Cat. No. 140M-C2E-
|
| A16
|
A25
|
A40
|
A63
|
B10
|
B16
|
B25
|
B40
|
B63
|
C10
|
C16
|
C20
|
C25
|
C29
|
C32
|
| Rated Operational Current, Ie
|
[A]
|
0.16
|
0.25
|
0.4
|
0.63
|
1
|
1.6
|
2.5
|
4
|
6.3
|
10
|
16
|
20
|
25
|
29
|
32
|
| Magnetic Release Current
|
[A]
|
2.1
|
3.3
|
5.2
|
8.2
|
13
|
21
|
33
|
52
|
82
|
130
|
208
|
260
|
325
|
406
|
448
|
| Switching of Standard Three-Phase Motors
|
| AC-3
|
| 230/240V
|
[kW]
|
—
|
—
|
0.06
|
0.09
|
0.18
|
0.25
|
0.37
|
0.75
|
1.5
|
2.2
|
4.0
|
5.5
|
5.5
|
7.5
|
7.5
|
| 400/415V
|
[kW]
|
0.02
|
0.04
|
0.09
|
0.18
|
0.25
|
0.55
|
0.75
|
1.5
|
2.2
|
4.0
|
7.5
|
10
|
11
|
13
|
15
|
| 500V
|
[kW]
|
0.06
|
0.09
|
0.12
|
0.18
|
0.37
|
0.75
|
1.1
|
2.2
|
3.0
|
6.3
|
10
|
11
|
15
|
18.5
|
20
|
| 690V
|
[kW]
|
0.06
|
0.09
|
0.18
|
0.25
|
0.55
|
1.1
|
1.8
|
3.0
|
4.0
|
7.5
|
13
|
17
|
22
|
25
|
25
|
| Back-Up Fuses
|
| gG, gL, only if Icc³Icu
|
| 230/240V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
100
|
100
|
125
|
125
|
| 400/415V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
100
|
100
|
125
|
125
|
| 440/460V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
63
|
80
|
80
|
80
|
100
|
100
|
| 500V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
80
|
80
|
80
|
100
|
100
|
| 690V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
16
|
20
|
35
|
50
|
50
|
63
|
63
|
63
|
80
|
80
|
| Ultimate Short Circuit Breaking Capacity
|
| Icu
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
65
|
65
|
50
|
50
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
65
|
50
|
15
|
15
|
15
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
10
|
6
|
6
|
6
|
6
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
10
|
6
|
6
|
6
|
6
|
| 690V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
8
|
8
|
8
|
4
|
4
|
3
|
3
|
3
|
3
|
3
|
| Rated Service Short Circuit Breaking Capacity
|
| Ics
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
50
|
25
|
25
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
15
|
15
|
15
|
15
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
6
|
6
|
6
|
6
|
6
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
6
|
6
|
6
|
6
|
6
|
| 690V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
8
|
8
|
8
|
4
|
4
|
3
|
3
|
3
|
3
|
3
|
|
|
| ⋆ No back-up fuse required.
