Bulletin 140M Motor Circuit Protectors
|
|
|
|
Bulletin 140M Motor Circuit Protectors
- Current range 0.16…1200 A
- UL Listed/Recognized for motor loads
- Short-circuit protection
- Overload protection must be provided separately
- Short-circuit protection
- Visible trip indication
- High current limiting
- High switching capacity
Your order must include: cat. no. of the Motor Circuit Protector selected and, if required, cat. no. of any accessories.
The Bulletin 140M Motor Circuit Protectors provide short circuit protection for individual motor loads. Factory-installed internal accessories make installation and wiring easy.
General Information
Motor Circuit Protectors may provide the following protective and control functions.
In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller.
140M-C, D and F Frames:
The 140M-C, D and F frame Motor Circuit Protectors have one UL/CSA Listing as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on for the specific ratings of each Motor Circuit Protector.
The 140M-C, D and F Frame Motor Circuit Protectors are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 103T and 107T Self-Protected IEC Combination Starters. These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices.
140M-H, J and L Frames:
The 140M-H, J and L frame Motor Circuit Protectors are UL/CSA Recognized as Circuit Breakers as shown in the table on . They are UL/CSA Recognized, rather than UL/CSA Listed, since they only provide short circuit protection and not thermal overload protection for the motor.
140M-H, J and L frame Motor Circuit Protectors (MCPs) are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 113 IEC Combination Starters. These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices.
Standards Compliance and Certifications
Standards Compliance
IEC/EN 60947-1, 2, -4-1, -5-1
IEC/EN 60204-1
CSA, C22.2 No.14
UL 508
UL 489
Certifications (0.16…45 A)
cULus Listed (File No. E54612, Guide No. NLRV, NLRV7)
CCC
CE Marked
Certifications (3…1200 A)
UR Recognized component (File No. E224135, Guide DKPU2)
CSA Certified (Cleass No. 3211-07)
Cat. No. Explanation
| 140M | | C | | 2 | | N | | A63 | | KN | | CC | | GJ |
| a | b | c | d | e | f | g | h |
Wiring Diagrams
|
3-Phase Power Supply
|
Product Selection
Motor Circuit Protectors
- Short-circuit protection — standard magnetic trip (fixed at 13 x Ie)
- Overload protection — none (magnetic trip only)
- For Trip Class 10 motor applications
|
|
|
| Cat. No. 140M-C | Cat. No. 140M-D | Cat. No. 140M-F |
| Rated Operational Current [A] (Ie) | Magnetic Trip Current [A] | Ultimate Interrupting Current [kA], (Icm) | Max. 3-phase Hp Ratings¹ | 3-phase kW Ratings¬ | Cat. No. | |||||||
| 400V | 480V | 200V | 230V | 460V | 575V | 230V | 400/415V | 500V | 690V | |||
| C-Frame | ||||||||||||
| 0.16 | 2.1 | 100 | 65 | — | — | — | — | — | 0.02 | — | — | 140M-C2N-A16 |
| 0.25 | 3.3 | 100 | 65 | — | — | — | — | — | 0.06 | — | — | 140M-C2N-A25 |
| 0.4 | 5.2 | 100 | 65 | — | — | — | — | — | 0.09 | — | — | 140M-C2N-A40 |
| 0.63 | 8.2 | 100 | 65 | — | — | — | — | 0.09 | 0.18 | 0.18 | 0.25 | 140M-C2N-A63 |
| 1 | 13 | 100 | 65 | — | — | 0.5 | 0.75 | 0.12 | 0.25 | 0.37 | 0.55 | 140M-C2N-B10 |
| 1.6 | 21 | 100 | 65 | — | — | 1 | 1 | 0.25 | 0.55 | 0.75 | 1.1 | 140M-C2N-B16 |
| 2.5 | 33 | 100 | 65 | 0.5 | 0.75 | 1.5 | 2 | 0.37 | 0.75 | 1.1 | 1.8 | 140M-C2N-B25 |
| D-Frame | ||||||||||||
| 2.5 | 33 | 100 | 65 | 0.5 | 0.75 | 1.5 | 2 | 0.37 | 0.75 | 1.1 | 1.8 | 140M-D8N-B25 |
| 4 | 52 | 100 | 65 | 1 | 1 | 3 | 3 | 0.75 | 1.5 | 2.2 | 3 | 140M-D8N-B40 |
| 6.3 | 82 | 100 | 65 | 1.5 | 2 | 5 | 5 | 1.5 | 2.2 | 3 | 4 | 140M-D8N-B63 |
| 10 | 130 | 100 | 65 | 3 | 3 | 7.5 | 10 | 2.2 | 4 | 6.3 | 7.5 | 140M-D8N-C10 |
| 16 | 208 | 100 | 65 | 5 | 5 | 10 | 15 | 4 | 7.5 | 10 | 13 | 140M-D8N-C16 |
| 25 | 325 | 50 | 65 | 7.5 | 7.5 | 15 | 20 | — | 11 | 15 | 22 | 140M-D8N-C25 |
| F-Frame | ||||||||||||
| 25 | 325 | 65 | 65 | 7.5 | 10 | 20 | 25 | 6.3 | 11 | 15 | 22 | 140M-F8N-C25 |
| 32 | 416 | 65 | 65 | 7.5 | 10 | 25 | 30 | 7.5 | 15 | 20 | 25 | 140M-F8N-C32 |
| 45 | 585 | 65 | 65 | 10 | 15 | 30 | 40 | 13 | 22 | 30 | 40 | 140M-F8N-C45 |
| ¬ Horsepower/kW ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load current and, in North America, service factor. | ||||||||||||
| For heavy-duty starting applications (exceeding Trip Class 10), please consult your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||||||||||
Motor Circuit Protectors
- Short-Circuit Protection — Magnetic Trip (Adjustable at 3...10 x Ie)
- Overload Protection — None (Magnetic Trip Only)
|
|
|
| Cat. No. 140M-H | Cat. No. 140M-J | Cat. No. 140M-L |
| Rated Operational Current [A] (Ie) | Magnetic Trip Current [A] | 3-phase Hp Ratings¬ | 3-phase kW Ratings¬ | Cat. No.T | ||||||||||||||
| Cam Setting | ||||||||||||||||||
| A | B | C | D | E | F | G | H | I | 200V | 230V | 460V | 575V | 230V | 400/ 415V |
500V | 690V | ||
| H-Frame | ||||||||||||||||||
| 3 | 9 | 15 | 21 | 27 | 30 | 33 | — | — | — | 0.5 | 0.5 | 1.5 | 2 | 0.6 | 0.75 | 1.1 | 1.5 | 140M-H8P-B30 |
| 7 | 21 | 35 | 49 | 63 | 70 | 77 | — | — | — | 1.5 | 2 | 3 | 5 | 1.1 | 2.2 | 3 | 4 | 140M-H8P-B70 |
| 15 | 45 | 75 | 100 | 135 | 150 | 165 | — | — | — | 3 | 3 | 10 | 10 | 3 | 5.5 | 7.5 | 11 | 140M-H8P-C15 |
| 30 | 90 | 150 | 210 | 270 | 300 | 330 | — | — | — | 7.5 | 10 | 20 | 25 | 5.5 | 11 | 15 | 22 | 140M-H8P-C30 |
| 50 | 150 | 250 | 350 | 450 | 500 | 550 | — | — | — | 15 | 15 | 30 | 40 | 11 | 22 | 22 | 37 | 140M-H8P-C50 |
| 70 | 210 | 350 | 490 | 630 | 700 | 770 | — | — | — | 20 | 25 | 50 | 60 | 15 | 30 | 37 | 55 | 140M-H8P-C70 |
| 100 | 300 | 500 | 700 | 900 | 1000 | 1100 | — | — | — | 25 | 30 | 60 | 75 | 22 | 45 | 55 | 75 | 140M-H8P-D10 |
| 100 | 500 | 700 | 900 | 1100 | 1300 | 1500 | — | — | — | 30 | 30 | 75 | 100 | 30 | 55 | 75 | 110 | 140M-H8R-D10 |
| J-Frame | ||||||||||||||||||
| 100 | 500 | 600 | 700 | 800 | 900 | 1000 | — | — | — | 30 | 30 | 75 | 100 | 22 | 37 | 45 | 55 | 140M-J8P-D10 |
