Product Selection

Motor Circuit Protectors


Click to enlarge - 140M-C2N_100 Click to enlarge - 140M-D8N_100 Click to enlarge - 140M-F8N_4c
Cat. No. 140M-C Cat. No. 140M-D Cat. No. 140M-F

Rated Operational Current (Ie)
[A]
Magnetic Trip Current
[A]
Ultimate Interrupting Current [kA] Max. 3-phase Hp Ratings⋆  Max. kW, 3-Phase — AC-3⋆  Cat. No.
400V
(Icu)
480V
(group motor)
200V 230V 460V 575V 230V 400/415V 500V 690V
C-Frame
0.16 2.1 100 65 0.02 0.06 0.06 140M-C2N-A16
0.25 3.3 100 65 0.04 0.09 0.09 140M-C2N-A25
0.4 5.2 100 65 0.25 0.06 0.09 0.12 0.18 140M-C2N-A40
0.63 8.2 100 65 0.25 0.33 0.09 0.18 0.18 0.25 140M-C2N-A63
1 13 100 65 0.5 0.75 0.18 0.25 0.37 0.55 140M-C2N-B10
1.6 21 100 65 0.25 0.33 1 1 0.25 0.55 0.75 1.1 140M-C2N-B16
2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-C2N-B25
D-Frame
2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-D8N-B25
4 52 100 65 1 1 3 3 0.75 1.5 2.2 3 140M-D8N-B40
6.3 82 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-D8N-B63
10 130 100 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-D8N-C10
16 208 100 65 5 5 10 15 4 7.5 10 13 140M-D8N-C16
25 325 65 30 7.5 7.5 20 20 5.5 11 15 22 140M-D8N-C25
32 448 50 30 7.5 10 25 30 7.5 15 20 25 140M-D8N-C32
F-Frame
25 325 100 65 7.5 10 20 25 6.3 11 15 22 140M-F8N-C25
32 416 65 65 7.5 10 25 30 7.5 15 20 30 140M-F8N-C32
45 585 65 65 10 15 30 40 13 22 30 40 140M-F8N-C45
  
⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load current.

Note:In applications with 140M-C_N, 140M-D_N and 140M-F_N as the short circuit protection device of heavy duty starting motors, the rated operational current Ie of the above devices must be over-dimensioned with following factors:

             CLASS 10 = 1.00
             CLASS 15 = 1.22
             CLASS 20 = 1.42
             CLASS 25 = 1.58
             CLASS 30 = 1.73


Motor Circuit Protectors


Click to enlarge - 140MH8_bw Click to enlarge - 140M-J (MCP) Click to enlarge - 140M-L (MCP)
Cat. No. 140M-H Cat. No. 140M-J Cat. No. 140M-L

Rated Operational Current (Ie)
[A]
Magnetic Trip Current [A] 3-phase Hp Ratings⋆  Max. kW, 3-Phase — AC-3⋆  Cat. No.‡ 
Cam Setting
A B C D E F G H I 200V 230V 460V 575V 230V 400/415V 500V 690V
H-Frame
3 9 15 21 27 30 33 0.5 0.5 1.5 2 0.6 0.75 1.1 1.5 140M-H8P-B30
7 21 35 49 63 70 77 1.5 2 3 5 1.1 2.2 3 4 140M-H8P-B70
15 45 75 100 135 150 165 3 3 10 10 3 5.5 7.5 11 140M-H8P-C15
30 90 150 210 270 300 330 7.5 10 20 25 5.5 11 15 22 140M-H8P-C30
50 150 250 350 450 500 550 15 15 30 40 11 22 22 37 140M-H8P-C50
70 210 350 490 630 700 770 20 25 50 60 15 30 37 55 140M-H8P-C70
100 300 500 700 900 1000 1100 25 30 60 75 22 45 55 75 140M-H8P-D10
100 500 700 900 1100 1300 1500 30 30 75 100 30 55 75 110 140M-H8R-D10
J-Frame
100 500 600 700 800 900 1000 30 30 75 100 22 37 45 55 140M-J8P-D10
125 625 750 875 1000 1125 1250 40 40 100 125 22 45 55 90 140M-J8P-D12
150 750 900 1050 1200 1350 1500 50 50 100 150 30 55 75 110 140M-J8P-D15
175 875 1050 1225 1400 1575 1750 50 60 125 150 37 55 90 132 140M-J8P-D17
200 1000 1200 1400 1600 1800 2000 60 75 150 200 45 75 90 132 140M-J8P-D20
225 1125 1350 1575 1800 2025 2250 75 75 150 200 55 90 110 160 140M-J8P-D22
250 1250 1500 1750 2000 2250 2500 75 100 200 250 55 90 132 160 140M-J8P-D25
L-Frame
225 1125 1265 1410 1545 1690 1830 1970 2110 2250 50 60 125 150 55 90 110 160 140M-L8P-D22
250 1250 1405 1560 1720 1875 2030 2185 2340 2500 60 75 150 200 55 90 132 160 140M-L8P-D25
300 1500 1690 1875 2060 2250 2440 2625 2810 3000 75 75 150 200 55 110 160 200 140M-L8P-D30
350 1750 1970 2190 2410 2625 2840 3065 3285 3500 75 100 200 250 75 132 160 250 140M-L8P-D35
400 2000 2250 2500 2750 3000 3250 3500 3750 4000 100 100 250 300 90 160 200 250 140M-L8P-D40
450 2250 2530 2810 3098 3375 3660 3940 4220 4500 100 125 250 350 110 160 200 315 140M-L8P-D45
500 2500 2810 3125 3440 3750 4375 4660 4690 5000 125 150 300 400 110 200 250 355 140M-L8P-D50
600 3000 3375 3760 4110 4500 4880 5250 5630 6000 150 150 350 450 132 250 315 450 140M-L8P-D60
N-Frame
800 1600 2400 3200 4000 4800 5600 6400 150 200 400 500 160 250 355 500 140M-N8P-D80
1200 2400 3600 4800 6000 7200 8400 9600 250 300 600 700 200 250 500 710 140M-N8P-E12
  
⋆ The Hp and kW ratings shown are for reference only. They allow for a magnetic trip setting of at least up to 13X the motor FLA. However, the final selection of the MCP should be made based on motor full load current and the requirements of local electrical codes.