| Rated Operational Current [A] (Ie)
|
Magnetic Trip Current [A]
|
Ultimate Interrupting Current [kA], (Icm)
|
Max. 3-phase Hp Ratings¹
|
3-phase kW Ratings¬
|
Cat. No.
|
| 400V
|
480V
|
200V
|
230V
|
460V
|
575V
|
230V
|
400/415V
|
500V
|
690V
|
| C-Frame
|
| 0.16
|
2.1
|
100
|
65
|
—
|
—
|
—
|
—
|
—
|
0.02
|
—
|
—
|
140M-C2N-A16
|
| 0.25
|
3.3
|
100
|
65
|
—
|
—
|
—
|
—
|
—
|
0.06
|
—
|
—
|
140M-C2N-A25
|
| 0.4
|
5.2
|
100
|
65
|
—
|
—
|
—
|
—
|
—
|
0.09
|
—
|
—
|
140M-C2N-A40
|
| 0.63
|
8.2
|
100
|
65
|
—
|
—
|
—
|
—
|
0.09
|
0.18
|
0.18
|
0.25
|
140M-C2N-A63
|
| 1
|
13
|
100
|
65
|
—
|
—
|
0.5
|
0.75
|
0.12
|
0.25
|
0.37
|
0.55
|
140M-C2N-B10
|
| 1.6
|
21
|
100
|
65
|
—
|
—
|
1
|
1
|
0.25
|
0.55
|
0.75
|
1.1
|
140M-C2N-B16
|
| 2.5
|
33
|
100
|
65
|
0.5
|
0.75
|
1.5
|
2
|
0.37
|
0.75
|
1.1
|
1.8
|
140M-C2N-B25
|
| D-Frame
|
| 2.5
|
33
|
100
|
65
|
0.5
|
0.75
|
1.5
|
2
|
0.37
|
0.75
|
1.1
|
1.8
|
140M-D8N-B25
|
| 4
|
52
|
100
|
65
|
1
|
1
|
3
|
3
|
0.75
|
1.5
|
2.2
|
3
|
140M-D8N-B40
|
| 6.3
|
82
|
100
|
65
|
1.5
|
2
|
5
|
5
|
1.5
|
2.2
|
3
|
4
|
140M-D8N-B63
|
| 10
|
130
|
100
|
65
|
3
|
3
|
7.5
|
10
|
2.2
|
4
|
6.3
|
7.5
|
140M-D8N-C10
|
| 16
|
208
|
100
|
65
|
5
|
5
|
10
|
15
|
4
|
7.5
|
10
|
13
|
140M-D8N-C16
|
| 25
|
325
|
50
|
65
|
7.5
|
7.5
|
15
|
20
|
—
|
11
|
15
|
22
|
140M-D8N-C25
|
| F-Frame
|
| 25
|
325
|
65
|
65
|
7.5
|
10
|
20
|
25
|
6.3
|
11
|
15
|
22
|
140M-F8N-C25
|
| 32
|
416
|
65
|
65
|
7.5
|
10
|
25
|
30
|
7.5
|
15
|
20
|
25
|
140M-F8N-C32
|
| 45
|
585
|
65
|
65
|
10
|
15
|
30
|
40
|
13
|
22
|
30
|
40
|
140M-F8N-C45
|
|
|
| ¬ Horsepower/kW ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load current and, in North America, service factor.
|
| For heavy-duty starting applications (exceeding Trip Class 10), please consult your local Rockwell Automation sales office or Allen-Bradley distributor.
|
| Rated Operational Current [A] (Ie)
|
Magnetic Trip Current [A]
|
3-phase Hp Ratings¬
|
3-phase kW Ratings¬
|
Cat. No.T
|
| Cam Setting
|
| A
|
B
|
C
|
D
|
E
|
F
|
G
|
H
|
I
|
200V
|
230V
|
460V
|
575V
|
230V
|
400/ 415V
|
500V
|
690V
|
| H-Frame
|
| 3
|
9
|
15
|
21
|
27
|
30
|
33
|
—
|
—
|
—
|
0.5
|
0.5
|
1.5
|
2
|
0.6
|
0.75
|
1.1
|
1.5
|
140M-H8P-B30
|
| 7
|
21
|
35
|
49
|
63
|
70
|
77
|
—
|
—
|
—
|
1.5
|
2
|
3
|
5
|
1.1
|
2.2
|
3
|
4
|
140M-H8P-B70
|
| 15
|
45
|
75
|
100
|
135
|
150
|
165
|
—
|
—
|
—
|
3
|
3
|
10
|
10
|
3
|
5.5
|
7.5
|
11
|
140M-H8P-C15
|
| 30
|
90
|
150
|
210
|
270
|
300
|
330
|
—
|
—
|
—
|
7.5
|
10
|
20
|
25
|
5.5
|
11
|
15
|
22
|
140M-H8P-C30
|
| 50
|
150
|
250
|
350
|
450
|
500
|
550
|
—
|
—
|
—
|
15
|
15
|
30
|
40
|
11
|
22
|
22
|
37
|
140M-H8P-C50
|
| 70
|
210
|
350
|
490
|
630
|
700
|
770
|
—
|
—
|
—
|
20
|
25
|
50
|
60
|
15
|
30
|
37
|
55
|
140M-H8P-C70
|
| 100
|
300
|
500
|
700
|
900
|
1000
|
1100