| 125 | 625 | 750 | 875 | 1000 | 1125 | 1250 | — | — | — | 40 | 40 | 100 | 125 | 22 | 45 | 55 | 90 | 140M-J8P-D12 |
| 150 | 750 | 900 | 1050 | 1200 | 1350 | 1500 | — | — | — | 50 | 50 | 100 | 150 | 30 | 55 | 75 | 110 | 140M-J8P-D15 |
| 175 | 875 | 1050 | 1225 | 1400 | 1575 | 1750 | — | — | — | 50 | 60 | 125 | 150 | 37 | 55 | 90 | 132 | 140M-J8P-D17 |
| 200 | 1000 | 1200 | 1400 | 1600 | 1800 | 2000 | — | — | — | 60 | 75 | 150 | 200 | 45 | 75 | 90 | 132 | 140M-J8P-D20 |
| 225 | 1125 | 1350 | 1575 | 1800 | 2025 | 2250 | — | — | — | 75 | 75 | 150 | 200 | 55 | 90 | 110 | 160 | 140M-J8P-D22 |
| 250 | 1250 | 1500 | 1750 | 2000 | 2250 | 2500 | — | — | — | 75 | 100 | 200 | 250 | 55 | 90 | 132 | 160 | 140M-J8P-D25 |
| L-Frame | ||||||||||||||||||
| 225 | 1125 | 1265 | 1410 | 1545 | 1690 | 1830 | 1970 | 2110 | 2250 | 50 | 60 | 125 | 150 | 55 | 90 | 110 | 160 | 140M-L8P-D22 |
| 250 | 1250 | 1405 | 1560 | 1720 | 1875 | 2030 | 2185 | 2340 | 2500 | 60 | 75 | 150 | 200 | 55 | 90 | 132 | 160 | 140M-L8P-D25 |
| 300 | 1500 | 1690 | 1875 | 2060 | 2250 | 2440 | 2625 | 2810 | 3000 | 75 | 75 | 150 | 200 | 55 | 110 | 160 | 200 | 140M-L8P-D30 |
| 350 | 1750 | 1970 | 2190 | 2410 | 2625 | 2840 | 3065 | 3285 | 3500 | 75 | 100 | 200 | 250 | 75 | 132 | 160 | 250 | 140M-L8P-D35 |
| 400 | 2000 | 2250 | 2500 | 2750 | 3000 | 3250 | 3500 | 3750 | 4000 | 100 | 100 | 250 | 300 | 90 | 160 | 200 | 250 | 140M-L8P-D40 |
| 450 | 2250 | 2530 | 2810 | 3098 | 3375 | 3660 | 3940 | 4220 | 4500 | 100 | 125 | 250 | 350 | 110 | 160 | 200 | 315 | 140M-L8P-D45 |
| 500 | 2500 | 2810 | 3125 | 3440 | 3750 | 4660 | 4375 | 4690 | 5000 | 125 | 150 | 300 | 400 | 110 | 200 | 250 | 355 | 140M-L8P-D50 |
| 600 | 3000 | 3375 | 3760 | 4110 | 4500 | 4880 | 5250 | 5630 | 6000 | 150 | 150 | 350 | 450 | 132 | 250 | 315 | 450 | 140M-L8P-D60 |
| N-Frame | ||||||||||||||||||
| 800 | 1600 | 2400 | 3200 | 4000 | 4800 | 5600 | 6400 | — | — | 150 | 200 | 400 | 500 | 160 | 250 | 355 | 500 | 140M-N8P-D80 |
| 1200 | 2400 | 3600 | 4800 | 6000 | 7200 | 8400 | 9600 | — | — | 250 | 300 | 600 | 700 | 200 | 250 | 500 | 710 | 140M-N8P-E12 |
| ¬ The Hp and kW ratings shown are for reference only. They allow for a magnetic trip setting of at least up to 13X the motor FLA. However, the final selection of the MCP should be made based on motor full load current and the requirements of local electrical codes. | ||||||||||||||||||
| T The interrupting rating for MCPs is dependent upon the controller used. Please contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information. | ||||||||||||||||||
Application Ratings
UL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only
| Cat. No. | UL 508 — Manual Motor Controller | UL 508 Self-Protected (Type E) Combination Motor Controller |
UL 489 Inverse Time C.B. w/UL 508 Motor Overload Protection |
||||||||
| Group Motor Installation | Motor Disconnect | Tap Conductor Protection | |||||||||
| Max. Fuse or C.B. per NEC | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | ||||||
| 480V | 600V | 480V | 600V | 480V | 600V | 480Y/277V | 600Y/347V | 480V | 600V | ||
| C-Frame | |||||||||||
| 140M-C2E-A16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A25 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A40 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A63 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B10 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B25 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-C2E-B40 | 450 | 65 | 25 | 65 | 25 | 65 | 25 | 65 | 25 | — | — |
| 140M-C2E-B63 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-C2E-C10 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-C2E-C16 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — | — | — |
| 140M-C2E-C20 | 450 | 30 | 30 | 10 | 10 | 10 | — | 10 | — | — | — |
| 140M-C2E-C25 | 450 | 25 | 10 | 10 | 5 | — | — | — | — | — | — |
| D-Frame | |||||||||||
| 140M-D8E-B25 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-B40 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-B63 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C10 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C16 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C20 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-D8E-C25 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — | — | — |
| F-Frame | |||||||||||
| 140M-F8E-C10 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C16 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C20 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C25 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C32 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C45 | 600 | 65 | 18 | 65 | 18 | 65 | — | 65 | — | — | — |
| CMN-Frame | |||||||||||
| 140-CMN-2500 | 1000 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-4000 | 1000 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-6300 | 1000 | 42 | 18 | — | — | — | — | — | — | — | — |
| 140-CMN-9000 | 1000 | 35 | 10 | — | — | — | — | — | — | — | — |
| I-Frame | |||||||||||
| 140M-I8E-C80 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D10 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D16 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D20 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| J-Frame | |||||||||||
| 140M-J2E-C50 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D10 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D16 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D25 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J8E-C50 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D10 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D16 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D25 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| L-Frame | |||||||||||
