Bulletin 140M Motor Protection Circuit Breakers
|
|
|
|
|
Bulletin 140M Motor Protection Circuit Breakers
- Current Range 0.1…630 A
- UL Listed for Motor Loads
- Short Circuit Protection
- Overload Protection
- Short Circuit Protection
- Visible Trip Indication
- High Current Limiting
- High Switching Capacity
Your order must include: cat. no. of the Motor Protection Circuit Breaker selected and, if required, cat. no. of any accessories.
The Bulletin 140M Motor Protection Circuit Breakers provide short circuit and overload protection for individual motor loads. Factory-installed internal accessories make installation and wiring easy.
General Information
Motor Protection Circuit Breakers may provide the following protective and control functions.
In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller.
140M-C, D and F Frames:
The 140M-C, D and F frame Motor Protection Circuit Breakers may have 2 cULus Listings as Manual, Self-Protected Combination Motor Controllers and as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation).
When UL/CSA listed as Manual, Self-Protected Combination Motor Controllers, the 140M Motor Protection Circuit Breakers provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices.
At some higher voltages and currents (particularly at 600V), a few of the 140M-C, D and F frame devices are only UL/CSA Listed as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on UL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only for the specific ratings of each Motor Protection Circuit Breaker.
140-CMN Frame:
The 140-CMN frame Motor Protection Circuit Breakers are UL Listed/CSA Certified as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on UL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only for the specific ratings of each Motor Protection Circuit Breaker.
140M-I, J and L Frames:
The 140M-I, J and L frame Motor Protection Circuit Breakers are cULus Listed as Circuit Breakers as shown in the table on Motor Protection Circuit Breakers. In these cases, the 140M Motor Protection Circuit Breakers provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices.
For further details on the proper application of Motor Protection Circuit Breakers, please see the diagrams on the following pages.
Standards Compliance and Certifications
Standards Compliance
IEC/EN 60947-1, -2, -4-1, -5-1
IEC/EN 60204-1
CSA, C22.2 No.14
UL 508
UL 489 (I-, J-, L-Frame)
Certifications
CE Marked
cULus Listed (File No.
E54612, NLRV(7); E205542, NKJH(7); E197878, DIVQ(7);)
CCC
CSA Certified
ATEX
Product Line Overview
Cat. No. Explanation
| 140M | | C | 2 | E | | A63 | | KN | | CC | | GJ |
| a | b | c | d | e | f | g | h |
| a | b | c | d | ||||||||
| Bulletin Number | Frame Size and Rating | Interrupting Rating / Breaking Capacity | Protection Type | ||||||||
| Code | Description | Code | Description | Code | Description | Code | Description | ||||
| 140M | Motor Protection Circuit Breakers (MPCBs) | C | 32 A | 2 | Normal Break | E | Adj Thermal/ Fixed Mag (13 x In) | ||||
| D | 32 A | 8 | High Break | T | Adj Thermal / Fixed Mag (Fixed at 16...20 x In) | ||||||
| F | 45 A | ||||||||||
| I | 205 A | ||||||||||
| J | 250 A | ||||||||||
| L | 400 A and 600 A | ||||||||||
| e | f | g | h | ||||||||
| Current Range | Miscellaneous See 140M Factory Modifications (Open) | Aux/Trip Contacts See 140M Factory Modifications (Open) | UV and Shunt Trips See 140M Factory Modifications (Open) | ||||||||
| Code | Description | Example | |||||||||
| A | A = .10 | A16 = 0.16 | |||||||||
| B | B = 1.0 | B16 = 1.6 | |||||||||
| C | C = 10 | C16 = 16 | |||||||||
| D | D = 100 | D16 = 160 | |||||||||
| E | E = 1000 | E16 = 1600 | |||||||||
Wiring Diagrams
|
3-Phase Power Supply
|
Type E and Type F Combination Motor Controllers
Most of the 140M-C…F motor protection circuit breakers are UL listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass, is to perform 6000 electrical ops. and an additional 4000 mechanical ops. after a short circuit.
