| For Use With¬
|
Setting Range [A]T
|
Max. Back-up fuse [A]
|
Cat. No.
|
| gL/gG
|
UL Class K5
|
| 50 kA, 690V AC
|
5 kA, 600V AC
|
| IEC/EN 60947-4-1 Coordination
|
UL 508
|
| Type 1
|
Type 2
|
| 100-C09…100-C23
|
0.1…0.16
|
50
|
—
|
1
|
193-T1AA16
|
| 0.16…0.25
|
50
|
—
|
1
|
193-T1AA25
|
| 0.25…0.40
|
50
|
2
|
1
|
193-T1AA40
|
| 0.35…0.50
|
50
|
2
|
2
|
193-T1AA50
|
| 0.45…0.63
|
50
|
2
|
2
|
193-T1AA63
|
| 0.55…0.80
|
50
|
4
|
3
|
193-T1AA80
|
| 0.75…1.0
|
50
|
4
|
3
|
193-T1AB10
|
| 0.90…1.3
|
50
|
6
|
4
|
193-T1AB13
|
| 1.1…1.6
|
50
|
6
|
5
|
193-T1AB16
|
| 1.4…2.0
|
50
|
10
|
8
|
193-T1AB20
|
| 1.8…2.5
|
50
|
16
|
10
|
193-T1AB25
|
| 2.3…3.2
|
50
|
16
|
12
|
193-T1AB32
|
| 2.9…4.0
|
50
|
16
|
15
|
193-T1AB40
|
| 3.5…4.8
|
50
|
16
|
15
|
193-T1AB48
|
| 4.5…6.3
|
50
|
20
|
20
|
193-T1AB63
|
| 5.5…7.5
|
50
|
25
|
25
|
193-T1AB75
|
| 7.2…10
|
50
|
25
|
35
|
193-T1AC10
|
| 9.0…12.5
|
50
|
35
|
50
|
193-T1AC12
|
| 100-C12…100-C23
|
11.3…16
|
50
|
35
|
60
|
193-T1AC16
|
| 100-C16…100-C23
|
15…20
|
80
|
40
|
80
|
193-T1AC20
|
| 17.5…21.5
|
80
|
50
|
80
|
193-T1AC21
|
| 100-C23
|
21…25
|
80
|
50
|
100
|
193-T1AC25
|
| 100-C30…100-C37
|
15…20
|
80
|
40
|
80
|
193-T1BC20
|
| 17.5…21.5
|
80
|
50
|
80
|
193-T1BC21
|
| 21…25
|
80
|
50
|
100
|
193-T1BC25
|
| 24.5…30
|
100
|
63
|
100
|
193-T1BC30
|
| 29…36
|
125
|
63
|
125
|
193-T1BC36
|
| 100-C37
|
33…38
|
125
|
63
|
150
|
193-T1BC38
|
| 100-C43
|
17…25
|
100
|
50
|
100
|
193-T1CC25
|
| 24.5…36
|
125
|
80
|
125
|
193-T1CC36
|
| 35…47
|
160
|
100
|
175
|
193-T1CC47
|
| 100-C60…100-C85
|
35…47
|
160
|
100
|
175
|
193-T1DC47
|
| 45…60
|
200
|
125
|
250§
|
193-T1DC60
|
| 100-C72…100-C85
|
58…75
|
200
|
125
|
300§
|
193-T1DC75
|
| 100-C85
|
72…90
|
250
|
160
|
350§
|
193-T1DC90
|
| Separate mounting required (Panel-mounted device)
|
35…47
|
160
|
100
|
175
|
193-T1DC47P
|
| 45…60
|
200
|
125
|
250§
|
193-T1DC60P
|
| 58…75
|
200
|
125
|
300§
|
193-T1DC75P
|
| 72…90
|
250
|
160
|
350§
|
193-T1DC90P
|
|
|
| ¬ Bulletin 193-T1 overload relays shall not be used with 100-C09…100-C43 conventional DC coil-controlled contactors. Use electronic controlled DC coil versions.
|
| T To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58.
|
| For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current.
|
| § Max. Back-up fuse [A], UL Class K5, 10 kA, 600V AC
|
| § Only in combination with 100-C contactors.
|
|
|
Description
|
For Use With
|
Pkg. Quantity ¬
|
Cat. No.
