Bulletin 193-EA/-EB/-ES - E1 and E2 Solid-State Overload Relays
|
|
Bulletin 193-EA/-EB/-ES — E1 and E2 Solid-State Overload Relays
193-EA/-ES
- Self-Powered
- Phase Loss Protection
- Wide Adjustment Range (3.2:1)
- 1 N.O. and 1 N.C. Isolated Auxiliary Contact
- Choice of Tripping Classes — Class 10 or 20
- Compact Size
- Low Energy Consumption (150 mW)
- Ambient Temperature Compensation
193-EB also includes:
- Selectable Trip Class 10, 15 or 20
- Ground Fault Tripping
- Jam/Stall Protection
The Bulletin 193-EA/EB/ES is a self-powered, solid-state overload relay that provides advanced motor protection when compared to traditional bimetallic overload relays. It provides improved protection against the damage caused to motors under phase loss conditions. It also offers, as standard, a manually operated trip function, visible trip indicator, and isolated N.O. alarm contacts.
Your order must include 1) the Cat. No. of overload relay selected and 2) if required, Cat. No. of any accessories.
Standards Compliance and Certifications
Standards Compliance
EN 60947-4-1
CSA C22.2 No. 14
UL 508
Certifications
CE
CSA Certified
UL Listed
CCC (193-EA only)
Product Selection
Bulletin 193-EA/193-ES Electronic Motor Protection Relays
| For Use With | Adjustment Range (A) | Trip Class 10 | Trip Class 20 | Trip Class 10 | Trip Class 20 |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||
| Manual Reset for 3Æ Applications | Automatic/Manual Reset for 3Æ Applications | ||||
| 100-M05…100-C23 | 0.1…0.32 | 193-EA1AB | 193-EA2AB | 193-EA4AB | 193-EA5AB |
| 0.32…1.0 | 193-EA1CB | 193-EA2CB | 193-EA4CB | 193-EA5CB | |
| 1.0…2.9 | 193-EA1DB | 193-EA2DB | 193-EA4DB | 193-EA5DB | |
| 1.6…5.0 | 193-EA1EB | 193-EA2EB | 193-EA4EB | 193-EA5EB | |
| 3.7…12 | 193-EA1FB | 193-EA2FB | 193-EA4FB | 193-EA5FB | |
| 100-C09…100-C23 | 12…32 | 193-EA1GB | 193-EA2GB | 193-EA4GB | 193-EA5GB |
| 100-C30…100-C37 | 3.7…12 | 193-EA1FC | 193-EA2FC | 193-EA4FC | 193-EA5FC |
| 12…37 | 193-EA1HC | 193-EA2HC | 193-EA4HC | 193-EA5HC | |
| 100-C43 | 14…45 | 193-EA1JD | 193-EA2JD | 193-EA4JD | 193-EA5JD |
| 100-C60…100-C85 | 26…85 | 193-EA1KE | 193-EA2KE | 193-EA4KE | 193-EA5KE |
| Manual Reset for 1Æ Applications | Automatic/Manual Reset for 1Æ Applications | ||||
| 100-M05…100-C23 | 2.0…7.0 | 193-ES1AB | 193-ES2AB | 193-ES4AB | 193-ES5AB |
| 5.0…15 | 193-ES1BB | 193-ES2BB | 193-ES4BB | 193-ES5BB | |
| 100-C09…100-C23 | 12…32 | 193-ES1CB | 193-ES2CB | 193-ES4CB | 193-ES5CB |
| 100-C30…100-C37 | 12…37 | 193-ES1DC | 193-ES2DC | 193-ES4DC | 193-ES5DC |
| 100-C43 | 14…45 | 193-ES1FD | 193-ES2FD | 193-ES4FD | 193-ES5FD |
| 100-C60…100-C85 | 26…85 | 193-ES1HE | 193-ES2HE | 193-ES4HE | 193-ES5HE |
Bulletin 193-EB Electronic Motor Protection Relays
Automatic/Manual Reset, Adjustable Trip Class 10, 15 or 20, Jam/Stall and Ground Fault Tripping.¬
| For Use With | Adjustment Range (A) | Cat. No. |
| 100-C09…100-C23 | 0.1…0.32 | 193-EB1AB |
| 0.32…1.0 | 193-EB1CB | |
| 1.0…2.9 | 193-EB1DB | |
| 1.6…5.0 | 193-EB1EB | |
| 3.7…12 | 193-EB1FB | |
| 12…32 | 193-EB1GB | |
| 100-C30…100-C37 | 14…45 | 193-EB1JC |
| 100-C43 | 5.0…15 | 193-EB1SD |
| 14…45 | 193-EB1JD | |
| 100-C60…100-C85 | 23…75 | 193-EB1ME |
| 60…85 | 193-EB1NE | |
| ¬ Ground Fault Tripping and Jam/Stall are inhibited for approximately 30 seconds to eliminate the possibility of nuisance tripping during motor starting. | ||
Accessories
Add-On Accessories
| Description | For Use With | Pkg. Qty. | Cat. No. | ||
|
DIN Rail/Panel Adapter For separate mounting of the electronic motor protection relay Can be mounted to top-hat rail EN 50 022-35 |
193-EA_ _ B, ES__B, -EA__C, -ES__C | 1 | 193-EPM1 | |
| 193-EB__B, -EB__C, -E__D |
193-EPM2 | ||||