|
|
|
Cat. No. 140M-D8E-
|
Cat. No. 140M-F8E-
|
| B25
|
B40
|
B63
|
C10
|
C16
|
C20
|
C25
|
C29
|
C32
|
C10
|
C16
|
C20
|
C25
|
C32
|
C45
|
| Rated Operational Current, Ie
|
[A]
|
2.5
|
4.0
|
6.3
|
10
|
16
|
20
|
25
|
29
|
32
|
10
|
16
|
20
|
25
|
32
|
45
|
| Magnetic Release Current
|
[A]
|
33
|
52
|
82
|
130
|
208
|
260
|
325
|
406
|
448
|
130
|
208
|
260
|
325
|
416
|
585
|
| Switching of Standard Three-Phase Motors
|
| AC-3
|
| 230/240V
|
[kW]
|
0.37
|
0.75
|
1.5
|
2.2
|
4.0
|
5.5
|
5.5
|
7.5
|
7.5
|
2.2
|
4.0
|
5.5
|
6.3
|
7.5
|
13
|
| 400/415V
|
[kW]
|
0.75
|
1.5
|
2.2
|
4.0
|
7.5
|
10
|
11
|
13
|
15
|
4.0
|
7.5
|
10
|
11
|
15
|
22
|
| 500V
|
[kW]
|
1.1
|
2.2
|
3.0
|
6.3
|
10
|
11
|
15
|
18.5
|
20
|
6.3
|
10
|
11
|
15
|
20
|
30
|
| 690V
|
[kW]
|
1.8
|
3.0
|
4.0
|
7.5
|
13
|
17
|
22
|
25
|
25
|
7.5
|
13
|
17
|
22
|
30
|
40
|
| Back-Up Fuses
|
| gG, gL, only if Icc³Icu
|
| 230/240V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
| 400/415V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
100
|
100
|
125
|
125
|
80
|
100
|
100
|
100
|
125
|
125
|
| 440/460V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
100
|
100
|
125
|
125
|
80
|
100
|
100
|
100
|
125
|
125
|
| 500V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
80
|
80
|
100
|
100
|
80
|
100
|
100
|
100
|
125
|
125
|
| 690V
|
[A]
|
20
|
35
|
50
|
50
|
63
|
63
|
63
|
80
|
80
|
63
|
80
|
80
|
80
|
100
|
100
|
| Ultimate Short Circuit Breaking Capacity
|
| Icu
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
65
|
65
|
100
|
100
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
65
|
50
|
50
|
100
|
100
|
100
|
100
|
65
|
65
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
50
|
50
|
25
|
25
|
65
|
65
|
65
|
65
|
65
|
50
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
50
|
50
|
25
|
25
|
50
|
50
|
50
|
50
|
50
|
50
|
| 690V
|
[kA]
|
10
|
10
|
10
|
6
|
6
|
6
|
6
|
6
|
6
|
10
|
10
|
10
|
10
|
10
|
10
|
| Rated Service Short Circuit Breaking Capacity
|
| Ics
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
50
|
100
|
100
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
25
|
25
|
25
|
25
|
50
|
50
|
50
|
50
|
50
|
50
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
25
|
25
|
20
|
20
|
50
|
50
|
50
|
50
|
50
|
50
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
25
|
25
|
20
|
20
|
50
|
50
|
50
|
50
|
50
|
50
|
| 690V
|
[kA]
|
10
|
10
|
10
|
6
|
4
|
4
|
4
|
4
|
4
|
10
|
10
|
10
|
10
|
6
|
6
|
|
|
| ⋆ No back-up fuse required.
|
| Cat. No.
|
140-CMN-…
|
| -2500
|
-4000
|
-6300
|
-9000
|
| Rated Operational Current, Ie
|
[A]
|
25
|
40
|
63
|
90
|
| Magnetic Release Current
|
[A]
|
350
|
560
|
890
|
1260
|
| Switching of Standard Three-Phase Motors
|
| AC-3
|
| 230/240V
|
[kW]
|
5.5/7.5
|
10/11
|
13/20
|
22/25
|
| 400/415V
|
[kW]
|
7.5/13
|
15/22
|
25/32
|
37/45
|
| 500V
|
[kW]
|
11/15
|
18.5/25
|
30/40
|
45/55
|
| 690V
|
[kW]
|
15/22
|
25/30
|
37/55
|
63/75
|
| Back-up fuses
|
| gG, gL,, only if Icc ³ Icu
|
| 230/240V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
| 400/415V
|
[A]
|
160
|
160
|
160
|
160
|
| 500V
|
[A]
|
160
|
160
|
160
|
160
|
| 690V
|
[A]
|
160
|
160
|
160
|
160
|
| Ultimate short-circuit breaking capacity Icu
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
65
|
65
|
65
|
50
|
| 500V
|
[kA]
|
50
|
30
|
30
|
25
|
| 690V
|
[kA]
|
15
|
8
|
8
|
6
|
| Rated service short-circuit breaking capacity Ics
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
65
|
50
|
50
|
25
|
| 500V
|
[kA]
|
50
|
25
|
25
|
13
|
| 690V
|
[kA]
|
15
|
8
|
6
|
6
|
|
|
| ⋆ No back-up fuse required.
