Bulletin 193-K Bimetallic Overload Relays

Click to enlarge - 193-K_4c


Bulletin 193-K — Miniature Bimetallic Overload Relays


Bulletin 193-K bimetallic overload relays are designed for use with Bulletin 100-K contactors and Bulletin 104-K Reversing Contactors. These class 10A ambient temperature-compensated thermal overload relays include a differential mechanism for sensitivity to phase-loss conditions.

Standards Compliance and Certifications

Standards Compliance

IEC/EN 60947-1,-4-1,-5-1
UL 508
CSA 22.2. No. 14


Certifications

CE marked
cULus Listed (File No. E33916, Guide NKCR, NKCR7)


Product Selection/Accessories

Miniature Bimetallic Overload Relays

Mounts to Contactor Setting Range [A] ¬ T  Max. Current Rating of Backup Fuse [A] Cat. No.
IEC Coordination UL Class K5/5 kA, 600V AC
Type 1 Type 2 UL 508
100-K05…100-K12 0.10…0.16 35 1 1 193-KA16
0.16…0.25 35 1 1 193-KA25
0.25…0.40 35 2 1 193-KA40
0.35…0.50 35 2 2 193-KA50
0.45…0.63 35 2 2 193-KA63
0.55…0.80 35 4 3 193-KA80
0.75…1.0 35 4 3 193-KB10
0.9…1.3 35 6 4 193-KB13
1.1…1.6 35 6 5 193-KB16
1.4…2.0 35 10 8 193-KB20
1.8…2.5 35 20 10 193-KB25
2.3…3.2 35 20 12 193-KB32
2.9…4.0 35 20 15 193-KB40
3.5…4.8 35 20 15 193-KB48
4.5…6.3 35 20 20 193-KB63
100-K09…100-K12 5.5…7.5 35 20 25 193-KB75
7.2…10.0 35 20 35 193-KC10
100-K12 9.0…12.5 35 20 50 193-KC12
  
¬ To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58.
T For motors with Service Factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current.

Accessories

  Description Cat. No.
Click to enlarge - 193-T1R_reset solenoid Remote Reset Solenoid
For remote reset of 193-K and 193-T1 overload relays
193-T1RÄ
  Reset Adapter
Expands the reset target area when using an external reset
193-RA3
Click to enlarge - 800F_reset_operator_4c External Reset Button
For enclosed, through-the-door reset applications. Metal construction IP66, non-illuminated with rod (length: 142 mm, adjustable range 141…159 mm).
Refer to the 800F catalog pages for additional types.
Reset Button 800FM-R611
Click to enlarge - 800F_reset_rod_4c Rod 800F-ATR08
  

Ä Coil Voltage Codes for Remote Reset Solenoid

  [V] 24 48 110 120 125 220…240
50 Hz D
60 Hz D
50/60 Hz KJ KY KF
DC ZJ ZY ZD ZS