Catalogs > Industrial Controls Catalog > Motor Control, IEC > Motor Protection Circuit Breakers and Motor Circuit Protectors > Bulletin 140M Motor Circuit Protectors
Bulletin 140M Motor Circuit Protectors
| Introduction | Standards Compliance and Certifications | Cat. No. Explanation | Wiring Diagrams | Product Selection |
| Application Ratings | Accessories | Specifications | Approximate Dimensions |
IEC Performance Data
| Cat. No. 140M-C2E- | ||||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | C20 | C25 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1 | 1.6 | 2.5 | 4 | 6.3 | 10 | 16 | 20 | 25 |
| Magnetic Release Current | [A] | 2.1 | 3.3 | 5.2 | 8.2 | 13 | 21 | 33 | 52 | 82 | 130 | 208 | 260 | 325 |
| Switching of Standard Three-Phase Motors | ||||||||||||||
| AC-2, AC-3 | ||||||||||||||
| 230/240V | [kW] | — | — | — | 0.06/0.09 | 0.12 | 0.18/0.25 | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 4.0/5.5 | — |
| 400/415V | [kW] | 0.02 | 0.06 | 0.09 | 0.12/0.18 | 0.25 | 0.37/0.55 | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 | 7.5/10 | 11 |
| 500V | [kW] | — | — | — | 0.18 | 0.25/0.37 | 0.55/0.75 | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 | 11 | 15 |
| 690V | [kW] | — | — | — | 0.25 | 0.37/0.55 | 0.75/1.1 | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 | 15/17 | 18.5/22 |
| Back-Up Fuses | ||||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 | 100 | 100 |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 | 80 | 80 |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 | 80 | 80 | 80 |
| 690V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 16 | 20 | 35 | 50 | 50 | 63 | 63 | 63 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||||
| Icu | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 50 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 50 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||||
| Ics | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 50 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 15 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 |
| ¬ No back-up fuse required. | ||||||||||||||
| Cat. No. 140M-D8E- | Cat. No. 140M-F8E- | |||||||||||||
| B25 | B40 | B63 | C10 | C16 | C20 | C25 | C10 | C16 | C20 | C25 | C32 | C45 | ||
| Rated Operational Current, Ie | [A] | 2.5 | 4.0 | 6.3 | 10 | 16 | 20 | 25 | 10 | 16 | 20 | 25 | 32 | 45 |
| Magnetic Release Current | [A] | 33 | 52 | 82 | 130 | 208 | 260 | 325 | 130 | 208 | 260 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | ||||||||||||||
| AC-2, AC-3 | ||||||||||||||
| 230/240V | [kW] | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 4.0/5.5 | — | 2.2 | 3.0/4.0 | 4.0/5.5 | 5.5/6.3 | 7.5 | 11/13 |
| 400/415V | [kW] | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 | 7.5/10 | 11 | 3.0/4.0 | 5.5/7.5 | 7.5/10 | 11 | 15 | 18.5/22 |
| 500V | [kW] | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 | 11 | 15 | 4.0/6.3 | 7.5/10 | 11 | 15 | 15/20 | 22/30 |
| 690V | [kW] | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 | 15/17 | 18.5/22 | 5.5/7.5 | 11/13 | 15/17 | 18.5/22 | 22/25 | 30/40 |
| Back-Up Fuses | ||||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 | 80 | 100 | 100 | 100 | 125 | 125 |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 | 80 | 100 | 100 | 100 | 125 | 125 |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | 80 | 100 | 100 | 80 | 100 | 100 | 100 | 125 | 125 |
| 690V | [A] | 20 | 35 | 50 | 50 | 63 | 63 | 63 | 63 | 80 | 80 | 80 | 100 | 100 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||||
| Icu | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 6 | 6 | 6 | 10 | 10 | 10 | 10 | 10 | 10 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||||
| Ics | ||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 4 | 4 | 4 | 10 | 10 | 10 | 10 | 6 | 6 |
| ¬ No back-up fuse required. | ||||||||||||||
| Cat. No. | 140-CMN-… | ||||
| -2500 | -4000 | -6300 | -9000 | ||
| Rated Operational Current, Ie | [A] | 25 | 40 | 63 | 90 |