|
| Power ratings: Preferred values according to IEC 60072-1.
|
|
|
Cat. No. 140M-C2N-
|
| A16
|
A25
|
A40
|
A63
|
B10
|
B16
|
B25
|
| Rated Operational Current, Ie
|
[A]
|
0.16
|
0.25
|
0.4
|
0.63
|
1
|
1.6
|
2.5
|
| Magnetic Release Current
|
[A]
|
2.1
|
3.3
|
5.2
|
8.2
|
13
|
21
|
32
|
| Switching of Standard Three-Phase Motors
|
| AC-3
|
| 230/240V
|
[kW]
|
—
|
—
|
0.06
|
0.09
|
0.18
|
0.25
|
0.37
|
| 400/415V
|
[kW]
|
0.02
|
0.04
|
0.09
|
0.18
|
0.25
|
0.55
|
0.75
|
| 500V
|
[kW]
|
0.06
|
0.09
|
0.12
|
0.18
|
0.37
|
0.75
|
1.1
|
| 690V
|
[kW]
|
0.06
|
0.09
|
0.18
|
0.25
|
0.55
|
1.1
|
1.8
|
| Back-Up Fuses
|
| gG, gL, only if Icc³Icu⋆
|
| 230/240V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
| 400/415V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
| 440/460V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
| 500V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
| 690V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
16
|
20
|
| Ultimate Short Circuit Breaking Capacity
|
| Icu
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 690V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
10
|
8
|
| Rated Service Short Circuit Breaking Capacity
|
| Ics
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 690V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
8
|
8
|
|
|
| ⋆ No back-up fuse required.
|
|
|
Cat. No. 140M-D8N-
|
Cat. No. 140M-F8N-
|
| B25
|
B40
|
B63
|
C10
|
C16
|
C25
|
C32
|
C25
|
C32
|
C45
|
| Rated Operational Current, Ie
|
[A]
|
2.5
|
4.0
|
6.3
|
10
|
16
|
25
|
32
|
25
|
32
|
45
|
| Magnetic Release Current
|
[A]
|
32
|
52
|
82
|
130
|
208
|
325
|
448
|
325
|
416
|
585
|
| Switching of Standard Three-Phase Motors
|
| AC-3
|
| 230/240V
|
[kW]
|
0.37
|
0.75
|
1.5
|
2.2
|
4.0
|
5.5
|
7.5
|
6.3
|
7.5
|
13
|
| 400/415V
|
[kW]
|
0.75
|
1.5
|
2.2
|
4.0
|
7.5
|
11
|
15
|
11
|
15
|
22
|
| 500V
|
[kW]
|
1.1
|
2.2
|
3.0
|
6.3
|
10
|
15
|
20
|
15
|
20
|
30
|
| 690V
|
[kW]
|
1.8
|
3.0
|
4.0
|
7.5
|
13
|
22
|
25
|
22
|
30
|
40
|
| Back-Up Fuses
|
| gG, gL, only if Icc³Icu
|
| 230/240V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
100
|
125
|
125
|
| 400/415V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
100
|
125
|
100
|
125
|
125
|
| 440/460V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
100
|
125
|
100
|
125
|
125
|
| 500V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
80
|
100
|
100
|
125
|
125
|
| 690V
|
[A]
|
20
|
35
|
50
|
50
|
63
|
63
|
80
|
80
|
100
|
100
|
| Ultimate Short Circuit Breaking Capacity
|
| Icu
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
65
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
65
|
50
|
100
|
65
|
65
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
50
|
25
|
65
|
65
|
50
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
25
|
25
|
50
|
50
|
50
|
| 690V
|
[kA]
|
10
|
10
|
10
|
6
|
6
|
6
|
6
|
10
|
10
|
10
|
| Rated Service Short Circuit Breaking Capacity
|
| Ics
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
25
|
25
|
50
|
50
|
50
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
25
|
20
|
50
|
50
|
50
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
50
|
25
|
20
|
50
|
50
|
50
|
| 690V
|
[kA]
|
10
|
10
|
10
|
6
|
4
|
4
|
4
|
10
|
6
|
6
|
|
|
| ⋆ No back-up fuse required.