|
|
DIN Rail/Panel Mounting Adapter For separate mounting of overload relays Snaps on to 35 mm top hat rail
|
193-T1AA, 193-T1AB, 193-T1AC, 193-T1BC
|
1
|
193-T1APM
|
|
Screw Adapter For screw fixing of the 193-T1APM panel adapter (1 required per adapter)
|
193-T1APM
|
10
|
140M-C-N45
|
|
Remote Reset Solenoid For remote reset of 193-K and 193-T1 overload relays
|
193-K, 193-T1 (not for 193-T1DC_P)
|
1
|
193-T1RÄ
|
|
External Reset Button For enclosed, through-the-door reset applications. Metal construction, IP66, non-illuminated. Refer to the 800F selection information for additional types.
|
All
|
1
|
800FM-R611
|
|
Reset Rod Length 142 mm, adjustable range 141…159 mm
|
All
|
1
|
800F-ATR08
|
|
Reset Adapter Expands the reset target area when using an external reset
|
193-K, 193-T1 (not for 193-T1DC_P)
|
1
|
193-RA3
|
|
|
| ¬ Must be ordered in multiples of package quantity.
|
|
|
Description
|
Pkg. Quantity¬
|
Cat. No.
|
|
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm
|
10
|
100-FMS
|
|
Marking Tag Sheet 160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
|
10
|
100-FMP
|
Transparent Cover To be used with marking tag sheets
|
100
|
100-FMC
|
|
|
| ¬ Must be ordered in multiples of package quantities.
|
| Main Circuits
|
| Cat. No.
|
193-T1…
|
| Rated isolation voltage Ui
|
690V AC
|
| Rated impulse withstand voltage Uimp (between main poles and between main poles and auxiliary circuits)
|
6kV AC
|
| Rated impulse withstand voltage Uimp (between auxiliary circuits)
|
4kV AC
|
| Rated operating voltage Ue
|
IEC
|
690V AC
|
| 440V DC
|
| UL, CSA
|
600V AC
|
Rated frequencies
|
[Hz]
|
50/60
|
| Operational frequencies
|
DC…400 Hz
|
| Power dissipation
|
193-T1A, 193-T1B
|
up to 0.4 A
|
7 W
|
| 0.5…36 A
|
6 W
|
| 38 A
|
12 W
|
| 193-T1C
|
25…47 A
|
12 W
|
| 193-T1D
|
47…90 A
|
18 W
|
|
|
| Control Circuits
|
| Cat. No.
|
193-T1…
|
| Rated operating current Ie
|
| AC-15
|
24V
|
[A]
|
4
|
| 240V
|
[A]
|
2
|
| 400V
|
[A]
|
1.6
|
| 690V
|
[A]
|
0.15
|
| DC-13
|
24V
|
[A]
|
2
|
| 110V
|
[A]
|
0.4
|
| 220V
|
[A]
|
0.25
|
| 440V
|
[A]
|
0.08
|
| Thermal Current Ith
|
5
|
| Short-circuit withstand, Fuse
|
IEC, gL/gG
|
[A]
|
6
|
| Short-circuit withstand, circuit breaker £ 1 kA prospective short-circuit-current
|
[A]
|
4
|
| Min. contact load for reliable operation
|
15V, 2 mA
|
| UL Rating
|
A600/Q300
|
|
|
| Terminations
|
| Cat. Nos.
|
Main Circuits
|
Control Circuits
|
Remote Reset
|
| 193-T1A…
|
193-T1BC20… T1BC25
|
193-T1BC30… T1BC38
|
193-T1C…
|
193-T1D…
|
193-T1APM
|
193-T1… all
|
193-T1R…
|
Wiring cross section Terminal type
|
|
|
|
|
| Terminal screws
|
M4
|
M4
|
M4
|
M5
|
M6
|
M4
|
M3.5
|
M3.5
|
|
Fine stranded with ferrule
|
1 conductor [mm2] 2 conductors [mm2]
|
1.5…4 1.5…4
|
1.5…4 1.5…4
|
2.5…10 -
|
2.5…16 -
|
10…35 -
|
1.5…10 -
|
1…4 1…4
|
1…2.5 -
|
|
Solid or coarse stranded
|
1 conductor [mm2] 2 conductors [mm2]
|
1.5…6 1.5…6
|
1.5…6 1.5…6
|
2.5…16 -
|
2.5…25 -
|
10…35 -
|
1.5…16 -
|
1…4 1…4
|
1…2.5 -
|
|
1 conductor [AWG] 2 conductors [AWG]
|
No. 16…10 No. 16…10
|
No. 14…10 No. 14…10
|
No. 10…6 -
|
No. 10…6 -
|
No. 8…1 -
|
No. 16…6 -
|
No. 18…12 No. 18…12
|
No. 16…12 -
|
| Recommended torque
|
[Nm]
|
1.5 ... 2.2
|
1.5 ... 2.2
|
2.5 … 3.5
|
2.5 … 3.5
|
4.5 … 6
|
1.8…2.8
|
1.2
|
1.2
|
| [lb-in]
|
13 … 20
|
13 … 20
|
22 … 31
|
22 … 31
|
40 … 53
|
16…25
|
10.6
|
10.6
|
| Pozidrive screwdriver No.