| 140M-L2E-D25 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L2E-D40 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L2E-D60 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L2E-D63 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L8E-D25 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| 140M-L8E-D40 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| 140M-L8E-D60 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| 140M-L8E-D63 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||||
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Self-Protected (Type E) Combination Motor Controller |
|||||||
| Group Motor Installation | Motor Disconnect | Tap Conductor Protection | |||||||
| Max. Fuse or C.B. per NEC | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | |||||
| 480V | 600V | 480V | 600V | 480V | 600V | 480Y/277V | 600Y/347V | ||
| C-Frame | |||||||||
| 140M-C2T-A16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A25 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A40 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A63 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-B10 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-B16 | 450 | 65 | 47 | 65 | 47 | 65 | 30 | 65 | 30 |
| 140M-C2T-B25 | 450 | 65 | 25 | 65 | 25 | 65 | 25 | 65 | 25 |
| 140M-C2T-B40 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — |
| 140M-C2T-B63 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — |
| 140M-C2T-C10 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — |
| 140M-C2T-C16 | 450 | 30 | 30 | 10 | 10 | 10 | — | 10 | — |
| D-Frame | |||||||||
| 140M-D8T-C16 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 |
| 140M-D8T-C20 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — |
| F-Frame | |||||||||
| 140M-F8T-C25 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 |
| 140M-F8T-C32 | 600 | 65 | 18 | 65 | 18 | 65 | 18 | 65 | 18 |
| For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||
UL Listed Application Ratings — Motor Circuit Protectors Only§
| Cat. No. | UL 508 Manual Motor Controller | UL 489 Instantaneous Trip Circuit Breaker (Magnetic Only) | |||||
| Group Motor Installation | Motor Disconnect | Motor Circuit Protector | |||||
| Max. Fuse or C.B. per NEC | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | ||||
| 480V | 600V | 480V | 600V | 480V | 600V | ||
| C-Frame | |||||||
| 140M-C2N-A16 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A25 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A40 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A63 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B10 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B16 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B25 | 450 | 65 | 30 | 65 | 30 | — | — |
| D-Frame | |||||||
| 140M-D8N-B25 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-B40 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-B63 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C10 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C16 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C25 | 450 | 30 | 30 | 30 | 30 | — | — |
| F-Frame | |||||||
| 140M-F8N-C25 | 600 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8N-C32 | 600 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8N-C45 | 600 | 65 | 18 | 65 | 18 | — | — |
| H-Frame | |||||||
| 140M-H8P-B30 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-B70 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C15 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C30 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C50 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C70 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-D10 | — | — | — | — | — | 65 | 30 |
| 140M-H8R-D10 | — | — | — | — | — | 65 | 30 |
| J-Frame | |||||||
| 140M-J8P-C70 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-C90 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D10 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D12 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D15 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D17 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D20 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D22 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D25 | — | — | — | — | — | 65 | 30 |
| L-Frame | |||||||
| 140M-L8P-D22 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D25 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D30 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D35 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D40 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D45 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D50 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D60 | — | — | — | — | — | 65 | 30 |
| N-Frame | |||||||
| 140M-N8P-D80 | — | — | — | — | — | 65 | 35 |
| 140M-N8P-E12 | — | — | — | — | — | 65 | 35 |
| § Separate overload protection is required. | |||||||
| The interrupting rating for MCPs is dependent upon the controller used. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information. | |||||||
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-K Contactors
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type F Combination Motor Controller |
UL 508 Type E Self-Protected Combination Motor Controller |
|||||||||
| Group Motor Installation | Motor Disconnect | |||||||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | |||||
| 480V | 600V | 480V | 600V | 480Y/277V§ | 600Y/347V§ | 480Y/277V§ | 600Y/347V§ | |||||
| C-Frame | ||||||||||||
| 140M-C2E-A16 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A25 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A40 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A63 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B10 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B16 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B25 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-C2E-B40 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-C2E-B63 | 450 | 100-K05 | 65 | 30 | 65 | 30 | — | — | — | — | — | — |