|
|
|
Cat. No. 140M-C2T-
|
| A16
|
A25
|
A40
|
A63
|
B10
|
B16
|
B25
|
B40
|
B63
|
C10
|
C16
|
| Rated Operational Current, Ie
|
[A]
|
0.16
|
0.25
|
0.40
|
0.63
|
1.0
|
1.6
|
2.5
|
4.0
|
6.3
|
10
|
16
|
| Magnetic Release Current
|
[A]
|
3.2
|
5.2
|
8.2
|
13
|
21
|
32
|
52
|
82
|
130
|
208
|
260
|
| Switching of Standard Three-Phase Motors
|
| AC-3
|
| 230/240V
|
[kW]
|
—
|
—
|
0.06
|
0.09
|
0.18
|
0.25
|
0.37
|
0.75
|
1.5
|
2.2
|
4.0
|
| 400/415V
|
[kW]
|
0.02
|
0.04
|
0.09
|
0.18
|
0.25
|
0.55
|
0.75
|
1.5
|
2.2
|
4.0
|
7.5
|
| 500V
|
[kW]
|
0.06
|
0.09
|
0.12
|
0.18
|
0.37
|
0.75
|
1.1
|
2.2
|
3.0
|
6.3
|
10
|
| 690V
|
[kW]
|
0.06
|
0.09
|
0.18
|
0.25
|
0.55
|
1.1
|
1.8
|
3.0
|
4.0
|
7.5
|
13
|
| Back-Up Fuses
|
| gG, gL, only if Icc³Icu
|
| 230/240V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
| 400/415V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
| 440/460V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
63
|
80
|
| 500V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
80
|
80
|
| 690V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
⋆
|
16
|
20
|
35
|
50
|
50
|
63
|
| Ultimate Short Circuit Breaking Capacity
|
| Icu
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
10
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
10
|
| 690V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
8
|
8
|
8
|
4
|
4
|
3
|
| Rated Service Short Circuit Breaking Capacity
|
| Ics
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
15
|
| 440/460V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
6
|
| 500V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
100
|
50
|
6
|
| 690V
|
[kA]
|
100
|
100
|
100
|
100
|
100
|
8
|
8
|
8
|
4
|
4
|
3
|
|
|
| ⋆ No back-up fuse required.
|
|
|
Cat. No. 140M-D8T-
|
Cat. No. 140M-F8T-
|
| C16
|
C20
|
C25
|
C32
|
| Rated Operational Current, Ie
|
[A]
|
16
|
20
|
25
|
32
|
| Magnetic Release Current
|
[A]
|
260
|
325
|
416
|
585
|
| Switching of Standard Three-Phase Motors
|
| AC-3
|
| 230/240V
|
[kW]
|
4.0
|
5.5
|
6.3
|
7.5
|
| 400/415V
|
[kW]
|
7.5
|
10
|
11
|
15
|
| 500V
|
[kW]
|
10
|
11
|
15
|
20
|
| 690V
|
[kW]
|
13
|
17
|
22
|
30
|
| Back-up fuses
|
| gG, gL,, only if Icc ³ Icu
|
| 230/240V
|
[A]
|
⋆
|
⋆
|
⋆
|
⋆
|
| 400/415V
|
[A]
|
80
|
100
|
100
|
125
|
| 440/460V
|
[A]
|
80
|
100
|
100
|
125
|
| 500V
|
[A]
|
80
|
80
|
100
|
125
|
| 690V
|
[A]
|
63
|
63
|
80
|
100
|
| Ultimate short-circuit breaking capacity
|
| Icu
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
100
|
65
|
65
|
65
|
| 440/460V
|
[kA]
|
50
|
25
|
65
|
65
|
| 500V
|
[kA]
|
50
|
25
|
50
|
50
|
| 690V
|
[kA]
|
6
|
6
|
10
|
10
|
| Rated service short-circuit breaking capacity Ics
|
| Ics
|
| 230/240V
|
[kA]
|
100
|
100
|
100
|
100
|
| 400/415V
|
[kA]
|
25
|
25
|
50
|
50
|
| 440/460V
|
[kA]
|
25
|
25
|
50
|
50
|
| 500V
|
[kA]
|
25
|
25
|
50
|
50
|
| 690V
|
[kA]
|
4
|
4
|
6
|
6
|
|
|
| ⋆ No back-up fuse required.