By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a Bulletin 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits.
A combination of a Bulletin 140M manual self protected combination motor controller and 100-C contactor can be listed as a Type E self-protected combination motor controller. In this case, both the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require over sizing of the Bulletin 140M MPCB or the 100-C contactor to achieve weld free performance and meet the additional life requirements.
Motor Protection Circuit Breakers
- Short Circuit Protection — Standard Magnetic Trip (13…14 x Ie)
- Motor Overload Protection — Trip Class 10
|
|
|
|
| Cat. No. 140M-C | Cat. No. 140M-D | Cat. No. 140M-F | Cat. No. 140M-CMN |
| Rated Operational Current (Ie) [A] |
Motor Current Adjustment Range [A] |
Magnetic Trip Current [A] |
Max. Short Circuit Current [kA] | Max. 3-phase Hp Ratings⋆ | Max. kW, 3-Phase — AC-3⋆ | Cat. No. | |||||||
| 400V (Icu) |
480V (group motor) |
200V | 230V | 460V | 575V | 230V | 400/415V | 500V | 690V | ||||
| C-Frame | |||||||||||||
| 0.16 | 0.10…0.16 | 2.1 | 100 | 65 | — | — | — | — | — | 0.02 | 0.06 | 0.06 | 140M-C2E-A16 |
| 0.25 | 0.16…0.25 | 3.3 | 100 | 65 | — | — | — | — | — | 0.04 | 0.09 | 0.09 | 140M-C2E-A25 |
| 0.4 | 0.25…0.40 | 5.2 | 100 | 65 | — | — | — | 0.25 | 0.06 | 0.09 | 0.12 | 0.18 | 140M-C2E-A40 |
| 0.63 | 0.40…0.63 | 8.2 | 100 | 65 | — | — | 0.25 | 0.33 | 0.09 | 0.18 | 0.18 | 0.25 | 140M-C2E-A63 |
| 1 | 0.63…1.0 | 13 | 100 | 65 | — | — | 0.5 | 0.75 | 0.18 | 0.25 | 0.37 | 0.55 | 140M-C2E-B10 |
| 1.6 | 1.0…1.6 | 21 | 100 | 65 | 0.25 | 0.33 | 1 | 1 | 0.25 | 0.55 | 0.75 | 1.1 | 140M-C2E-B16 |
| 2.5 | 1.6…2.5 | 33 | 100 | 65 | 0.5 | 0.75 | 1.5 | 2 | 0.37 | 0.75 | 1.1 | 1.8 | 140M-C2E-B25 |
| 4 | 2.5…4.0 | 52 | 100 | 65 | 1 | 1 | 3 | 3 | 0.75 | 1.5 | 2.2 | 3 | 140M-C2E-B40 |
| 6.3 | 4.0…6.3 | 82 | 100 | 65 | 1.5 | 2 | 5 | 5 | 1.5 | 2.2 | 3 | 4 | 140M-C2E-B63 |
| 10 | 6.3…10 | 130 | 100 | 65 | 3 | 3 | 7.5 | 10 | 2.2 | 4 | 6.3 | 7.5 | 140M-C2E-C10 |
| 16 | 10…16 | 208 | 65 | 30 | 5 | 5 | 10 | 15 | 4 | 7.5 | 10 | 13 | 140M-C2E-C16 |
| 20 | 14.5…20 | 260 | 50 | 30 | 5 | 7.5 | 15 | 20 | 5.5 | 10 | 11 | 17 | 140M-C2E-C20 |
| 25 | 18…25 | 325 | 15 | 25 | 7.5 | 7.5 | 20 | 20 | 5.5 | 11 | 15 | 22 | 140M-C2E-C25 |
| 29 | 24…29 | 406 | 15 | 25 | 7.5 | 10 | 20 | 25 | 7.5 | 13 | 18.5 | 25 | 140M-C2E-C29 |
| 32 | 27…32 | 448 | 15 | 25 | 7.5 | 10 | 25 | 30 | 7.5 | 15 | 20 | 25 | 140M-C2E-C32 |
| D-Frame | |||||||||||||
| 2.5 | 1.6…2.5 | 33 | 100 | 65 | 0.5 | 0.75 | 1.5 | 2 | 0.37 | 0.75 | 1.1 | 1.8 | 140M-D8E-B25 |
| 4 | 2.5…4.0 | 52 | 100 | 65 | 1 | 1 | 3 | 3 | 0.75 | 1.5 | 2.2 | 3 | 140M-D8E-B40 |
| 6.3 | 4.0…6.3 | 82 | 100 | 65 | 1.5 | 2 | 5 | 5 | 1.5 | 2.2 | 3 | 4 | 140M-D8E-B63 |
| 10 | 6.3…10 | 130 | 100 | 65 | 3 | 3 | 7.5 | 10 | 2.2 | 4 | 6.3 | 7.5 | 140M-D8E-C10 |
| 16 | 10…16 | 208 | 100 | 65 | 5 | 5 | 10 | 15 | 4 | 7.5 | 10 | 13 | 140M-D8E-C16 |
| 20 | 14.5…20 | 260 | 100 | 65 | 5 | 7.5 | 15 | 20 | 5.5 | 10 | 11 | 17 | 140M-D8E-C20 |
| 25 | 18…25 | 325 | 65 | 30 | 7.5 | 7.5 | 20 | 20 | 5.5 | 11 | 15 | 22 | 140M-D8E-C25 |
| 29 | 24…29 | 406 | 50 | 30 | 7.5 | 10 | 20 | 25 | 7.5 | 13 | 18.5 | 25 | 140M-D8E-C29 |
| 32 | 27…32 | 448 | 50 | 30 | 7.5 | 10 | 25 | 30 | 7.5 | 15 | 20 | 25 | 140M-D8E-C32 |