| Magnetic Release Current | [A] | 350 | 560 | 890 | 1260 |
| Switching of Standard Three-Phase Motors | |||||
| AC-2, AC-3 | |||||
| 230/240VT | [kW] | 5.5/7.5 | 10/11 | 13/20 | 22/25 |
| 400/415VT | [kW] | 7.5/13 | 15/22 | 25/32 | 37/45 |
| 500VT | [kW] | 11/15 | 18.5/25 | 30/40 | 45/55 |
| 690VT | [kW] | 15/22 | 25/30 | 37/55 | 63/75 |
| Back-up fuses | |||||
| gG, gL,, only if Icc ³ Icu | |||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | 160 | 160 | 160 | 160 |
| 500V | [A] | 160 | 160 | 160 | 160 |
| 690V | [A] | 160 | 160 | 160 | 160 |
| Ultimate short-circuit breaking capacity Icu | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 65 | 65 | 65 | 50 |
| 500V | [kA] | 50 | 30 | 30 | 25 |
| 690V | [kA] | 15 | 8 | 8 | 6 |
| Rated service short-circuit breaking capacity Ics | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 65 | 50 | 50 | 25 |
| 500V | [kA] | 50 | 25 | 25 | 13 |
| 690V | [kA] | 15 | 8 | 6 | 6 |
| ¬ No back-up fuse required. | |||||
| T Power ratings: Preferred values according to IEC 60072-1. | |||||
IEC Performance Data, Continued
| Cat. No. 140M-C2N- | ||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1 | 1.6 | 2.5 |
| Magnetic Release Current | [A] | 2.1 | 3.3 | 5.2 | 8.2 | 13 | 21 | 32 |
| Switching of Standard Three-Phase Motors | ||||||||
| AC-2, AC-3 | ||||||||
| 230/240V | [kW] | — | — | — | 0.06/0.09 | 0.12 | 0.18/0.25 | 0.37 |
| 400/415V | [kW] | 0.02 | 0.06 | 0.09 | 0.12/0.18 | 0.25 | 0.37/0.55 | 0.75 |
| 500V | [kW] | — | — | — | 0.18 | 0.25/0.37 | 0.55/0.75 | 1.1 |
| 690V | [kW] | — | — | — | 0.25 | 0.37/0.55 | 0.75/1.1 | 1.8 |
| Back-Up Fuses | ||||||||
| gG, gL, only if Icc³Icu¬ | ||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 690V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 16 | 20 |
| Ultimate Short Circuit Breaking Capacity | ||||||||
| Icu | ||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 10 | 8 |
| Rated Service Short Circuit Breaking Capacity | ||||||||
| Ics | ||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 |
| ¬ No back-up fuse required. | ||||||||
| Cat. No. 140M-D8N- | Cat. No. 140M-F8N- | |||||||||
| B25 | B40 | B63 | C10 | C16 | C25 | C25 | C32 | C45 | ||
| Rated Operational Current, Ie | [A] | 2.5 | 4.0 | 6.3 | 10 | 16 | 25 | 25 | 32 | 45 |
| Magnetic Release Current | [A] | 32 | 52 | 82 | 130 | 208 | 325 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | ||||||||||
| AC-2, AC-3 | ||||||||||
| 230/240V | [kW] | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | — | 5.5/6.3 | 7.5 | 11/13 |
| 400/415V | [kW] | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 | 11 | 11 | 15 | 18.5/22 |
| 500V | [kW] | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 | 15 | 15 | 15/20 | 22/30 |
| 690V | [kW] | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 | 18.5/22 | 18.5/22 | 22/25 | 30/40 |
| Back-Up Fuses | ||||||||||
| gG, gL, only if Icc³Icu | ||||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 125 | 125 |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 100 | 100 | 125 | 125 |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | 80 | 100 | 100 | 125 | 125 |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | 80 | 80 | 100 | 125 | 125 |
| 690V | [A] | 20 | 35 | 50 | 50 | 63 | 63 | 80 | 100 | 100 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||
| Icu | ||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 50 | 65 | 65 | 65 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 50 | 65 | 65 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 6 | 6 | 10 | 10 | 10 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||
| Ics | ||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 4 | 4 | 10 | 6 | 6 |
| ¬ No back-up fuse required. | ||||||||||
| Cat. No. 140M-C2T- | ||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.40 | 0.63 | 1.0 | 1.6 | 2.5 | 4.0 | 6.3 | 10 | 16 |
| Magnetic Release Current | [A] | 3.2 | 5.2 | 8.2 | 13 | 21 | 32 | 52 | 82 | 130 | 208 | 260 |