|
| Consult your local Rockwell Automation sales office or Allen-Bradley distributor.
|
| Cat. No.
|
140M-C
|
140M-D
|
140M-F
|
140-CMN
|
| Rated Insulation Voltage Ui
|
| IEC, SEV, VDE 0660
|
[V]
|
690
|
690
|
| UL, CSA
|
[V]
|
600
|
600
|
| Rated Impulse Withstand Voltage Uimp
|
| Pollution degree
|
3
|
3
|
| Main circuits Uimp /Overvoltage Category
|
6 kV/III
|
6 kV/III
|
| Auxiliary circuits Uimp /Overvoltage Category
|
6 kV/III
|
6 kV/III
|
| Rated Frequency
|
[Hz]
|
50/60
|
40…60
|
| Utilization Category
|
| IEC 60947-2 (Circuit breaker)
|
A
|
A
|
| IEC 60947-4-1 (Motor starter)
|
AC-3
|
AC-3
|
| Life Span
|
| Mechanical
|
[operations]
|
100 000
|
30 000
|
30 000
|
| Electrical (Ie max.)
|
[operations]
|
100 000
|
30 000
|
10 000 (up to 63 A) 5 000 (up to 90 A)
|
| Switching Frequency
|
[operations/h]
|
max. 25
|
max. 20
|
| Ambient Temperature
|
| Storage
|
[°C]
|
-40 … +80
|
-25… +80
|
| Operation
|
[°C]
|
-25… +60
|
| Climatic resistance
|
| Moisture change climate (600068-2-30)
|
23 °C / 83 % relative humidity and 40 °C / 92 % relative humidity, 56 cycles
|
| Dry heat (60086-2-2)
|
100 °C, relative humidity <50 %, 7 days
|
| Moisture heat (60068-2-3)
|
40 °C, relative humidity 93 %, 56 days
|
| Site Altitude
|
[m]
|
to 2000 N.N.
|
|
| Protection Class
|
IP2X, when wired
|
| Resistance to Shock, Transport (60068-2-27)
|
30 g, 11 ms, all axes
|
30, 11 ms
|
| Resistance to Vibration, Opertion (60068-2-6)
|
5 g
|
|
| Rated Thermal Current Ith
|
| up to 40 °C ambient temperature
|
[A]
|
0.1…32
|
1.6…32
|
6.3…45
|
16… 90
|
| up to 60 °C ambient temperature
|
[A]
|
0.1…32
|
1.6…32
|
6.3…45
|
16… 90
|
| Rated Supply Current Ie
|
[A]
|
0.1…32
|
1.6…32
|
6.3…45
|
16… 90
|
| Dependence on Temperature
|
| 40 °C
|
[A]
|
no reduction
|
| 50 °C
|
[A]
|
no reduction
|
| 60 °C
|
[A]
|
no reduction
|
| 70 °C
|
[A]
|
15 % current reduction of the upper rated current Ie
|
| Overload Protection
|
| Characteristics
|
IEC 60947-4-1 Motor protection (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N)
|
IEC 60947
|
| Ambient Temperature Compensation
|
[°C]
|
-20 …+60
|
| Phase-loss Protection
|
Differential release
|
| Trip class
|
10 (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) fixed setting
|
10
|
Magnetic Release Release current (+/-20 %)
|
fixed setting 13…14 x Ie max. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N) 16…21 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T) Ie max. = maximum values of setting ranges
|
fixed setting 14 x Ie max.
|
| Total Power loss Pv
|
| Circuit Breaker at rated load operating temperature
|
[W]
|
6…11.5
|
6…11.6
|
9…16
|
33
|
| Main Disconnect Switch Application
|
Yes, with accessories
|
| Application Conditions
|
For utilization outside North America, assemblies (of products) shall comply to the IEC 61439-1 requirements
|
| 140M manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments.