| F-Frame | |||||||||||||
| 10 | 6.3…10 | 130 | 100 | 65 | 3 | 3 | 7.5 | 10 | 2.2 | 4 | 6.3 | 7.5 | 140M-F8E-C10 |
| 16 | 10…16 | 208 | 100 | 65 | 5 | 5 | 10 | 15 | 4 | 7.5 | 10 | 13 | 140M-F8E-C16 |
| 20 | 14.5…20 | 260 | 100 | 65 | 5 | 7.5 | 15 | 20 | 5.5 | 10 | 11 | 17 | 140M-F8E-C20 |
| 25 | 18…25 | 325 | 100 | 65 | 7.5 | 10 | 20 | 25 | 6.3 | 11 | 15 | 22 | 140M-F8E-C25 |
| 32 | 23…32 | 416 | 65 | 65 | 7.5 | 10 | 25 | 30 | 7.5 | 15 | 20 | 30 | 140M-F8E-C32 |
| 45 | 32…45 | 585 | 65 | 65 | 10 | 15 | 30 | 40 | 13 | 22 | 30 | 40 | 140M-F8E-C45 |
| CMN-Frame | |||||||||||||
| 25 | 16…25 | 350 | 65 | 65 | 5 | 7.5 | 15 | 20 | 7.5 | 13 | 15 | 22 | 140-CMN-2500 |
| 40 | 25…40 | 560 | 65 | 65 | 10 | 10 | 30 | 30 | 11 | 22 | 25 | 30 | 140-CMN-4000 |
| 63 | 40…63 | 882 | 65 | 42 | 20 | 20 | 40 | 60 | 20 | 32 | 40 | 55 | 140-CMN-6300 |
| 90 | 63…90 | 1260 | 50 | 35 | 25 | 30 | 60 | 75 | 25 | 45 | 55 | 75 | 140-CMN-9000 |
| ⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current. | |||||||||||||
Motor Protection Circuit Breakers
- Short Circuit Protection — Standard Magnetic Trip (Fixed at 12...15 x Ie)
- Overload Protection — Trip Class 10...30 (Adjustable)
|
|
|
| Cat. No. 140M-I | Cat. No. 140M-J | Cat. No. 140M-L |
| Rated Operational Current (Ie) [A] |
Motor Current Adjustment Range [A] |
Magnetic Trip Current [A] |
Ultimate Interrupting Current [kA] (Icm) |
3-phase Hp Ratings⋆ | Max. kW, 3-Phase — AC-3⋆ | Cat. No. | |||||||
| 400V | 480V | 200V | 230V | 460V | 575V | 230V | 400/415V | 500V | 690V | ||||
| I-Frame | |||||||||||||
| 80 | 40…80 | 1200 | 70 | 65 | 25 | 30 | 60 | 75 | 22 | 37 | 55 | 75 | 140M-I8E-C80 § |
| 100 | 80…100 | 1500 | 70 | 65 | 30 | 40 | 75 | 100 | 30 | 55 | 55 | 90 | 140M-I8E-D10 § |
| 160 | 100…160 | 2400 | 70 | 65 | 50 | 60 | 125 | 150 | 45 | 75 | 110 | 132 | 140M-I8E-D16 § |
| 205 | 160…205 | 2665 | 70 | 65 | 60 | 75 | 150 | 200 | 55 | 110 | 132 | 200 | 140M-I8E-D20 ♣ |
| J-Frame | |||||||||||||
| 50 | 20…50 | 700 | 25 | 25 | 25 | 30 | 60 | 75 | 15 | 22 | 30 | 45 | 140M-J2E-C50 |
| 100 | 40…100 | 1400 | 25 | 25 | 30 | 40 | 75 | 100 | 30 | 55 | 55 | 90 | 140M-J2E-D10 |
| 160 | 64…160 | 2240 | 25 | 25 | 50 | 60 | 125 | 150 | 45 | 90 | 110 | 160 | 140M-J2E-D16 |
| 250 | 100…250 | 3500 | 25 | 25 | 75 | 100 | 200 | 250 | 55 | 132 | 160 | 250 | 140M-J2E-D25 |
| 50 | 20…50 | 700 | 70 | 65 | 25 | 30 | 60 | 75 | 15 | 22 | 30 | 45 | 140M-J8E-C50 |
| 100 | 40…100 | 1400 | 70 | 65 | 30 | 40 | 75 | 100 | 30 | 55 | 55 | 90 | 140M-J8E-D10 |
| 160 | 64…160 | 2240 | 70 | 65 | 50 | 60 | 125 | 150 | 45 | 90 | 110 | 160 | 140M-J8E-D16 |
| 250 | 100…250 | 3500 | 70 | 65 | 75 | 100 | 200 | 250 | 55 | 132 | 160 | 250 | 140M-J8E-D25 |
| L-Frame | |||||||||||||
| 250 | 100…250 | 3000 | 40 | 35 | 75 | 100 | 200 | 250 | 55 | 132 | 160 | 250 | 140M-L2E-D25 |
| 400 | 160…400 | 4800 | 40 | 35 | 125 | 150 | 300 | 400 | 132 | 200 | 250 | 400 | 140M-L2E-D40 |
| 630 | 250…630 | 7580 | 40 | 35 | 200 | 250 | 500 | 600 | 200 | 355 | 450 | 630 | 140M-L2E-D63 |
| 250 | 100…250 | 3000 | 70 | 65 | 75 | 100 | 200 | 250 | 55 | 132 | 160 | 250 | 140M-L8E-D25 |
| 400 | 160…400 | 4800 | 70 | 65 | 150 | 150 | 350 | 450 | 132 | 200 | 250 | 400 | 140M-L8E-D40 |
