Motor Protection Circuit Breakers and Motor Circuit Protectors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Motor Protection Circuit Breakers and Motor Circuit Protectors > Bulletin 140M Motor Circuit Protectors

Bulletin 140M Motor Circuit Protectors

Introduction Standards Compliance and Certifications Cat. No. Explanation Wiring Diagrams Product Selection
Application Ratings Accessories Specifications Approximate Dimensions
Specifications

IEC Performance Data

  Cat. No. 140M-C2E-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 C25
Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325
Switching of Standard Three-Phase Motors
AC-2, AC-3
230/240V [kW] 0.06/0.09 0.12 0.18/0.25 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 4.0/5.5
400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 7.5/10 11
500V [kW] 0.18 0.25/0.37 0.55/0.75 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 11 15
690V [kW] 0.25 0.37/0.55 0.75/1.1 1.8 2.2/3.0 4.0 5.5/7.5 11/13 15/17 18.5/22
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  100 100
400/415V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  80 100 100
440/460V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  80 80 80
500V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  80 80 80 80
690V [A] ¬  ¬  ¬  ¬  ¬  16 20 35 50 50 63 63 63
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 65 50 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3
  
¬ No back-up fuse required.

  Cat. No. 140M-D8E- Cat. No. 140M-F8E-
B25 B40 B63 C10 C16 C20 C25 C10 C16 C20 C25 C32 C45
Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 20 25 10 16 20 25 32 45
Magnetic Release Current [A] 33 52 82 130 208 260 325 130 208 260 325 416 585
Switching of Standard Three-Phase Motors
AC-2, AC-3
230/240V [kW] 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 4.0/5.5 2.2 3.0/4.0 4.0/5.5 5.5/6.3 7.5 11/13
400/415V [kW] 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 7.5/10 11 3.0/4.0 5.5/7.5 7.5/10 11 15 18.5/22
500V [kW] 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 11 15 4.0/6.3 7.5/10 11 15 15/20 22/30
690V [kW] 1.8 2.2/3.0 4.0 5.5/7.5 11/13 15/17 18.5/22 5.5/7.5 11/13 15/17 18.5/22 22/25 30/40
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬ 
400/415V [A] ¬  ¬  ¬  ¬  ¬  100 100 80 100 100 100 125 125
440/460V [A] ¬  ¬  ¬  ¬  ¬  100 100 80 100 100 100 125 125
500V [A] ¬  ¬  ¬  ¬  80 100 100 80 100 100 100 125 125
690V [A] 20 35 50 50 63 63 63 63 80 80 80 100 100
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 65 65 65 65 65 65 65 65
440/460V [kA] 100 100 100 100 65 65 65 65 65 65 65 65 50
500V [kA] 100 100 100 100 50 50 50 50 50 50 50 50 50
690V [kA] 10 10 10 6 6 6 6 10 10 10 10 10 10
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50
440/460V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50
500V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50
690V [kA] 10 10 10 6 4 4 4 10 10 10 10 6 6
  
¬ No back-up fuse required.

Cat. No. 140-CMN-…
-2500 -4000 -6300 -9000
Rated Operational Current, Ie [A] 25 40 63 90
Magnetic Release Current [A] 350 560 890 1260
Switching of Standard Three-Phase Motors
AC-2, AC-3
230/240VT  [kW] 5.5/7.5 10/11 13/20 22/25
400/415VT  [kW] 7.5/13 15/22 25/32 37/45
500VT  [kW] 11/15 18.5/25 30/40 45/55
690VT  [kW] 15/22 25/30 37/55 63/75
Back-up fuses
gG, gL,, only if Icc ³ Icu
230/240V [A] ¬  ¬  ¬  ¬ 
400/415V [A] 160 160 160 160
500V [A] 160 160 160 160
690V [A] 160 160 160 160
Ultimate short-circuit breaking capacity Icu
230/240V [kA] 100 100 100 100
400/415V [kA] 65 65 65 50
500V [kA] 50 30 30 25
690V [kA] 15 8 8 6
Rated service short-circuit breaking capacity Ics
230/240V [kA] 100 100 100 100
400/415V [kA] 65 50 50 25
500V [kA] 50 25 25 13
690V [kA] 15 8 6 6
  
¬ No back-up fuse required.
T Power ratings: Preferred values according to IEC 60072-1.