|
|
|
| Cat. No.
|
140M-C…
|
140M-D…
|
140M-F…
|
140-CMN
|
| Conformity to Standards
|
IEC 60947-1; -2; -4-1; EN 60947-1; -2; -4-1; UL 508; CSA 22.2, No. 14
|
IEC 60947-1; -2; EN 60947-1; -2; UL 508; CSA 22.2, No. 14
|
| Approvals
|
CE, UL, CSA
|
CE, UL, CSA
|
Terminal Parts Type of terminals
|
|
|
|
| Screwdriver
|
Pozidriv No. 2/Blade No. 3
|
Pozidriv No. 2/Blade No. 3
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
1…6/No. 16…10 1…4/No. 16…10
|
2.5…25/No. 14…4 2.5…25/No. 14…4
|
2.5…35
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
1…6/No. 16…10 1…6/No. 16…10
|
2.5…25/No. 14…4 2.5…25/No. 14…4
|
2.5…35
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
1.5…6/No. 16…8 1.5…6/No. 16…8
|
16…25/No. 14…4 16…25/No. 14…4
|
4…50 / 12…2
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
1…6/No. 16…10 1…6/No. 16…10
|
2.5…10/No. 14…8 2.5…10/No. 14…8
|
4…50 / 12…2
|
| Tightening torque
|
[Nm]/[lbin]
|
2…2.5/18…22
|
3…3.5/27…30
|
6…10/55…90
|
|
|
| Cat. No.
|
140M-RC…
|
Terminal Parts Type of terminals
|
|
| Screwdriver
|
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
0.5…2.5/— 0.5…2.5/—
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
0.5…2.5/No. 18…12 0.5…2.5/No. 18…12
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
1…4/No. 16…12 1…4/No. 16…12
|
|
|
|
|
Auxiliary Contact Blocks for Front Mounting Cat. No. 140M-C-AFA…, 140M-C-AFAR…
|
Auxiliary Contact Blocks for Right-Side Mounting Cat. No. 140M-C-ASA…, 140M-C-ASAR…
|
Rated Thermal Current Ith at 40 °C ambient temperature at 60 °C ambient temperature
|
[A] [A]
|
5 4
|
10 6
|
Contact Class Coordination According to NEMA
|
|
|
(UL/CSA Standards)
|
AC DC
|
B 300 Q 300
|
B 600 Q 600
|
| Back-Up Fuses gG, gL
|
[A]
|
10
|
10
|
| Rated Supply Current
|
[V]
|
24
|
120
|
240
|
24
|
120
|
240
|
415
|
690
|
|
|
AC-15
|
[A]
|
4
|
3
|
1.5
|
6
|
5
|
3
|
2
|
0.7
|
|
|
DC-13
|
[V]
|
24
|
120
|
240
|
24
|
120
|
240
|
415
|
|
|
|
[A]
|
2
|
0.5
|
0.25
|
2
|
0.5
|
0.25
|
0.15
|
|
Terminal Parts Type of terminals
|
|
| Screwdriver
|
Pozidriv No. 2/Blade No. 3
|
|
1. conductor 2. conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.5…1.5/18…14 0.75…1.5/18…14
|
0.5…2.5/18…14 0.75…2.5/18…14
|
|
1. conductor 2. conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.75…1.5/18…14 0.75…1.5/18…14
|
0.75…2.5/18…14 0.75…2.5/18…14
|
|
1. conductor 2. conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.75…1.5/18…14 0.75…1.5/18…14
|
0.75…2.5/18…14 0.75…2.5/18…14
|
| Tightening torque
|
[Nm]/[lbin]
|
1.2…1.5/10.6…13
|
1.2…1.5/10.6…13
|
|
|
|
|
Undervoltage Trip for Left-Side Mounting Cat. No. 140M-C-UX…
|
Undervoltage Trip with 2 Auxiliary Contacts for Left-Side Mounting Cat. No. 140M-C-UC…
|
Shunt Trip for Left-Side Mounting Cat. No. 140M-C-SN…
|
| Actuating Voltage
|
|
|
|
Pull-in Drop-out
|
0.85…1.1 x Us 0.7…0.35 x Us
|
0.85…1.1 x Us 0.7…0.35 x Us
|
0.7…1.1 x Us
|
Rated Control Voltage
|
min. max.