| 140M-C2E-C10 | 450 | 100-K09 | 65 | 30 | 65 | 30 | — | — | — | — | — | — |
| 140M-C2E-C16 | 450 | 100-K12 | 30 | 30 | 30 | 30 | — | — | — | — | — | — |
| 140M-C2E-C20 | — | — | — | — | — | — | — | — | — | — | — | — |
| 140M-C2E-C25 | — | — | — | — | — | — | — | — | — | — | — | — |
| 140M-C2E-C25 | — | — | — | — | — | — | — | — | — | — | — | — |
| D-Frame | ||||||||||||
| 140M-D8E-B25 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-B40 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-B63 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-C10 | 450 | 100-K09 | 65 | 30 | 65 | 30 | 100-K09 | 65 | 30 | — | — | — |
| 140M-D8E-C16 | 450 | 100-K12 | 65 | 30 | 65 | 30 | 100-K12 | 65 | 30 | — | — | — |
| 140M-D8E-C20 | — | — | — | — | — | — | — | — | — | — | — | — |
| 140M-D8E-C25 | — | — | — | — | — | — | — | — | — | — | — | — |
| § For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | ||||||||||||
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-C Contactors
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type F Combination Motor Controller |
UL 508 Type E Self-Protected Combination Motor Controller |
|||||||||
| Group Motor Installation | Motor Disconnect | |||||||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | |||||
| 480V | 600V | 480V | 600V | 480Y/277V§ | 600Y/347V§ | 480Y/277V§ | 600Y/347V§ | |||||
| C-Frame | ||||||||||||
| 140M-C2E-A16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A25 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A40 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A63 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B10 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C09 | 65 | 30 |
| 140M-C2E-B40 | 450 | 100-C09 | 65 | 25 | 65 | 25 | 100-C09 | 65 | 30 | — | 65 | 25 |
| 140M-C2E-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — | — | 65 | — |
| 140M-C2E-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — | — | 65 | — |
| 140M-C2E-C16 | 450 | 100-C12 | 30 | 30 | 30 | 30 | 100-C12 | 30 | — | — | 30 | — |
| 140M-C2E-C20 | 450 | 100-C16 | 30 | 30 | 10 | 10 | 100-C23 | 10 | — | — | 10 | — |
| 140M-C2E-C25 | 450 | 100-C23 | 25 | 10 | 10 | 10 | — | — | — | — | — | — |
| 140M-C2E-C25 | 450 | 100-C30 | 25 | 10 | 10 | 5 | — | — | — | — | — | — |
| D-Frame | ||||||||||||
| 140M-D8E-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C09 | 65 | 30 |
| 140M-D8E-B25 | — | — | — | — | — | — | — | — | — | 100-C23 | 65 | 30 |
| 140M-D8E-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C23 | 65 | 30 |
| 140M-D8E-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C16 | 450 | 100-C12 | 65 | 30 | 65 | 30 | 100-C12 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C20 | 450 | 100-C23 | 65 | 30 | 65 | 30 | 100-C23 | 65 | — | 100-C30 | 65 | — |
| 140M-D8E-C25 | 450 | 100-C23 | 30 | 30 | 30 | 30 | 100-C23 | 30 | — | 100-C30 | 30 | — |
| F-Frame | ||||||||||||
| 140M-F8E-C10 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C16 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C20 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C25 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C32 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C45 | 600 | 100-C37 | 65 | 18 | 65 | 18 | 100-C37 | 65 | — | 100-C37 | 65 | — |
| CMN-Frame | ||||||||||||
| 140-CMN-2500 | 1000 | 100-C16 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-4000 | 1000 | 100-C30 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-6300 | 1000 | 100-C43 | 42 | 18 | — | — | — | — | — | — | — | — |
| 140-CMN-9000 | 1000 | 100-C72 | 35 | 10 | — | — | — | — | — | — | — | — |
| § For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | ||||||||||||
UL Listed Application Ratings - Motor Circuit Protectors with Bulletin 100-C Contactors§
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type E (Self-Protected) Combination Motor Controller | |||||||
| Group Motor Installation | Motor Disconnect | ||||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | |||
| 480V | 600V | 480V | 600V | 480Y/277VT | 600Y/347VT | ||||
| C-Frame | |||||||||
| 140M-C2N-A16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A25 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A40 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A63 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B10 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — |
| D-Frame | |||||||||
| 140M-D8N-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — |
| 140M-D8N-B25 | — | — | — | — | — | — | 100-C23 | 65 | 30 |
| 140M-D8N-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C23 | 65 | 30 |
| 140M-D8N-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C16 | 450 | 100-C12 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C25 | 450 | 100-C23 | 30 | 30 | 30 | 30 | 100-C30 | 65 | — |
| F-Frame | |||||||||
| 140M-F8N-C25 | 600 | 100-C23 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8N-C32 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8N-C45 | 600 | 100-C37 | 65 | 18 | 65 | 18 | 100-C37 | 65 | — |
| § Separate overload protection is required. | |||||||||
| T For full-voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||
Definition of Type 2 Short Circuit Coordination:
- The contactor or starter must not endanger persons or plant in the event of a short circuit.
- No damage to the motor protection device or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without appreciable deformation (such as with a screwdriver).
In the event of short circuit, fast-opening, current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical, fully short-circuit coordinated starter combinations with Type 2 coordination.