| Switching of Standard Three-Phase Motors | ||||||||||||
| AC-2, AC-3 | ||||||||||||
| 230/240V | [kW] | — | — | — | 0.06/0.09 | 0.12 | 0.18/0.25 | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 |
| 400/415V | [kW] | 0.02 | 0.06 | 0.09 | 0.12/0.18 | 0.25 | 0.37/0.55 | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 |
| 500V | [kW] | — | — | — | 0.18 | 0.25/0.37 | 0.55/0.75 | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 |
| 690V | [kW] | — | — | — | 0.25 | 0.37/0.55 | 0.75/1.1 | 1.8 | 2.2/3.0 | 4.0 | 5.5/7.5 | 11/13 |
| Back-Up Fuses | ||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 |
| 440/460V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 |
| 500V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | ¬ | 80 | 80 |
| 690V | [A] | ¬ | ¬ | ¬ | ¬ | ¬ | 16 | 20 | 35 | 50 | 50 | 63 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||
| Icu | ||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||
| Ics | ||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 |
| ¬ No back-up fuse required. | ||||||||||||
| Cat. No. 140M-D8T- | Cat. No. 140M-F8T- | ||||
| C16 | C20 | C25 | C32 | ||
| Rated Operational Current, Ie | [A] | 16 | 20 | 25 | 32 |
| Magnetic Release Current | [A] | 260 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | |||||
| AC-2, AC-3 | |||||
| 230/240V T | [kW] | 3.0/4.0 | 4.0/5.5 | 5.5/6.3 | 7.5 |
| 400/415V T | [kW] | 5.5/7.5 | 7.5/10 | 11 | 15 |
| 500V T | [kW] | 7.5/10 | 11 | 15 | 15/20 |
| 690V T | [kW] | 11/13 | 15/17 | 18.5/22 | 22/25 |
| Back-up fuses | |||||
| gG, gL,, only if Icc ³ Icu | |||||
| 230/240V | [A] | ¬ | ¬ | ¬ | ¬ |
| 400/415V | [A] | 80 | 100 | 100 | 125 |
| 440/460V | [A] | 80 | 100 | 100 | 125 |
| 500V | [A] | 80 | 80 | 100 | 125 |
| 690V | [A] | 63 | 63 | 80 | 100 |
| Ultimate short-circuit breaking capacity | |||||
| Icu | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 65 | 65 | 65 | 65 |
| 440/460V | [kA] | 65 | 65 | 65 | 65 |
| 500V | [kA] | 50 | 25 | 50 | 50 |
| 690V | [kA] | 6 | 6 | 10 | 10 |
| Rated service short-circuit breaking capacity Ics | |||||
| Ics | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 25 | 25 | 50 | 50 |
| 440/460V | [kA] | 25 | 25 | 50 | 50 |
| 500V | [kA] | 25 | 25 | 50 | 50 |
| 690V | [kA] | 4 | 4 | 6 | 6 |
| ¬ No back-up fuse required. | |||||
| T Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||
| Cat. No. | 140M-C | 140M-D | 140M-F | 140-CMN | |
| Rated Insulation Voltage Ui | |||||
| IEC, SEV, VDE 0660 | [V] | 690 | 690 | ||
| UL, CSA | [V] | 600 | 600 | ||
| Rated Impulse Withstand Voltage Uimp | |||||
| Pollution degree | 3 | 3 | |||
| Main circuits Uimp /Overvoltage Category | 6 kV/III | 6 kV/III | |||
| Auxiliary circuits Uimp /Overvoltage Category | 6 kV/III | 6 kV/III | |||
| Rated Frequency | [Hz] | 50/60 | 40…60 | ||
| Utilization Category | |||||
| IEC 60947-2 (Circuit breaker) | A | A | |||
| IEC 60947-4-1 (Motor starter) | AC-3 | AC-3 | |||
| Life Span | |||||
| Mechanical | [operations] | 100 000 | 30 000 | 30 000 | |
| Electrical (Ie max.) | [operations] | 100 000 | 30 000 | 10 000 (up to 63 A) 5 000 (up to 90 A) |
|
| Switching Frequency | [operations/h] | max. 25 (motor starts) | max. 20 | ||
| Ambient Temperature | |||||
| Storage | [°C] | -40 … +80 | -25… +80 | ||
| Operation | [°C] | -25… +60 | |||
| Resistance to Climatic Change | IEC 68-2 | C IV (acc. to IEC 68) | |||
| Moisture/heat resistance | 40 °C, 92% relative humidity, 56 days | ||||
| Moisture/change resistance | 23 °C, 83%/40 °C, 92%, 50 cycles | ||||
| Site Altitude | [m] | to 2000 N.N. | |||
| Protection Class | IP20, when wired | ||||
| Resistance to Shock | [g] | 30, 11 ms | 30, 11 ms | ||
| Resistance to Vibration | IEC 68-2 | ||||
| Frequency range | [Hz] | 10…150 | |||
| in all directions | [g] | under testing | |||
| Rated Thermal Current Ith | |||||
| IEC, SEV, VDE 0660 | |||||
| up to 40 °C ambient temperature | [A] | 0.1…25 | 1.6…25 | 6.3…45 | 16… 90 |
| up to 60 °C ambient temperature | [A] | 0.1…25 | 1.6…25 | 6.3…45 | 16… 90 |