| 630 | 250…630 | 7560 | 70 | 65 | 200 | 250 | 500 | 600 | 200 | 355 | 450 | 630 | 140M-L8E-D63 |
| ⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current. | |||||||||||||
| For IEC approvals and CE marking, add an "E" to the end of the Cat. No. Example: 140M-18E-C80E. | |||||||||||||
| § Overload Protection — adjustable Trip Class 5, 10, 15, or 20. | |||||||||||||
| ♣ Overload Protection — fixed Trip Class 10. | |||||||||||||
High Inrush Motor Protection Circuit Breakers
- Short Circuit Protection — High Magnetic Trip (Fixed at 16…21 x Ie)
- Motor Overload Protection — Trip Class 10
|
|
|
| Cat. No. 140M-C | Cat. No. 140M-D | Cat. No. 140M-F |
| Rated Operational Current (Ie) [A] |
Motor Current Adjustment Range [A] |
Magnetic Trip Current [A] |
Max. Short Circuit Current [kA] | Max. 3-phase Hp Ratings⋆ | Max kW, 3-Phase — AC-3⋆ | Cat. No. | |||||||
| 400V (Icu) |
480V (group motor) |
200V | 230V | 460V | 575V | 230V | 400/415V | 500V | 690V | ||||
| C-Frame | |||||||||||||
| 0.16 | 0.10…0.16 | 3.3 | 100 | 65 | — | — | — | — | — | 0.02 | 0.06 | 0.06 | 140M-C2T-A16 |
| 0.25 | 0.16…0.25 | 5.2 | 100 | 65 | — | — | — | — | — | 0.04 | 0.09 | 0.09 | 140M-C2T-A25 |
| 0.4 | 0.25…0.40 | 8.2 | 100 | 65 | — | — | — | 0.25 | 0.06 | 0.09 | 0.12 | 0.18 | 140M-C2T-A40 |
| 0.63 | 0.40…0.63 | 13 | 100 | 65 | — | — | 0.25 | 0.33 | 0.09 | 0.18 | 0.18 | 0.25 | 140M-C2T-A63 |
| 1 | 0.63…1.0 | 21 | 100 | 65 | — | — | 0.5 | 0.75 | 0.18 | 0.25 | 0.37 | 0.55 | 140M-C2T-B10 |
| 1.6 | 1.0…1.6 | 33 | 100 | 65 | 0.25 | 0.33 | 1 | 1 | 0.25 | 0.55 | 0.75 | 1.1 | 140M-C2T-B16 |
| 2.5 | 1.6…2.5 | 52 | 100 | 65 | 0.5 | 0.75 | 1.5 | 2 | 0.37 | 0.75 | 1.1 | 1.8 | 140M-C2T-B25 |
| 4 | 2.5…4 | 82 | 100 | 65 | 1 | 1 | 3 | 3 | 0.75 | 1.5 | 2.2 | 3 | 140M-C2T-B40 |
| 6.3 | 4…6.3 | 130 | 100 | 65 | 1.5 | 2 | 5 | 5 | 1.5 | 2.2 | 3 | 4 | 140M-C2T-B63 |
| 10 | 6.3…10 | 208 | 100 | 30 | 3 | 3 | 7.5 | 10 | 2.2 | 4 | 6.3 | 7.5 | 140M-C2T-C10 |
| 16 | 10…16 | 260 | 50 | 30 | 5 | 5 | 10 | 15 | 4 | 7.5 | 10 | 13 | 140M-C2T-C16 |
| D-Frame | |||||||||||||
| 16 | 10…16 | 260 | 100 | 65 | 5 | 5 | 10 | 15 | 4 | 7.5 | 10 | 13 | 140M-D8T-C16 |
| 20 | 14.5…20 | 325 | 65 | 30 | 5 | 7.5 | 15 | 20 | 5.5 | 10 | 11 | 17 | 140M-D8T-C20 |
| F-Frame | |||||||||||||
| 25 | 18…25 | 416 | 65 | 65 | 7.5 | 10 | 20 | 25 | 6.3 | 11 | 15 | 22 | 140M-F8T-C25 |
| 32 | 23…32 | 585 | 65 | 65 | 7.5 | 10 | 25 | 30 | 7.5 | 15 | 20 | 30 | 140M-F8T-C32 |
| ⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current. | |||||||||||||
Motor Protection Circuit Breakers — Screwless
- Short Circuit Protection — Standard Magnetic Trip (13…14 x Ie)
- Motor Overload Protection — Trip Class 10
|
| Rated Operational Current (Ie) [A] |
Motor Current Adjustment Range [A] |
Magnetic Trip Current [A] |
Max. Short Circuit Current [kA] | Max. 3-phase Hp Ratings⋆ | Max. kW, 3-Phase — AC-3⋆ | Cat. No. | |||||||
| 400V (Icu) |
480V (group motor) |
200V | 230V | 460V | 575V | 230V | 400/415V | 500V | 690V | ||||
| C-Frame | |||||||||||||
| 0.16 | 0.10…0.16 | 2.1 | 100 | 65 | — | — | — | — | — | 0.02 | 0.06 | 0.06 | 140M-RC2E-A16 |
| 0.25 | 0.16…0.25 | 3.3 | 100 | 65 | — | — | — | — | — | 0.04 | 0.09 | 0.09 | 140M-RC2E-A25 |
| 0.4 | 0.25…0.40 | 5.2 | 100 | 65 | — | — | — | 0.25 | 0.06 | 0.09 | 0.12 | 0.18 | 140M-RC2E-A40 |
