193-EC4PB
1…5 193-EC4AB
3…15 193-EC4BB
5…25 193-EC4CB
100-C30…100-C43 9…45 193-EC4DD
100-C60…100-C85 18…90 193-EC4EE
  
T Does not include terminal lugs. See Accessories, Add-on Accessories.
T Does not include terminal lugs.

Panel Mount Devices for use with External Current Transformers§ 

Description Adjustment Range [A] Cat. No.
  • 2 Inputs

  • 1 Output
  • 9…5000 193-EC1ZZ
  • 4 Inputs

  • 2 Outputs

  • Ground Fault Sensor Input

  • PTC Thermistor Input

  • DeviceLogix
  • 9…5000 193-EC3ZZ
    193-EC4ZZ
      
    § Current transformers supplied by customer. Refer to Bulletin 1411 Current Transformers and the CT Ratio to FLA chart below for proper current transformer selection.

    CT Ratio to FLA Setting Range Correlation

    CT Ratio FLA Setting
    Range (A)
    CT Ratio FLA Setting
    Range (A)
    CT Ratio FLA Setting
    Range (A)
    50:5 9…45 300:5 60…302 1200:5 240…1215
    100:5 18…90 500:5 84…420 2500:5 450…2250
    150:5 28…140 600:5 125…630 5000:5 1000…5000
    200:5 42…210 800:5 172…860