Catalogs > Industrial Controls Catalog > Motor Control, IEC > Overload Relays > Bulletin 193-EF Solid-State Overload Relays
Bulletin 193-EF Solid-State Overload Relays
| Introduction | Standards Compliance and Certifications | Product Overview | Catalog Number Explanation |
| Product Selection | Accessories | Specifications | Approximate Dimensions |
Test Button for Thermal Overload Protection
Pressing the test button will verify thermal tripping operation time at 6x/e without the motor being connected. The test button must be held for longer than the set trip time t6x/e.
Device Installation and Commissioning
The operating instructions enclosed with the device provide all of the information necessary to set and commission it.
Surface Mounting
193-EF_A Snap-on fixing to standard DIN Rail or screw fixing
193-EF_B Screw fixing
193-EF_C Screw fixing
Mounting position: optional
Setting the Rated Current (0.5…20 A) (193-EF1A and 193-EF2A Requires 193-HD)
The motor supply cables are looped through the current transformer twice, thereby doubling the rated motor current. The setting on the Bulletin 193-EF overload relay is the product of:
Ie [A] x…number of loops
| Rated Voltage Motor Circuit (primary circuit of current measuring device) | |||||
| IEC 947, EN 60947 | [V] | 1000 | |||
| CSA, UL | [V] | 600 | |||
| Control Circuit | |||||
| IEC 947, EN 60947 | [V] | 440 | |||
| CSA, UL | [V] | 240 | |||
| Rated Control Voltage US | |||||
| AC 50/60 Hz | [V] | 24, 36, 48, 110, 120, 230, 240, 400, 415, 440, (0.8…1.1US) | |||
| DC | [V] | 24, 48 (0.9…1.2 US) | |||
| Terminal Cross-section | |||||
| Control circuit | [mm2] | 2 x 2.5 | |||
| Device Protection Fuse | 10 A Type gG or 16 A Type gG | ||||
| Output Relay Contact Information | |||||
| Contact assembly | 1 N.O. and 1 N.C., galvanically separated | ||||
| Rated operating voltage per UL/CSA: pilot duty 240V | [V] | 24 | 110…125 | 220…250 | 380… 440 |
| Continuous Thermal current | [A] | 4 | |||
| Rated AC operating current AC-15 | [A] |
3 |
3 |
1.2 |
|
| Max. permissible switching current (cos = 0.3) AC-15 |
[A] |
30 |
30 |
12 |
|
| Rated DC operating current (L/R = 300 ms), no protective circuit needed DC-13 |
[A] |
2 |
0.3 |
0.2 |
— |
| Max. rated back-up fuse current | 10 A, 500V AC Type gG | ||||
| Ambient temperature Operation Storage Transport |
-5…+60 °C -50…+60 °C -50…+85 °C |
||||
| Sensor Measurement Circuit | |||
| Measurement circuit Cross section |
[mm2] | 0.5 | 1.5 |
| Max. lead length | [m] | 200 | 600 |
| Max. cold resistance of PTC sensor chain | kW | 1.5 | |
| Max. number of PTC sensors per IEC 34-11-2 | 6 | ||
| Weights | |||
| Overload Relay | |||
| 193-EF1A | [g] | 1 070 | |
| 193-EF2A | [g] | 1 090 | |
| 193-EF1B | [g] | 2 510 | |
| 193-EF2B | [g] | 2 530 | |
| 193-EF2C | [g] | 5 550 | |
| 193-LB1 indication module | [g] | 160 | |
| 193-RB1 Remote reset module | [g] | 160 | |
| 196-MTM Adapter | [g] | 5 | |
| 193-PA Front cover | [g] | 3 | |
| 193-HD Terminal lug | [g] | 40 | |
| Bus bars | |||
| 825-MVM | [g] | 230 | |
| 825-MVM2 | [g] | 290 | |
| 825-MVS | [g] | 280 | |
| 825-MVS2 | [g] | 350 | |
| Approvals | |||
| CE, UL Listed, CSA, Bureau Veritas, Lloyds Register of Shipping, Maritime Register of Shipping, RINA |
|||
| Type of wiring: insulated control leads, screened > 200 m (shield connected with 1T1) | |||