| 0.63 | 0.40…0.63 | 8.2 | 100 | 65 | — | — | 0.25 | 0.33 | 0.09 | 0.18 | 0.18 | 0.25 | 140M-RC2E-A63 |
| 1 | 0.63…1.0 | 13 | 100 | 65 | — | — | 0.5 | 0.75 | 0.18 | 0.25 | 0.37 | 0.55 | 140M-RC2E-B10 |
| 1.6 | 1.0…1.6 | 21 | 100 | 65 | 0.25 | 0.33 | 1 | 1 | 0.25 | 0.55 | 0.75 | 1.1 | 140M-RC2E-B16 |
| 2.5 | 1.6…2.5 | 33 | 100 | 65 | 0.5 | 0.75 | 1.5 | 2 | 0.37 | 0.75 | 1.1 | 1.8 | 140M-RC2E-B25 |
| 4 | 2.5…4.0 | 52 | 100 | 65 | 1 | 1 | 3 | 3 | 0.75 | 1.5 | 2.2 | 3.0 | 140M-RC2E-B40 |
| 6.3 | 4.0…6.3 | 82 | 100 | 65 | 1.5 | 2 | 5 | 5 | 1.5 | 2.2 | 3.0 | 4.0 | 140M-RC2E-B63 |
| 10 | 6.3…10 | 130 | 100 | 65 | 3 | 3 | 7.5 | 10 | 2.2 | 4.0 | 6.3 | 7.5 | 140M-RC2E-C10 |
| 16 | 10…16 | 208 | 65 | 30 | 5 | 5 | 10 | 15 | 4.0 | 7.5 | 10 | 13 | 140M-RC2E-C16 |
| ⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current. | |||||||||||||
Application Ratings
UL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only
| Cat. No. | UL 508 — Manual Motor Controller | UL 508 Self-Protected (Type E) Combination Motor Controller |
UL 489 Inverse Time C.B. w/UL 508 Motor Overload Protection |
||||||||
| Max. Fuse or C.B. per NEC | Group Motor Installation | Motor Disconnect | Tap Conductor Protection | ||||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | |||||||
| 480V | 600V | 480V | 600V | 480V | 600V | 480Y/277V§ | 600Y/347V§ | 480V | 600V | ||
| C-Frame | |||||||||||
| 140M-C2E-A16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A25 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A40 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A63 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B10 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B25 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-C2E-B40 | 450 | 65 | 25 | 65 | 25 | 65 | 25 | 65 | 25 | — | — |
| 140M-C2E-B63 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-C2E-C10 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-C2E-C16 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — | — | — |
| 140M-C2E-C20 | 450 | 30 | 30 | 10 | 10 | 10 | — | 10 | — | — | — |
| 140M-C2E-C25 | 450 | 25 | 10 | 10 | 5 | — | — | — | — | — | — |
| 140M-C2E-C29 | 450 | 25 | 30 | 10 | — | — | — | — | — | — | — |
| 140M-C2E-C32 | 450 | 25 | 30 | 10 | — | — | — | — | — | — | — |
| D-Frame | |||||||||||
| 140M-D8E-B25 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-B40 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-B63 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C10 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C16 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C20 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-D8E-C25 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — | — | — |
| 140M-D8E-C29 | 450 | 30 | 30 | 30 | 18 | — | — | — | — | — | — |
| 140M-D8E-C32 | 450 | 30 | 30 | 30 | 18 | — | — | — | — | — | — |
| F-Frame | |||||||||||
| 140M-F8E-C10 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C16 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C20 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C25 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C32 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C45 | 600 | 65 | 18 | 65 | 18 | 65 | — | 65 | — | — | — |
| CMN-Frame | |||||||||||