IEC Performance Data, Continued

  Cat. No. 140M-C2N-
A16 A25 A40 A63 B10 B16 B25
Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 32
Switching of Standard Three-Phase Motors
AC-2, AC-3
230/240V [kW] 0.06/0.09 0.12 0.18/0.25 0.37
400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75
500V [kW] 0.18 0.25/0.37 0.55/0.75 1.1
690V [kW] 0.25 0.37/0.55 0.75/1.1 1.8
Back-Up Fuses
gG, gL, only if Icc³Icu¬ 
230/240V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬ 
400/415V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬ 
440/460V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬ 
500V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬ 
690V [A] ¬  ¬  ¬  ¬  ¬  16 20
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 10 8
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 8 8
  
¬ No back-up fuse required.

  Cat. No. 140M-D8N- Cat. No. 140M-F8N-
B25 B40 B63 C10 C16 C25 C25 C32 C45
Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 25 25 32 45
Magnetic Release Current [A] 32 52 82 130 208 325 325 416 585
Switching of Standard Three-Phase Motors
AC-2, AC-3
230/240V [kW] 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 5.5/6.3 7.5 11/13
400/415V [kW] 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 11 11 15 18.5/22
500V [kW] 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 15 15 15/20 22/30
690V [kW] 1.8 2.2/3.0 4.0 5.5/7.5 11/13 18.5/22 18.5/22 22/25 30/40
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ¬  ¬  ¬  ¬  ¬  ¬  100 125 125
400/415V [A] ¬  ¬  ¬  ¬  ¬  100 100 125 125
440/460V [A] ¬  ¬  ¬  ¬  80 100 100 125 125
500V [A] ¬  ¬  ¬  ¬  80 80 100 125 125
690V [A] 20 35 50 50 63 63 80 100 100
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 50 65 65 65
440/460V [kA] 100 100 100 100 50 50 65 65 50
500V [kA] 100 100 100 100 50 25 50 50 50
690V [kA] 10 10 10 6 6 6 10 10 10
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 50 25 50 50 50
440/460V [kA] 100 100 100 100 50 25 50 50 50
500V [kA] 100 100 100 100 50 25 50 50 50
690V [kA] 10 10 10 6 4 4 10 6 6
  
¬ No back-up fuse required.

  Cat. No. 140M-C2T-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16
Rated Operational Current, Ie [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 10 16
Magnetic Release Current [A] 3.2 5.2 8.2 13 21 32 52 82 130 208 260
Switching of Standard Three-Phase Motors
AC-2, AC-3
230/240V [kW] 0.06/0.09 0.12 0.18/0.25 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0
400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5
500V [kW] 0.18 0.25/0.37 0.55/0.75 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10
690V [kW] 0.25 0.37/0.55 0.75/1.1 1.8 2.2/3.0 4.0 5.5/7.5 11/13
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬ 
400/415V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  80
440/460V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  80
500V [A] ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  ¬  80 80
690V [A] ¬  ¬  ¬  ¬  ¬  16 20 35 50 50 63
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10
500V [kA] 100 100 100 100 100 100 100 100 100 50 10
690V [kA] 100 100 100 100 100 8 8 8 4 4 3
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3
  
¬ No back-up fuse required.

  Cat. No. 140M-D8T- Cat. No. 140M-F8T-
C16 C20 C25 C32
Rated Operational Current, Ie [A] 16 20 25 32
Magnetic Release Current [A] 260 325 416 585
Switching of Standard Three-Phase Motors
AC-2, AC-3
230/240V T  [kW] 3.0/4.0 4.0/5.5 5.5/6.3 7.5
400/415V T  [kW] 5.5/7.5 7.5/10 11 15
500V T  [kW] 7.5/10 11 15 15/20
690V T  [kW] 11/13 15/17 18.5/22 22/25
Back-up fuses
gG, gL,, only if Icc ³ Icu
230/240V [A] ¬  ¬  ¬  ¬ 
400/415V [A] 80 100 100 125
440/460V [A] 80 100 100 125
500V [A] 80 80 100 125
690V [A] 63 63 80 100
Ultimate short-circuit breaking capacity
Icu
230/240V [kA] 100 100 100 100
400/415V [kA] 65 65 65 65
440/460V [kA] 65 65 65 65
500V [kA] 50 25 50 50
690V [kA] 6 6 10 10
Rated service short-circuit breaking capacity Ics
Ics
230/240V [kA] 100 100 100 100
400/415V [kA] 25 25 50 50
440/460V [kA] 25 25 50 50
500V [kA] 25 25 50 50
690V [kA] 4 4 6 6
  