|
Size
|
2
|
2
|
2
|
2
|
-
|
2
|
2
|
2
|
| Slotted screwdriver
|
[mm]
|
0.8 x 5.5
|
0.8 x 5.5
|
0.8 x 5.5
|
0.8 x 5.5
|
-
|
0.8 x 5.5
|
0.8 x 5.5
|
0.8 x 5.5
|
| Hexagon socket screw
|
Size
|
-
|
-
|
-
|
-
|
4
|
-
|
-
|
-
|
|
|
| 193-T1R Remote Reset
|
| Operating Limits
|
| Maximum Command Impulse
|
5s
|
| AC 50/60 Hz
|
Pick-up [x Us]
|
0.8….1.1
|
| Drop-out [x Us]
|
|
| DC
|
Pick-up [x Us]
|
0.7….1.25
|
| Drop-out [x Us]
|
|
| Coil Consumtion
|
| AC 50/60 Hz
|
Pick-up [VA/W]
|
|
| Hold-in [VA/W]
|
|
| DC
|
Pick-up [W]
|
17 (24, 110, 125V) 25 (48V)
|
| Hold-in [W]
|
17 (24, 110, 125V) 25 (48V)
|
|
|
| General
|
| Cat. No.
|
193-T1…
|
| Type of Overload Relay
|
Bimetallic, Ambient Compensated, Phase Loss Sensitive
|
| Trip Rating (ultimate tripping current)
|
120% FLA
|
| Phase loss sensitivity: Trip rating at phase loss
|
115% FLA
|
| Trip Class
|
193-T1A/-T1B
|
193-T1C/-T1D
|
|
|
IEC/EN 60947-4-1
|
10A
|
10
|
| UL
|
10
|
| Reset Mode
|
Automatic or Manual
|
| Test release
|
Manual release of auxiliary contacts
|
| Trip indication
|
By means of a flag visible through an opening in the relay front
|
| Compensation temperature range
|
-20…+60 °C (-4…+140 °F)
|
| Climatic Conditions
|
Release Tolerance at -20 °C
|
1.05…1.4 x In
|
| Storage Temperature Range
|
-55…+80 °C (-67…+176 °F)
|
| Operating Temperature Range
|
-20…+60 °C (-4…+140 °F)
|
| Air moisture (Storage/Operating)
|
5…95% rel.humidity, non-condensing
|
| Vibration
|
(per IEC/EN 60068-2-6), service
|
3g
|
| IEC/EN 61373 (vibration railways)
|
category 1, class B
|
| IEC/EN 60092-504 (vibration ships), service
|
0.7 g, all axes, 2…200 Hz
|
| Shock
|
(per IEC/EN 68000-2-27), transport
|
30 g
|
| IEC/EN 60068-2-27 (Shock half-sinus), service
|
11 ms > 5 g all axes
|
| IEC/EN 61373 (shock railways)
|
category 1, class B, 5g 30 ms
|
| Max. Altitude
|
2000 m
|
| Pollution Degree
|
3
|
| Degree of Protection, with wires connected
|
IP2X
|
| Approximate Weight (unpackaged)
|
193-T1A, 193-T1B
|
0.16…25 A
|
0.115 kg
|
| 193-T1B
|
30…38 A
|
0.155 kg
|
| 193-T1C
|
25…47 A
|
0.330 kg
|
| 193-T1D
|
47…90 A
|
0.360 kg
|
| 193-T1….P
|
47…90 A
|
0.415 kg
|
| Standards
|
IEC/EN 60497-1, -4-1, -5-1, UL508, CSA C22.2 No.14
|
| Certifications
|
CE, cULus
|
|
|