|
21V 50 Hz, 24V 60 Hz 600V 50 Hz
|
21V 50 Hz, 24V 60 Hz 600V 50 Hz
|
21V 50 Hz, 24V 60 Hz 600V 50 Hz
|
| On-Time
|
100%
|
100%
|
100%
|
Coil Rating
|
Pull-in Hold
|
8.5 VA, 8 W 4 VA, 2 W
|
8.5 VA, 8 W 4 VA, 2 W
|
8.5 VA, 8 W 4 VA, 2 W
|
Terminal Parts Type of terminals
|
|
| Screwdriver
|
Pozidriv No. 2/Blade No. 3
|
|
1. conductor 2. conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.5…2.5/No. 18…14 0.75…2.5/No. 18…14
|
|
1. conductor 2. conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.75…2.5/No. 18…14 0.75…2.5/No. 18…14
|
|
1. conductor 2. conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.75…2.5/No. 18…14 0.75…2.5/No. 18…14
|
| Tightening torque
|
[Nm]/[lbin]
|
1.2…1.5/10.6…13.3
|
|
|
|
|
Compact Busbar Feeder Terminal
|
Compact Busbar
|
Compact Busbar Feeder Block
|
Rated Thermal Current Ith at 60 °C ambient temperature
|
|
140M-C-WTN 140M-C-WTEN
|
140M-F-WTE
|
140M-C -W…
|
140M-F -W…
|
140M-C-WBE L1, L2, L3
|
140M-C-WBE T1, T2, T3
|
140M-F-WBE L1, L2, L3
|
140M-F-WBE T1, T2, T3
|
| [A]
|
64
|
120
|
64
|
120
|
64
|
IEC 120/UL 115
|
|
1. conductor
|
[mm2]/[AWG]
|
2.5…25/14…4
|
—
|
—
|
—
|
4…25/10…4
|
for use with 140M-C-W
|
4…50/10…4
|
for use with 140M-F-W
|
|
1. conductor
|
[mm2]/[AWG]
|
2.5…25/14…4
|
4…50/12…1/0
|
—
|
—
|
4…25/10…4
|
for use with 140M-C-W
|
4…25/10…4
|
for use with 140M-F-W
|
|
1. conductor
|
[mm2]/[AWG]
|
2.5…25/14…4
|
2.5…50/12…1/0
|
—
|
—
|
2.5…25/14…4
|
for use with 140M-C-W
|
2.5…25/14…4
|
for use with 140M-F-W
|
| Tightening torque
|
[Nm]/[lbin]
|
3…3.5/27…31
|
5…6/45…54
|
—
|
—
|
3…3.5/27…31
|
2.5…3/23…27
|
5…6/45…54
|
|
|
| Cat. No.
|
140M-RC…
|
Terminal Parts Type of terminals
|
|
| Screwdriver
|
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
0.5…1.5/— 0.5…1.5/—
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
0.5…1.5/No. 18…14 0.5…1.5/No. 18…14
|
|
1. conductor 2. conductor
|
[mm2 ]/[AWG] [mm2 ]/[AWG]
|
0.5…1.5/No. 18…14 0.5…1.5/No. 18…14
|
|
|
| Description
|
Weight [g]
|
Cat.No.