¬ No back-up fuse required.
T Consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Cat. No. 140M-C 140M-D 140M-F 140-CMN
Rated Insulation Voltage Ui
IEC, SEV, VDE 0660 [V] 690 690
UL, CSA [V] 600 600
Rated Impulse Withstand Voltage Uimp
Pollution degree 3 3
Main circuits Uimp /Overvoltage Category 6 kV/III 6 kV/III
Auxiliary circuits Uimp /Overvoltage Category 6 kV/III 6 kV/III
Rated Frequency [Hz] 50/60 40…60
Utilization Category
IEC 60947-2 (Circuit breaker) A A
IEC 60947-4-1 (Motor starter) AC-3 AC-3
Life Span
Mechanical [operations] 100 000 30 000 30 000
Electrical (Ie max.) [operations] 100 000 30 000 10 000 (up to 63 A)
5 000 (up to 90 A)
Switching Frequency [operations/h] max. 25 (motor starts) max. 20
Ambient Temperature
Storage [°C] -40 … +80 -25… +80
Operation [°C] -25… +60
Resistance to Climatic Change IEC 68-2 C IV (acc. to IEC 68)
Moisture/heat resistance 40 °C, 92% relative humidity, 56 days
Moisture/change resistance 23 °C, 83%/40 °C, 92%, 50 cycles
Site Altitude [m] to 2000 N.N.  
Protection Class IP20, when wired  
Resistance to Shock [g] 30, 11 ms 30, 11 ms
Resistance to Vibration IEC 68-2  
Frequency range [Hz]   10…150
in all directions [g]   under testing
Rated Thermal Current Ith
IEC, SEV, VDE 0660        
up to 40 °C ambient temperature [A] 0.1…25 1.6…25 6.3…45 16… 90
up to 60 °C ambient temperature [A] 0.1…25 1.6…25 6.3…45 16… 90
Rated Supply Current Ie [A] 0.1…25 1.6…25 6.3…45 16… 90
Number of setting ranges 13 7 6 4
Dependence on Temperature
40 °C [A] no reduction
50 °C [A] no reduction
60 °C [A] no reduction
70 °C [A] 15 % current reduction of the upper rated current Ie
Overload Protection
Characteristics IEC 60947-4-1 Motor protection
(except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N)
IEC 60947-4-1 Motor protection
Ambient Temperature Compensation [°C] -20 …+60
Phase-loss Protection Differential release
Trip class 10 (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) fixed setting 10
Magnetic Release
Release current
fixed setting
13 x Ie max. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N)
16…20 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T)
Ie max. = maximum values of setting ranges
fixed setting
14 x Ie max.
Total Power loss Pv
Circuit Breaker at rated load operating temperature [W] 6…8 6…8 9…16 33
Main Circuit Breaker Application Usable as main circuit breaker according to IEC 204 with corresponding accessories
  

General Data, Continued

Cat. No. 140M-C… 140M-D… 140M-F… 140-CMN
Conformity to Standards IEC 60947-1; -2; -4-1;
EN 60947-1; -2; -4-1;
UL 508; CSA 22.2, No. 14
IEC 60947-1; -2; -4-1;
EN 60947-1; -2; -4-1;
UL 508; CSA 22.2, No. 14
Approvals CE, UL, CSA CE, UL, CSA
Terminal Parts
    Type of terminals
Click to enlarge - 140M-29-1 Click to enlarge - 140M-29-2 Click to enlarge - 140M-29-3
Screwdriver Pozidriv No. 2/Blade No. 3 Pozidriv No. 2/Blade No. 3
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1…4/No. 16…10
1…4/No. 16…10
2.5…16/No. 14…4
2.5…10/No. 14…4
2.5…35
Click to enlarge - 140M-29-5 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1.5…6/No. 16…8
1.5…6/No. 16…8
2.5…16/No. 14…4
2.5…10/No. 14…4
4…50 / 12…2
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1…6/No. 16…10
1…6/No. 16…10
2.5…25/No. 14…4
2.5…16/No. 14…4
4…50 / 12…2
Tightening torque [Nm]/[lb•in] 2…2.5/18…22 3…3.5/27…30 6…10/55…90
  

Accessories for Bulletin 140M Motor Protection Circuit Breakers

  Auxiliary Contact Blocks for
Front Mounting
Cat. No. 140M-C-AFA…, 140M-C-AFAR…
Auxiliary Contact Blocks for
Right-Side Mounting
Cat. No. 140M-C-ASA…, 140M-C-ASAR…
Rated Thermal Current Ith
at 40 °C ambient temperature
at 60 °C ambient temperature

[A]
[A]