Type 2 Coordination 400V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Trip | High Trip | Mag Only Trip | 400V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 100 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 100 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 100 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 100 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 100 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 100 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 50 | 100-C09 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 50 | 100-C09 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 50 | 100-C09 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 50 | 100-C09 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 50 | 100-C12¬ |
| 140M-C2E-C20 | 140M-C2T-C16 | — | — | — |
| 140M-C2E-C25 | — | — | — | — |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 100 | 100-C09 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 100 | 100-C09 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 100 | 100-C09 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 65 | 100-C09 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 65 | 100-C12 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 65 | 100-C23 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 50 | 100-C23 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 100 | 100-C09 |
| 140M-F8E-C16 | — | — | 100 | 100-C12 |
| 140M-F8E-C20 | — | — | 100 | 100-C23 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 100 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 100 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 100 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 65 | 100-C16 |
| 140-CMN-4000 | — | — | 65 | 100-C30 |
| 140-CMN-6300 | — | — | 42 | 100-C43 |
| 140-CMN-9000 | — | — | 35 | 100-C72 |
| ¬ Cat. No. 100-C16 contactors Type 1 only | ||||
Type 2 Coordination 480V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Trip | High Trip | Mag Only Trip | 480V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 65 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 65 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 65 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 65 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 65 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 65 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 50 | 100-C16 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 50 | 100-C30 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 50 | 100-C30 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 50 | 100-C30 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 10 | 100-C30 |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 10 | 100-C30 |
| 140M-C2E-C25 | — | — | 10 | 100-C30 |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 65 | 100-C09 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 65 | 100-C09 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 65 | 100-C09 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 65 | 100-C09 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 65 | 100-C12 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 65 | 100-C23 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 65 | 100-C23 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 65 | 100-C09 |
| 140M-F8E-C16 | — | — | 65 | 100-C12 |
| 140M-F8E-C20 | — | — | 65 | 100-C23 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 65 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 65 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 65 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 65 | 100-C16 |
| 140-CMN-4000 | — | — | 65 | 100-C30 |
| 140-CMN-6300 | — | — | 42 | 100-C43 |
| 140-CMN-9000 | — | — | 35 | 100-C72 |
Type 2 Coordination 600V
| Cat. No. | Max. Short Circuit Current [kA] | Max Fuse or C.B per NEC | For Use With Contactors Below (or larger) | ||
| Standard Trip | High Trip | Mag Only Trip | 600V | ||
| C-Frame | |||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 47 | 450 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 47 | 450 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 47 | 450 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 47 | 450 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 47 | 450 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 47 | 450 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 10 | 450 | 100-C16 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 10 | 450 | 100-C16 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 5 | 450 | 100-C23 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 5 | 450 | 100-C30 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 5 | 450 | 100-C30 |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 5 | 450 | 100-C30 |
| 140M-C2E-C25 | — | — | 5 | 450 | 100-C30 |
| D-Frame | |||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 30 | 450 | 100-C30 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 30 | 450 | 100-C30 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 30 | 450 | 100-C30 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 30 | 450 | 100-C30 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 30 | 450 | 100-C30 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 5 | 450 | 100-C30 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 5 | 450 | 100-C30 |
| F-Frame | |||||
| 140M-F8E-C10 | — | — | 30 | 600 | 100-C30 |
| 140M-F8E-C16 | — | — | 30 | 600 | 100-C30 |
| 140M-F8E-C20 | — | — | 30 | 600 | 100-C30 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 30 | 600 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 30 | 600 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 10 | 600 | 100-C37 |
| CMN-Frame | |||||
| 140-CMN-2500 | — | — | 42 | 1000 | 100-C16 |
| 140-CMN-4000 | — | — | 42 | 1000 | 100-C30 |
| 140-CMN-6300 | — | — | 18 | 1000 | 100-C43 |
| 140-CMN-9000 | — | — | 10 | 1000 | 100-C72 |
Accessories
Notes: 1. See Bulletin 140U for Internal and External Accessories for Bulletin 140M-H, J, L and N frames.