| 140-CMN-2500 | 1000 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-4000 | 1000 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-6300 | 1000 | 42 | 18 | — | — | — | — | — | — | — | — |
| 140-CMN-9000 | 1000 | 35 | 10 | — | — | — | — | — | — | — | — |
| I-Frame | |||||||||||
| 140M-I8E-C80 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D10 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D16 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D20 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| J-Frame | |||||||||||
| 140M-J2E-C50 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D10 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D16 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D25 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J8E-C50 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D10 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D16 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D25 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| L-Frame | |||||||||||
| 140M-L2E-D25 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L2E-D40 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L2E-D63 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L8E-D25 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| 140M-L8E-D40 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| 140M-L8E-D63 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| § For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||||
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Self-Protected (Type E) Combination Motor Controller |
|||||||
| Max. Fuse or C.B. per NEC | Group Motor Installation | Motor Disconnect | Tap Conductor Protection | ||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | ||||||
| 480V | 600V | 480V | 600V | 480V | 600V | 480Y/277V§ | 600Y/347V§ | ||
| C-Frame | |||||||||
| 140M-C2T-A16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A25 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A40 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A63 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-B10 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-B16 | 450 | 65 | 47 | 65 | 47 | 65 | 30 | 65 | 30 |
| 140M-C2T-B25 | 450 | 65 | 25 | 65 | 25 | 65 | 25 | 65 | 25 |
| 140M-C2T-B40 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — |
| 140M-C2T-B63 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — |
| 140M-C2T-C10 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — |
| 140M-C2T-C16 | 450 | 30 | 30 | 10 | 10 | 10 | — | 10 | — |
| D-Frame | |||||||||
| 140M-D8T-C16 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 |
| 140M-D8T-C20 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — |
| F-Frame | |||||||||
| 140M-F8T-C25 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 |
| 140M-F8T-C32 | 600 | 65 | 18 | 65 | 18 | 65 | 18 | 65 | 18 |
| § For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||
UL Listed Application Ratings — Motor Circuit Protectors Only♣
| Cat. No. | UL 508 Manual Motor Controller | UL 489 Instantaneous Trip Circuit Breaker (Magnetic Only) | |||||
| Max. Fuse or C.B. per NEC | Group Motor Installation | Motor Disconnect | Motor Circuit Protector | ||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA]§ | |||||