| Rated Supply Current Ie | [A] | 0.1…25 | 1.6…25 | 6.3…45 | 16… 90 |
| Number of setting ranges | 13 | 7 | 6 | 4 | |
| Dependence on Temperature | |||||
| 40 °C | [A] | no reduction | |||
| 50 °C | [A] | no reduction | |||
| 60 °C | [A] | no reduction | |||
| 70 °C | [A] | 15 % current reduction of the upper rated current Ie | |||
| Overload Protection | |||||
| Characteristics | IEC 60947-4-1 Motor protection (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) |
IEC 60947-4-1 Motor protection | |||
| Ambient Temperature Compensation | [°C] | -20 …+60 | |||
| Phase-loss Protection | Differential release | ||||
| Trip class | 10 (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) fixed setting | 10 | |||
| Magnetic Release Release current |
fixed setting 13 x Ie max. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N) 16…20 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T) Ie max. = maximum values of setting ranges |
fixed setting 14 x Ie max. |
|||
| Total Power loss Pv | |||||
| Circuit Breaker at rated load operating temperature | [W] | 6…8 | 6…8 | 9…16 | 33 |
| Main Circuit Breaker Application | Usable as main circuit breaker according to IEC 204 with corresponding accessories | ||||
General Data, Continued
Accessories for Bulletin 140M Motor Protection Circuit Breakers
Weights
| Description | Weight [g] | Cat.No. |
| Motor Protection Circuit Breakers | 317 | 140M-C2E-… |
| 373 | 140M-D8E-… | |
| 782 | 140M-F8E-… | |
| 315 | 140M-C2N-… | |
| 365 | 140M-D8N-… | |
| 782 | 140M-F8N-… | |
| 315 | 140M-C2T-… | |
| 365 | 140M-D8T-… | |
| 782 | 140M-F8T-… | |
| 1845 | 140-CMN-… | |
| Auxiliary Contacts | 10 | 140M-C-AFA10 |
| 140M-C-AFA01 | ||
| 140M-C-AFA11 | ||
| 140M-C-AFA20 | ||
| 140M-C-ASA… | ||
| 15 | 140M-C-AFAR10A… | |
| 140M-C-ASAR…M… | ||
| 140M-C-ASAM11 | ||
| 31 | 140-CA… | |
| Undervoltage Trip | 108 | 140M-C-UX… |
| 110 | 140M-C-SN… | |
| 116 | 140M-C-UC… | |
| 94 | 140-CUV… | |
| Trip Contact Blocks | 31 | 140-CT… |
| Shunt Trip | 94 | 140-CRT… |
| ` | Weight [g] | Cat.No. |
| Anti-Tamper Cover | 2 | 140M-C-CA |
| Lockable Twist Knob | 5 | 140M-C-KN |
| 140M-C-KRY | ||
| Locking Tag | 30 | 140M-C-M3 |
| Door Coupling Handle | 123 | 140M-C-DN66 |
| 140M-C-NRY66 | ||
| Extension Shaft | 46 | 140M-C-DS |
| Legend Plate | 4 | 140M-C-DFC… |
| Feeder Terminal | 172 | 140M-C-WT |
| 140M-F-WT | ||
| Commoning Links | 47 | 140M-C-W452 |
| 80 | 140M-C-W453 | |
| 104 | 140M-C-W454 | |
| 132 | 140M-C-W455 | |
| 52 | 140M-C-W542 | |
| 86 | 140M-C-W543 | |
| 118 | 140M-C-W544 | |
| 154 | 140M-C-W545 | |
| 56 | 140M-C-W632 | |
| 92 | 140M-C-W633 | |
| 134 | 140M-C-W634 | |
| 170 | 140M-C-W635 | |
Accessories for Bulletin 140-CMN Circuit Breakers
Cut-off current
|
The Bulletin 140-M limits solid short-circuit current Icc (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system short-circuit current.
Bulletin 140M-C Circuit Breaker
Maximum cut-off current
|
Maximum forward energy
|
Bulletin 140M-D Circuit Breaker
Maximum cut-off current
|
Maximum cut-off current
|
Bulletin 140M-F Circuit Breaker
Maximum cut-off current
|
Maximum cut-off current
|
Time-Current Characteristic
Bulletin 140M-C, -D, -F Motor Protection Circuit Breakers
|
Bulletin 140-CMN Motor Protector
|
1) Thermal Release Trip Current
The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20 °C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single-phasing. The overload characteristic is also valid for transformer protection.
2) Magnetic Release Trip Current
The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13 times the maximum value of setting range. (Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher.
Current Setting IeF
The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC947-4-1. If a different value is prescribed (e.g., reduced Ie for cooling medium having a temperature higher than 40 °C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current Ie of the motor.