2. Bulletin 140M-I frame Accessories such as auxiliaries, alarms, undervoltage and shunt trips are only available as factory installed modifications. See 140M Factory Modifications (Open).
Internal Control Modules — Field Installed
Terminal Lugs
Terminal Lugs, Continued
140M Factory Modifications (Open)
Note: For modifications add (option code _) for desired features to cat. no. Available in North America only.
| f | ||
| Miscellaneous | ||
| Code | Description | Frame Size |
| KN | Black Lockable Knob | C, D, F, CMN |
| KY | Red/Yellow Lockable Knob | C, D, F, CMN |
| TE | Spacing Adapter for Self-Protected Starters (Type E) | C, D, F |
| MT | STD Bus Bar Mount, Top | C, D, F, H, CMN |
| MU | STD Bus Bar Mount, Universal | J, K, L |
| g | |||
| Aux / Trip Contacts - C, D, F | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Right Side | ||
| X | Placeholder | X | Placeholder |
| A | 1 N.C. | C | 1 N.O. + 1 N.C. |
| B | 1 N.O. | D | 2 N.O. |
| C | 1 N.O. + 1 N.C. | E | 2 N.C. |
| D | 2 N.O. | K | 1 N.C. (SC+OL) + 1 N.C. (SC) |
| E | 2 N.C. | L | 1 N.O. (SC+OL) + 1 N.O. (SC) |
| R | 1 N.C. + 1 N.O. (SC+OL) | M | 1 N.C. (SC+OL) + 1 N.O. (SC) |
| S | 1 N.O. + 1 N.O. (SC+OL) | N | 1 N.O. (SC+OL) + 1 N.C. (SC) |
| Q | 1 N.O. (SC) + 1 N.C. (SC) | ||
| g | |||
| Aux / Trip Contacts - CMN | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Top Front | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | K | 1 N.C. (OL) + 1 N.C. (SC) |
| D | 2 N.O. | L | 1 N.O. (OL) + 1 NO (SC) |
| E | 2 N.C. | M | 1 N.C. (OL) + 1 N.O. (SC) |
| N | 1 N.O. (OL) + 1 N.C. (SC) | ||
Cannot be combined with option "h".
| g | |||
| Aux / Trip Contacts - H, J, L | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Right Side | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | ||
| RT | 1 N.O. + 1 N.C. (Overload Function) | ||
| F¬ | 2 N.O. + 2 N.C. | ||
| N¬ | 1 N.O. (SC+OL) + 1 N.C. (SC) | ||
| T¬ | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) | ||
¬ Only available on MCPs.
T J- and L-Frame MPCB only.
| g | |||
| Aux / Trip Contacts - I, N | |||
| 1st Code | Description | 2nd Code | Description |
| Left Side | Right Side | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | C | 1 N.O. + 1 N.C. |
| F | 2 N.O. + 2 N.C. | F¬ | 2 N.O. + 2 N.C. |
| N | 1 N.O. (SC+OL) + 1 N.C. (SC) | N¬ | 1 N.O. (SC+OL) + 1 N.C. (SC) |
| T | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) | T¬ | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) |
¬ Only available on MCPs.
140M Factory Modifications (Open), Continued
Note: For modifications add (option code *) for desired features to cat. no. Available in North America only.