| 480V | 600V | 480V | 600V | 480V | 600V | ||
| C-Frame | |||||||
| 140M-C2N-A16 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A25 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A40 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A63 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B10 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B16 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B25 | 450 | 65 | 30 | 65 | 30 | — | — |
| D-Frame | |||||||
| 140M-D8N-B25 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-B40 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-B63 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C10 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C16 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C25 | 450 | 30 | 30 | 30 | 30 | — | — |
| 140M-D8N-C32 | 450 | 30 | 30 | 30 | 18 | — | — |
| F-Frame | |||||||
| 140M-F8N-C25 | 600 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8N-C32 | 600 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8N-C45 | 600 | 65 | 18 | 65 | 18 | — | — |
| H-Frame | |||||||
| 140M-H8P-B30 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-B70 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C15 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C30 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C50 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C70 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-D10 | — | — | — | — | — | 65 | 30 |
| 140M-H8R-D10 | — | — | — | — | — | 65 | 30 |
| J-Frame | |||||||
| 140M-J8P-C70 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-C90 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D10 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D12 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D15 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D17 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D20 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D22 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D25 | — | — | — | — | — | 65 | 30 |
| L-Frame | |||||||
| 140M-L8P-D22 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D25 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D30 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D35 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D40 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D45 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D50 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D60 | — | — | — | — | — | 65 | 30 |
| N-Frame | |||||||
| 140M-N8P-D80 | — | — | — | — | — | 65 | 35 |
| 140M-N8P-E12 | — | — | — | — | — | 65 | 35 |
| ♣ Separate overload protection is required. | |||||||
| § The interrupting rating for MCPs is dependent upon the controller used. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information. | |||||||
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-K Contactors
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type F Combination Motor Controller |
UL 508 Type E Self-Protected Combination Motor Controller |
|||||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Group Motor Installation | Motor Disconnect | |||||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | |||||||
