| For Use With¬
|
Setting Range [A]T
|
Max. Back-up fuse [A]
|
Cat. No.
|
| gL/gG
|
UL Class K5
|
| 50 kA, 690V AC
|
5 kA, 600V AC
|
| IEC/EN 60947-4-1 Coordination
|
UL 508
|
| Type 1
|
Type 2
|
| 100-C09…100-C23
|
0.1…0.16
|
50
|
—
|
1
|
193-T1AA16
|
| 0.16…0.25
|
50
|
—
|
1
|
193-T1AA25
|
| 0.25…0.40
|
50
|
2
|
1
|
193-T1AA40
|
| 0.35…0.50
|
50
|
2
|
2
|
193-T1AA50
|
| 0.45…0.63
|
50
|
2
|
2
|
193-T1AA63
|
| 0.55…0.80
|
50
|
4
|
3
|
193-T1AA80
|
| 0.75…1.0
|
50
|
4
|
3
|
193-T1AB10
|
| 0.90…1.3
|
50
|
6
|
4
|
193-T1AB13
|
| 1.1…1.6
|
50
|
6
|
5
|
193-T1AB16
|
| 1.4…2.0
|
50
|
10
|
8
|
193-T1AB20
|
| 1.8…2.5
|
50
|
16
|
10
|
193-T1AB25
|
| 2.3…3.2
|
50
|
16
|
12
|
193-T1AB32
|
| 2.9…4.0
|
50
|
16
|
15
|
193-T1AB40
|
| 3.5…4.8
|
50
|
16
|
15
|
193-T1AB48
|
| 4.5…6.3
|
50
|
20
|
20
|
193-T1AB63
|
| 5.5…7.5
|
50
|
25
|
25
|
193-T1AB75
|
| 7.2…10
|
50
|
25
|
35
|
193-T1AC10
|
| 9.0…12.5
|
50
|
35
|
50
|
193-T1AC12
|
| 100-C12…100-C23
|
11.3…16
|
50
|
35
|
60
|
193-T1AC16
|
| 100-C16…100-C23
|
15…20
|
80
|
40
|
80
|
193-T1AC20
|
| 17.5…21.5
|
80
|
50
|
80
|
193-T1AC21
|
| 100-C23
|
21…25
|
80
|
50
|
100
|
193-T1AC25
|
| 100-C30…100-C37
|
15…20
|
80
|
40
|
80
|
193-T1BC20
|
| 17.5…21.5
|
80
|
50
|
80
|
193-T1BC21
|
| 21…25
|
80
|
50
|
100
|
193-T1BC25
|
| 24.5…30
|
100
|
63
|
100
|
193-T1BC30
|
| 29…36
|
125
|
63
|
125
|
193-T1BC36
|
| 100-C37
|
33…38
|
125
|
63
|
150
|
193-T1BC38
|
| 100-C43
|
17…25
|
100
|
50
|
100
|
193-T1CC25
|
| 24.5…36
|
125
|
80
|
125
|
193-T1CC36
|
| 35…47
|
160
|
100
|
175
|
193-T1CC47
|
| 100-C60…100-C85
|
35…47
|
160
|
100
|
175
|
193-T1DC47
|
| 45…60
|
200
|
125
|
250§
|
193-T1DC60
|
| 100-C72…100-C85
|
58…75
|
200
|
125
|
300§
|
193-T1DC75
|
| 100-C85
|
72…90
|
250
|
160
|
350§
|
193-T1DC90
|
| Separate mounting required (Panel-mounted device)
|
35…47
|
160
|
100
|
175
|
193-T1DC47P
|
| 45…60
|
200
|
125
|
250§
|
193-T1DC60P
|
| 58…75
|
200
|
125
|
300§
|
193-T1DC75P
|
| 72…90
|
250
|
160
|
350§
|
193-T1DC90P
|
|
|
| ¬ Bulletin 193-T1 overload relays shall not be used with 100-C09…100-C43 conventional DC coil-controlled contactors. Use electronic controlled DC coil versions.
|
| T To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58.
|
| For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current.
|
| § Max. Back-up fuse [A], UL Class K5, 10 kA, 600V AC
|
| § Only in combination with 100-C contactors.
|