| h | |||
| UV and Shunt Trips - C, D, F | |||
| 1st Code | Description | 2nd Code | Description |
| Left Side | Voltage | ||
| G | Undervoltage Trip | J | 24V AC, 60 Hz |
| P | Shunt Trip | K | 24V AC, 50 Hz |
| D | 120V AC, 60 Hz | ||
| C | 110V AC, 50 Hz | ||
| H | 208V AC, 60 Hz | ||
| F | 220…230V AC, 50 Hz | ||
| A | 240V AC, 60 Hz | ||
| T | 277V AC, 50 Hz | ||
| N | 380…400V AC, 50 Hz | ||
| B | 480V AC, 60 Hz and 415V AC, 50 Hz | ||
| VC | 600V AC, 60 Hz | ||
| M | 575V AC, 60 Hz and 500V AC, 50 Hz | ||
| ZR | 9V DC | ||
| ZQ | 12V DC | ||
| ZJ | 24V DC | ||
| ZW | 36V DC | ||
| ZY | 48V DC | ||
| ZZ | 60V DC | ||
| ZB | 64V DC | ||
| ZG | 72V DC | ||
| ZE | 80V DC | ||
| h | |||
| UV and Shunt Trips - CMN | |||
| 1st Code | Description | 2nd Code | Description |
| Top Front | Voltage | ||
| G | Undervoltage Trip | KJ | 24V AC, 60 Hz and 24V AC, 50 Hz |
| P | Shunt Trip | D | 120V AC, 60 Hz and 110V AC, 50 Hz |
| A | 240V AC, 60 Hz and 220…230V AC, 50 Hz | ||
| Cannot be combined with option "g". | |||
| h | |||
| UV and Shunt Trips - H, J, L | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC/DC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…500V AC | ||
| C | 525…600V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…60V AC/DC |
| D | 110…240V AC/DC | ||
| B | 380…600V AC | ||
| h | |||
| UV and Shunt Trips - I | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…480V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…24V AC/DC |
| D | 48…127V AC and 48…60V DC | ||
| N | 208…380V AC and 110…127V DC | ||
| B | 415…600V AC and 220…250V DC | ||
| h | |||
| UV and Shunt Trips - N | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…480V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…24V AC/DC |
| D | 110…240V AC and 110…125V DC | ||
| N | 380…440V AC and 220…250V DC | ||
| B | 480…600V AC | ||
Specifications
IEC Performance Data
| Cat. No. 140M-C2E- | ||||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | C20 | C25 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1 | 1.6 | 2.5 | 4 | 6.3 | 10 | 16 | 20 | 25 |
| Magnetic Release Current | [A] | 2.1 | 3.3 | 5.2 | 8.2 | 13 | 21 | 33 | 52 | 82 | 130 | 208 | 260 | 325 |
| Switching of Standard Three-Phase Motors | ||||||||||||||
| AC-2, AC-3 | ||||||||||||||
| 230/240V | [kW] | — | — | — | 0.06/0.09 | 0.12 | 0.18/0.25 | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 4.0/5.5 | — |
| 400/415V | [kW] | 0.02 | 0.06 | 0.09 | 0.12/0.18 | 0.25 | 0.37/0.55 | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 | 7.5/10 | 11 |
| 500V | [kW] | — | — | — | 0.18 | 0.25/0.37 | 0.55/0.75 | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 | 11 | 15 |
| 690V | [kW] | — | — | — | 0.25 | 0.37/0.55 | 0.75/1.1 | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 | 15/17 | 18.5/22 |
| Back-Up Fuses | ||||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 | 100 | 100 |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 | 80 | 80 |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 | 80 | 80 | 80 |
| 690V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 16 | 20 | 35 | 50 | 50 | 63 | 63 | 63 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||||
| Icu | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 50 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 50 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||||
| Ics | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 50 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 15 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 |
| ¬ No back-up fuse required. | ||||||||||||||
| Cat. No. 140M-D8E- | Cat. No. 140M-F8E- | |||||||||||||
| B25 | B40 | B63 | C10 | C16 | C20 | C25 | C10 | C16 | C20 | C25 | C32 | C45 | ||
| Rated Operational Current, Ie | [A] | 2.5 | 4.0 | 6.3 | 10 | 16 | 20 | 25 | 10 | 16 | 20 | 25 | 32 | 45 |
| Magnetic Release Current | [A] | 33 | 52 | 82 | 130 | 208 | 260 | 325 | 130 | 208 | 260 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | ||||||||||||||
| AC-2, AC-3 | ||||||||||||||
| 230/240V | [kW] | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 4.0/5.5 | — | 2.2 | 3.0/4.0 | 4.0/5.5 | 5.5/6.3 | 7.5 | 11/13 |
| 400/415V | [kW] | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 | 7.5/10 | 11 | 3.0/4.0 | 5.5/7.5 | 7.5/10 | 11 | 15 | 18.5/22 |
| 500V | [kW] | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 | 11 | 15 | 4.0/6.3 | 7.5/10 | 11 | 15 | 15/20 | 22/30 |
| 690V | [kW] | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 | 15/17 | 18.5/22 | 5.5/7.5 | 11/13 | 15/17 | 18.5/22 | 22/25 | 30/40 |
| Back-Up Fuses | ||||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 | 80 | 100 | 100 | 100 | 125 | 125 |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 | 80 | 100 | 100 | 100 | 125 | 125 |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | 80 | 100 | 100 | 80 | 100 | 100 | 100 | 125 | 125 |
| 690V | [A] | 20 | 35 | 50 | 50 | 63 | 63 | 63 | 63 | 80 | 80 | 80 | 100 | 100 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||||