| 193-E__E | 193-EPM3 | ||||
|
Anti-Tamper Shield | SMP-1 SMP-2 193-E all |
1 | 193-BC4 | |
|
Current Adjustment Shield | SMP-1 SMP-2 |
1 | 193-BC5 | |
|
Anti-Tamper Shield for DIP Switches | 193-EB_ _ B, 193-EB_ _ C, 193-EB_ _D | 40 | 193-BC7 | |
|
Anti-Tamper Shield for DIP Switches | 193-EB_ _ E | 40 | 193-BC6 | |
|
Remote Reset Solenoid for remote reset of electronic overload | 193-T all, 150-C | 1 | 193-ER1Ä | |
|
|
External Reset Button for Enclosed Devices | 193-E all | 1 | 800ES-R611WTR08 |
|
|
Labelling Material Uniform labelling material for contactors, motor protection devices, timing relays and circuit breakers. |
See Marking Systems (For 100-C09…C97 contactors) | |||
Ä Voltage Suffix Code
| Voltage | 24V | 48V | 110V | 115V | 120V | 220V | 240V |
| 50 Hz | J | — | D | — | — | A | — |
| 60 Hz | J | — | — | — | D | — | A |
| DC | Z24 | Z48 | — | Z01 | — | — | — |
Specifications
Main Circuits
Control Circuits
General
| Cat. No. | 193-E_ _ _B | 193-E_ _ _C | 193-E_ _ _D | 193-E_ _ _E | ||
| Weight | [kg (lb)] | 0.14 (0.31) | 0.17 (0.37) | 0.21 (0.46) | 0.36 (0.84) | |
| Standards | EN 60947, DIN VDE 0660, CSA22.2 No. 14, UL 508 | |||||
| Approvals | CCC, CE, UL, CSA | |||||
| Corrosion Resistance | 95% relative humidity, without condensation, 30…60°C | |||||
| Ambient Temperature | open enclosed |
20…+60 °C (4…122 °F) 20…+40 °C (4…104 °F) |
||||
| Temperature Compensation | Continuous | |||||
| Shock Resistance (10 ms sinusodial shock) |
[G] | 30 | ||||
| Type of Protection (in connected state) |
IP20 | |||||
Trip Curves for 1Æ Applications (Bulletin 193-ES)
|
Trip Curves for 3Æ Applications (Bulletin 193-EA/EB)
|
Wiring Schematic
|
|
|
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Mounts to Bulletin 100-C Contactor
|
| Contactor Cat. No. | a Width | b Height | b1 | c Depth | e1 | e2 | d1 | d2 | h | j | Æd |
| 100-M05 with 193-EA or -ES | 45 (1-25/32) |
107 (4-13/64) |
77.4 (3-3/64) |
67.2 (2-41/64) |
18.2 (23/32) |
48.5 (1-29/32) |
50 (1-61/64) |
— | 48.3 (1-29/32) |
2 (5/64) | Two Æ 4.2 (Two 11/64 Æ) |
| 100-C09, -C12 -C16, -C23 with 193-EA or -ES | 45 (1-25/32) |
131 (5-11/64) |
87.8 (3-29/64) |
88.5 (3-1/2) |
18.2 (23/32) |
59 (2-21/64) |
60 (2-23/64) |
35 (1-3/8) |
85.1 (3-23/64) |
2 (5/64) | Two Æ 4.2 (Two 11/64 Æ) |
| 100-C09, -C12 -C16, -C23 with 193-EB | 54 (2-1/8) |
136.5 (5-3/8) |
93.4 (3-43/64) |
90.7 (3-37/64) |
22.6 (57-64) |
59 (2-21/64) |
60 (2-23/64) |
35 (1-3/8) |
85.1 (3-23/64) |
2 (5/64) | Two Æ 4.2 (Two 11/64 Æ) |
| 100-C30, -C37 with 193-EA or -ES | 45 (1-25/32) |
136.5 (5-3/8) |
93.4 (3-43/64) |
92.1 (3-5/8) |
18.2 (23/32) |
59 (2-21/64) |
60 (2-23/64) |
35 (1-3/8) |
104.7 (4-1/8) |
2 (5/64) | Two Æ 4.2 (Two 11/64 Æ) |
| 100-C30, -C37 with 193-EB | 54 (2-1/8) |
136.5 (5-3/8) |
93.4 (3-43/64) |
92.1 (3-5/8) |
22.6 (57/64) |
59 (2-21/64) |
60 (2-23/64) |
35 (1-3/8) |
104.7 (4-1/8) |
2 (5/64) | Two Æ 4.2 (Two 11/64 Æ) |
| 100-C43 with 193-EA, -ES or -EB | 54 (2-1/8) |
136.5 (5-3/8) |
93.4 (3-43/64) |
92.1 (3-5/8) |
22.6 (57/64) |
59 (2-21/64) |
60 (2-23/64) |
45 (1-49/64) |
104.7 (4-1/8) |
2 (5/64) | Two Æ 4.2 (Two 11/64 Æ) |
| 100-C60, -C72, -C85 with 193-EA, -ES or -EB | 72 (2-53/64) |
188.5 (7-27/64) |
125.5 (4-15/16) |
120.4 (4-3/4) |
18.2 (23/32) |
83.5 (3-9/32) |
100 (3-15/16) |
55 (2-11/64) |
123.9 (4-7/8) |
2 (5/64) | Four Æ 5.5 (Four 7/32 Æ) |
Individual Mounting with DIN Rail/Panel Adapter
|
| Cat. No. | A Width | B Height | C Depth | D | E |
| 193-EPM1 | 45 (1-25/32) | 90 (3-35/64) | 75 (2-61/64) | 30 (1-3/16) | 75 (2-61/64) |
| 193-EPM2 | 55 (2-11/64) | 90 (3-35/64) | 96.5 (4-29/32) | 40 (1-37/64) | — |
| 193-EPM3 | 70 (2-49/64) | 120 (4-23/32) | 110 (4-11/32) | 55 (2-11/64) | — |