5
4

10
6
Contact Class Coordination
According to NEMA
   
(UL/CSA Standards)
AC
DC
B 300
Q 300
B 600
Q 600
Back-Up Fuses gG, gL [A] 10 10
Rated Supply Current [V] 24 120 240 24 120 240 415 690
  AC-15 [A] 4 3 1.5 6 5 3 2 0.7
  DC-13 [V] 24 120 240 24 120 240 415  
  [A] 2 0.5 0.25 2 0.5 0.25 0.15  
Terminal Parts
    Type of terminals
Click to enlarge - 140M-29-1
Screwdriver Pozidriv No. 2/Blade No. 3
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.5…1.5/18…14
0.75…1.5/18…14
0.5…2.5/18…14
0.75…2.5/18…14
Click to enlarge - 140M-29-5 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…1.5/18…14
0.75…1.5/18…14
0.75…2.5/18…14
0.75…2.5/18…14
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…1.5/18…14
0.75…1.5/18…14
0.75…2.5/18…14
0.75…2.5/18…14
Tightening torque [N•m]/[lb•in] 1.2…1.5/10.6…13 1.2…1.5/10.6…13
  

  Undervoltage Trip
for Left-Side Mounting
Cat. No. 140M-C-UX…
Undervoltage Trip
with 2 Auxiliary Contacts
for Left-Side Mounting
Cat. No. 140M-C-UC…
Shunt Trip
for Left-Side Mounting
Cat. No. 140M-C-SN…
Actuating Voltage      
Pull-in
Drop-out
0.85…1.1 x Us
0.7…0.35 x Us
0.85…1.1 x Us
0.7…0.35 x Us
0.7…1.1 x Us
Rated Control Voltage
min.
max.
21V 50 Hz, 24V 60 Hz
600V 50 Hz
21V 50 Hz, 24V 60 Hz
600V 50 Hz
21V 50 Hz, 24V 60 Hz
600V 50 Hz
On-Time 100% 100% 100%
Coil Rating
Pull-in
Hold
8.5 VA, 6 W
3 VA, 1.2 W
8.5 VA, 6 W
3 VA, 1.2 W
8.5 VA, 6 W
3 VA, 1.2 W
Terminal Parts
    Type of terminals
Click to enlarge - 140M-29-1
Screwdriver Pozidriv No. 2/Blade No. 3
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.5…2.5/No. 18…14
0.75…2.5/No. 18…14
Click to enlarge - 140M-29-5 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
Tightening torque [N•m]/[lb•in] 1.2…1.5/10.6…13.3
  

  Commoning Link Feeder Terminal 140M-C-WTE Commoning Link
Rated Thermal Current Ith
at 60 °C ambient temperature
  140M-C-WTE 140M-F-WTE 140M-C-W 140M-F-W
[A] 64 120 64 120
Click to enlarge - 140M-29-4 1. conductor [mm2]/[AWG] 1.5…16
Click to enlarge - 140M-29-5 1. conductor [mm2]/[AWG] 1.5…25/No. 14…4 4…50/12…1/0
Click to enlarge - 140M-29-6 1. conductor [mm2]/[AWG] 1.5…25/No. 14…4 2.5…50/12…1/0
Tightening torque [N•m]/[lb•in] 3/27 5…6/45…54
  

Weights

Description Weight [g] Cat.No.
Motor Protection Circuit Breakers 317 140M-C2E-…
373 140M-D8E-…
782 140M-F8E-…
315 140M-C2N-…
365 140M-D8N-…
782 140M-F8N-…
315 140M-C2T-…
365 140M-D8T-…
782 140M-F8T-…
1845 140-CMN-…
Auxiliary Contacts 10 140M-C-AFA10
140M-C-AFA01
140M-C-AFA11
140M-C-AFA20
140M-C-ASA…
15 140M-C-AFAR10A…
140M-C-ASAR…M…
140M-C-ASAM11
31 140-CA…
Undervoltage Trip 108 140M-C-UX…
110 140M-C-SN…
116 140M-C-UC…
94 140-CUV…
Trip Contact Blocks 31 140-CT…
Shunt Trip 94 140-CRT…
  

` Weight [g] Cat.No.
Anti-Tamper Cover 2 140M-C-CA
Lockable Twist Knob 5 140M-C-KN
140M-C-KRY
Locking Tag 30 140M-C-M3
Door Coupling Handle 123 140M-C-DN66
140M-C-NRY66
Extension Shaft 46 140M-C-DS
Legend Plate 4 140M-C-DFC…
Feeder Terminal 172 140M-C-WT
140M-F-WT
Commoning Links 47 140M-C-W452
80 140M-C-W453
104 140M-C-W454
132 140M-C-W455
52 140M-C-W542
86 140M-C-W543
118 140M-C-W544
154 140M-C-W545
56 140M-C-W632
92 140M-C-W633
134 140M-C-W634
170 140M-C-W635
  