|
—
|
—
|
—
|
25
|
30
|
60
|
75
|
22
|
45
|
55
|
75
|
140M-H8P-D10
|
| 100
|
500
|
700
|
900
|
1100
|
1300
|
1500
|
—
|
—
|
—
|
30
|
30
|
75
|
100
|
30
|
55
|
75
|
110
|
140M-H8R-D10
|
| J-Frame
|
| 100
|
500
|
600
|
700
|
800
|
900
|
1000
|
—
|
—
|
—
|
30
|
30
|
75
|
100
|
22
|
37
|
45
|
55
|
140M-J8P-D10
|
| 125
|
625
|
750
|
875
|
1000
|
1125
|
1250
|
—
|
—
|
—
|
40
|
40
|
100
|
125
|
22
|
45
|
55
|
90
|
140M-J8P-D12
|
| 150
|
750
|
900
|
1050
|
1200
|
1350
|
1500
|
—
|
—
|
—
|
50
|
50
|
100
|
150
|
30
|
55
|
75
|
110
|
140M-J8P-D15
|
| 175
|
875
|
1050
|
1225
|
1400
|
1575
|
1750
|
—
|
—
|
—
|
50
|
60
|
125
|
150
|
37
|
55
|
90
|
132
|
140M-J8P-D17
|
| 200
|
1000
|
1200
|
1400
|
1600
|
1800
|
2000
|
—
|
—
|
—
|
60
|
75
|
150
|
200
|
45
|
75
|
90
|
132
|
140M-J8P-D20
|
| 225
|
1125
|
1350
|
1575
|
1800
|
2025
|
2250
|
—
|
—
|
—
|
75
|
75
|
150
|
200
|
55
|
90
|
110
|
160
|
140M-J8P-D22
|
| 250
|
1250
|
1500
|
1750
|
2000
|
2250
|
2500
|
—
|
—
|
—
|
75
|
100
|
200
|
250
|
55
|
90
|
132
|
160
|
140M-J8P-D25
|
| L-Frame
|
| 225
|
1125
|
1265
|
1410
|
1545
|
1690
|
1830
|
1970
|
2110
|
2250
|
50
|
60
|
125
|
150
|
55
|
90
|
110
|
160
|
140M-L8P-D22
|
| 250
|
1250
|
1405
|
1560
|
1720
|
1875
|
2030
|
2185
|
2340
|
2500
|
60
|
75
|
150
|
200
|
55
|
90
|
132
|
160
|
140M-L8P-D25
|
| 300
|
1500
|
1690
|
1875
|
2060
|
2250
|
2440
|
2625
|
2810
|
3000
|
75
|
75
|
150
|
200
|
55
|
110
|
160
|
200
|
140M-L8P-D30
|
| 350
|
1750
|
1970
|
2190
|
2410
|
2625
|
2840
|
3065
|
3285
|
3500
|
75
|
100
|
200
|
250
|
75
|
132
|
160
|
250
|
140M-L8P-D35
|
| 400
|
2000
|
2250
|
2500
|
2750
|
3000
|
3250
|
3500
|
3750
|
4000
|
100
|
100
|
250
|
300
|
90
|
160
|
200
|
250
|
140M-L8P-D40
|
| 450
|
2250
|
2530
|
2810
|
3098
|
3375
|
3660
|
3940
|
4220
|
4500
|
100
|
125
|
250
|
350
|
110
|
160
|
200
|
315
|
140M-L8P-D45
|
| 500
|
2500
|
2810
|
3125
|
3440
|
3750
|
4660
|
4375
|
4690
|
5000
|
125
|
150
|
300
|
400
|
110
|
200
|
250
|
355
|
140M-L8P-D50
|
| 600
|
3000
|
3375
|
3760
|
4110
|
4500
|
4880
|
5250
|
5630
|
6000
|
150
|
150
|
350
|
450
|
132
|
250
|
315
|
450
|
140M-L8P-D60
|
| N-Frame
|
| 800
|
1600
|
2400
|
3200
|
4000
|
4800
|
5600
|
6400
|
—
|
—
|
150
|
200
|
400
|
500
|
160
|
250
|
355
|
500
|
140M-N8P-D80
|
| 1200
|
2400
|
3600
|
4800
|
6000
|
7200
|
8400
|
9600
|
—
|
—
|
250
|
300
|
600
|
700
|
200
|
250
|
500
|
710
|
140M-N8P-E12
|
|
|
| ¬ The Hp and kW ratings shown are for reference only. They allow for a magnetic trip setting of at least up to 13X the motor FLA. However, the final selection of the MCP should be made based on motor full load current and the requirements of local electrical codes.
|
| T The interrupting rating for MCPs is dependent upon the controller used. Please contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information.
|