|
| Motor Protection Circuit Breakers
|
317
|
140M-C2E-…
|
| 373
|
140M-D8E-…
|
| 782
|
140M-F8E-…
|
| 315
|
140M-C2N-…
|
| 365
|
140M-D8N-…
|
| 782
|
140M-F8N-…
|
| 315
|
140M-C2T-…
|
| 365
|
140M-D8T-…
|
| 782
|
140M-F8T-…
|
| 1845
|
140-CMN-…
|
| Auxiliary Contacts
|
10
|
140M-C-AFA10
|
| 140M-C-AFA01
|
| 140M-C-AFA11
|
| 140M-C-AFA20
|
| 140M-C-ASA…
|
| 15
|
140M-C-AFAR10A…
|
| 140M-C-ASAR…M…
|
| 140M-C-ASAM11
|
| 31
|
140-CA…
|
| Undervoltage Trip
|
108
|
140M-C-UX…
|
| 110
|
140M-C-SN…
|
| 116
|
140M-C-UC…
|
| 94
|
140-CUV…
|
| Trip Contact Blocks
|
31
|
140-CT…
|
| Shunt Trip
|
94
|
140-CRT…
|
|
|
|
|
Cat. No. 140-CT Trip Contact Block for Flush Mounting on Cat. No. 140-CMN Circuit Breakers
|
Cat. No. 140-CRT, 140-CUV Undervoltage Trip and Shunt Trip for Flush Mounting on Cat. No. 140-CMN Circuit Breakers
|
Rated Thermal Current Ith up to 40 °C ambient temperature up to 60 °C ambient temperature
|
[A] [A]
|
10 6
|
2 2
|
NEMA contact class (UL/CSA-Approval)
|
AC DC
|
B 600 Standard Pilot Duty R 300 Light Pilot Duty
|
Make/Break max. voltage 432 VA72 VA480 V 28 VA28 VA250 V
|
| Back-Up Fuse gG, gL
|
16 A
|
16 A
|
| Rated Current Ie
|
|
|
|
|
|
|
|
|
|
|
|
| AC-15:
|
[V] [A]
|
230 3
|
400 2.5
|
500 1.5
|
690 0.75
|
|
AC-14:
|
24 1.5
|
110 1.5
|
230 1.0
|
400 1.0
|
500 0.75
|
| DC-13:
|
[V] [A]
|
24 2
|
48 0.6
|
110 0.2
|
230 0.1
|
440 0.04
|
DC 13:
|
24 1.5
|
48 0.5
|
60 0.4
|
110 0.2
|
|
| Terminals
|
|
|
| Screwdriver
|
|
|
|
1.conductor 2.conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14
|
0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14
|
|
1.conductor 2.conductor
|
[mm2]/[AWG] [mm2]/[AWG]
|
0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14
|
0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14
|
| Tightening torque
|
[Nm]/[lbin]
|
1… 1.5/8.8… 10.3
|
1… 1.5/8.8… 10.3
|
|
|
|
|
Cat. No. 140-CUV… Undervoltage Trip Unit for Right-Side Mounting on Cat. No. 140-CMN Circuit Breakers
|
Cat. No. 140-CRT... Shunt Trip for Flush Mounting on Cat. No. 140-CMN Circuit Breakers
|
| Operating Voltage
|
|
|
| Pick-up
|
0.8… 1.1 x Us
|
0.7… 1.1 x Us
|
| Drop-out
|
0.7… 0.35 x Us
|
—
|
| Duty cycle
|
100 % ED
|
100 % ED
|
| Control Voltage
|
|
|
|
|
min.
|
12 V 50 Hz/14 V 60 Hz
|
12 V 50 Hz/14 V 60 Hz
|
|
|
|
max.
|
600 V 50 Hz
|
600 V 50 Hz
|
| Coil Performance
|
|
|
Pick-up Drop-out
|
[VA/W] [VA/W]
|
11 / 8 4 / 1
|
12 / 7 6 / 2
|
Terminals Terminal type
|
|
|
|
Fine-stranded
|
[mm2]
|
2 x 0.75…2.5
|
2 x 0.75…2.5
|
|
Coarse-stranded
|
[mm2]
|
2 x 0.75…2.5
|
2 x 0.75…2.5
|
| Tightening torque
|
[Nm]
|
1… 1.5
|
1… 1.5
|
|
Coarse-stranded
|
[AWG]
|
No. 18…. 14
|
No. 18…. 12
|
| Tightening torque
|
[lbin]
|
8.8… 10.3
|
8.8… 10.3
|
|
|