Accessories for Bulletin 140-CMN Circuit Breakers

  Cat. No. 140-CT
Trip Contact Block for Flush Mounting on Cat.
No. 140-CMN Circuit Breakers
Cat. No. 140-CRT, 140-CUV
Undervoltage Trip and Shunt Trip for Flush Mounting on
Cat. No. 140-CMN Circuit Breakers
Rated Thermal Current Ith
up to 40 °C ambient temperature
up to 60 °C ambient temperature

[A]
[A]

10
6
2
2
NEMA contact class
(UL/CSA-Approval)

AC
DC

B 600 Standard Pilot Duty
R 300 Light Pilot Duty
Make/Break max. voltage
432 VA72 VA480 V
28 VA28 VA250 V
Back-Up Fuse gG, gL 16 A 16 A
Rated Current Ie                      
AC-15: [V]
[A]
230
3
400
2.5
500
1.5
690
0.75
  AC-14: 24
1.5
110
1.5
230
1.0
400
1.0
500
0.75
DC-13: [V]
[A]
24
2
48
0.6
110
0.2
230
0.1
440
0.04
DC 13: 24
1.5
48
0.5
60
0.4
110
0.2
 
Terminals Click to enlarge - 140M-29-1 Click to enlarge - 140M-29-1
Screwdriver    
Click to enlarge - 140M-29-4 1.conductor
2.conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
Click to enlarge - 140M-29-5 1.conductor
2.conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
Tightening torque [N•m]/[lb•in] 1… 1.5/8.8… 10.3 1… 1.5/8.8… 10.3
  

  Cat. No. 140-CUV…
Undervoltage Trip Unit for Right-Side Mounting on
Cat. No. 140-CMN Circuit Breakers
Cat. No. 140-CRT...
Shunt Trip for Flush Mounting on
Cat. No. 140-CMN Circuit Breakers
Operating Voltage    
Pick-up 0.8… 1.1 x Us 0.7… 1.1 x Us
Drop-out 0.7… 0.35 x Us
Duty cycle 100 % ED 100 % ED
Control Voltage    
  min. 12 V 50 Hz/14 V 60 Hz 12 V 50 Hz/14 V 60 Hz
    max. 600 V 50 Hz 600 V 50 Hz
Coil Performance    
Pick-up
Drop-out
[VA/W]
[VA/W]
11 / 8
4 / 1
12 / 7
6 / 2
Terminals
Terminal type
Click to enlarge - 140M-29-1 Click to enlarge - 140M-29-1
Click to enlarge - 140M-29-4 Fine-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5
Click to enlarge - 140M-29-5 Coarse-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5
Tightening torque [Nm] 1… 1.5 1… 1.5
Click to enlarge - 140M-29-5 Coarse-stranded [AWG] No. 18…. 14 No. 18…. 12
Tightening torque [lb•in] 8.8… 10.3 8.8… 10.3
  

Cut-off current

Click to enlarge - 140M-32-1
asymmetrical
symmetrical


The Bulletin 140-M limits solid short-circuit current Icc (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system short-circuit current.

Bulletin 140M-C Circuit Breaker

Maximum cut-off current

Click to enlarge - 140M-32-2


Maximum forward energy

Click to enlarge - 140M-32-3


Bulletin 140M-D Circuit Breaker

Maximum cut-off current

Click to enlarge - 140M-33-1


Maximum cut-off current

Click to enlarge - 140M-33-2


Bulletin 140M-F Circuit Breaker

Maximum cut-off current

Click to enlarge - 140M-33-3


Maximum cut-off current

Click to enlarge - 140M-33-4


Time-Current Characteristic

Bulletin 140M-C, -D, -F Motor Protection Circuit Breakers

Click to enlarge - 140M-C_D19_EN


Bulletin 140-CMN Motor Protector

Click to enlarge - 140M-34-1


1) Thermal Release Trip Current

The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20 °C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single-phasing. The overload characteristic is also valid for transformer protection.

2) Magnetic Release Trip Current

The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13 times the maximum value of setting range. (Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher.

Current Setting IeF

The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC947-4-1. If a different value is prescribed (e.g., reduced Ie for cooling medium having a temperature higher than 40 °C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current Ie of the motor.