| Icu | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 6 | 6 | 6 | 10 | 10 | 10 | 10 | 10 | 10 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||||
| Ics | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 4 | 4 | 4 | 10 | 10 | 10 | 10 | 6 | 6 |
| ¬ No back-up fuse required. | ||||||||||||||
| Cat. No. | 140-CMN-… | ||||
| -2500 | -4000 | -6300 | -9000 | ||
| Rated Operational Current, Ie | [A] | 25 | 40 | 63 | 90 |
| Magnetic Release Current | [A] | 350 | 560 | 890 | 1260 |
| Switching of Standard Three-Phase Motors | |||||
| AC-2, AC-3 | |||||
| 230/240VT | [kW] | 5.5/7.5 | 10/11 | 13/20 | 22/25 |
| 400/415VT | [kW] | 7.5/13 | 15/22 | 25/32 | 37/45 |
| 500VT | [kW] | 11/15 | 18.5/25 | 30/40 | 45/55 |
| 690VT | [kW] | 15/22 | 25/30 | 37/55 | 63/75 |
| Back-up fuses | |||||
| gG, gL,, only if Icc ³ Icu | |||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | 160 | 160 | 160 | 160 |
| 500V | [A] | 160 | 160 | 160 | 160 |
| 690V | [A] | 160 | 160 | 160 | 160 |
| Ultimate short-circuit breaking capacity Icu | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 65 | 65 | 65 | 50 |
| 500V | [kA] | 50 | 30 | 30 | 25 |
| 690V | [kA] | 15 | 8 | 8 | 6 |
| Rated service short-circuit breaking capacity Ics | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 65 | 50 | 50 | 25 |
| 500V | [kA] | 50 | 25 | 25 | 13 |
| 690V | [kA] | 15 | 8 | 6 | 6 |
| ¬ No back-up fuse required. | |||||
| T Power ratings: Preferred values according to IEC 60072-1. | |||||
IEC Performance Data, Continued
| Cat. No. 140M-C2N- | ||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1 | 1.6 | 2.5 |
| Magnetic Release Current | [A] | 2.1 | 3.3 | 5.2 | 8.2 | 13 | 21 | 32 |
| Switching of Standard Three-Phase Motors | ||||||||
| AC-2, AC-3 | ||||||||
| 230/240V | [kW] | — | — | — | 0.06/0.09 | 0.12 | 0.18/0.25 | 0.37 |
| 400/415V | [kW] | 0.02 | 0.06 | 0.09 | 0.12/0.18 | 0.25 | 0.37/0.55 | 0.75 |
| 500V | [kW] | — | — | — | 0.18 | 0.25/0.37 | 0.55/0.75 | 1.1 |
| 690V | [kW] | — | — | — | 0.25 | 0.37/0.55 | 0.75/1.1 | 1.8 |
| Back-Up Fuses | ||||||||
| gG, gL, only if Icc³Icu¬ | ||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 690V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 16 | 20 |
| Ultimate Short Circuit Breaking Capacity | ||||||||
| Icu | ||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 10 | 8 |
| Rated Service Short Circuit Breaking Capacity | ||||||||
| Ics | ||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 |
| ¬ No back-up fuse required. | ||||||||
| Cat. No. 140M-D8N- | Cat. No. 140M-F8N- | |||||||||
| B25 | B40 | B63 | C10 | C16 | C25 | C25 | C32 | C45 | ||
| Rated Operational Current, Ie | [A] | 2.5 | 4.0 | 6.3 | 10 | 16 | 25 | 25 | 32 | 45 |
| Magnetic Release Current | [A] | 32 | 52 | 82 | 130 | 208 | 325 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | ||||||||||
| AC-2, AC-3 | ||||||||||
| 230/240V | [kW] | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | — | 5.5/6.3 | 7.5 | 11/13 |
| 400/415V | [kW] | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 | 11 | 11 | 15 | 18.5/22 |
| 500V | [kW] | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 | 15 | 15 | 15/20 | 22/30 |
| 690V | [kW] | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 | 18.5/22 | 18.5/22 | 22/25 | 30/40 |
| Back-Up Fuses | ||||||||||
| gG, gL, only if Icc³Icu | ||||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 125 | 125 |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 | 125 | 125 |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | 80 | 100 | 100 | 125 | 125 |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | 80 | 80 | 100 | 125 | 125 |
| 690V | [A] | 20 | 35 | 50 | 50 | 63 | 63 | 80 | 100 | 100 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||
| Icu | ||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 50 | 65 | 65 | 65 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 50 | 65 | 65 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 6 | 6 | 10 | 10 | 10 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||
| Ics | ||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 4 | 4 | 10 | 6 | 6 |
| ¬ No back-up fuse required. | ||||||||||
| Cat. No. 140M-C2T- | ||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.40 | 0.63 | 1.0 | 1.6 | 2.5 | 4.0 | 6.3 | 10 | 16 |
| Magnetic Release Current | [A] | 3.2 | 5.2 | 8.2 | 13 | 21 | 32 | 52 | 82 | 130 | 208 | 260 |
| Switching of Standard Three-Phase Motors | ||||||||||||
| AC-2, AC-3 | ||||||||||||
| 230/240V | [kW] | — | — | — | 0.06/0.09 | 0.12 | 0.18/0.25 | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 |
| 400/415V | [kW] | 0.02 | 0.06 | 0.09 | 0.12/0.18 | 0.25 | 0.37/0.55 | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 |
| 500V | [kW] | — | — | — | 0.18 | 0.25/0.37 | 0.55/0.75 | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 |
| 690V | [kW] | — | — | — | 0.25 | 0.37/0.55 | 0.75/1.1 | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 |
| Back-Up Fuses | ||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||
| 230/240V | [A] | ¬ | ¬ | |||||||||