| 480V | 600V | 480V | 600V | 480Y/277V♣ | 600Y/347V♣ | 480Y/277V♣ | 600Y/347V♣ | |||||
| C-Frame | ||||||||||||
| 140M-C2E-A16 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A25 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A40 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A63 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B10 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B16 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B25 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-C2E-B40 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-C2E-B63 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | — | — | — | — |
| 140M-C2E-C10 | 450 | 100-K09 | 65 | 30 | 65 | 30 | 100-K09 | 65 | — | — | — | — |
| 140M-C2E-C16 | 450 | 100-K12 | 30 | 30 | 30 | 30 | 100-K12 | 30 | — | — | — | — |
| D-Frame | ||||||||||||
| 140M-D8E-B25 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-B40 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-B63 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-C10 | 450 | 100-K09 | 65 | 30 | 65 | 30 | 100-K09 | 65 | 30 | — | — | — |
| 140M-D8E-C16 | 450 | 100-K12 | 65 | 30 | 65 | 30 | 100-K12 | 65 | 30 | — | — | — |
| ♣ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | ||||||||||||
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-C Contactors
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type F Combination Motor Controller |
UL 508 Type E Self-Protected Combination Motor Controller |
|||||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Group Motor Installation | Motor Disconnect | |||||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | |||||||
| 480V | 600V | 480V | 600V | 480Y/277V♣ | 600Y/347V♣ | 480Y/277V♣ | 600Y/347V♣ | |||||
| C-Frame | ||||||||||||
| 140M-C2E-A16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A25 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A40 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A63 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B10 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C09 | 65 | 30 |
| 140M-C2E-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | — | 65 | 25 |
| 140M-C2E-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — | — | 65 | — |
| 140M-C2E-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — | — | 65 | — |
| 140M-C2E-C16 | 450 | 100-C12 | 30 | 30 | 30 | 25 | 100-C12 | 30 | — | — | 30 | — |
| 140M-C2E-C20 | 450 | 100-C16 | 30 | 30 | 30 | 30 | 100-C23 | 10 | — | — | 10 | — |
| 140M-C2E-C25 | 450 | 100-C23 | 30 | 30 | 10 | 10 | — | — | — | — | — | — |
| 450 | 100-C30 | 30 | 30 | 30 | 30 | — | — | — | — | — | — | |
| 140M-C2E-C29 | 450 | 100-C30 | 30 | 30 | 10 | 10 | — | — | — | — | — | — |
| 140M-C2E-C32 | 450 | 100-C37 | 30 | 30 | 10 | 10 | — | — | — | — | — | — |
| D-Frame | ||||||||||||
| 140M-D8E-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C09 | 65 | 30 |
| — | — | — | — | — | — | — | — | — | 100-C23 | 65 | 30 | |
| 140M-D8E-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C23 | 65 | 30 |
| 140M-D8E-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C16 | 450 | 100-C12 | 65 | 30 | 65 | 30 | 100-C12 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C20 | 450 | 100-C23 | 65 | 30 | 65 | 30 | 100-C23 | 65 | — | 100-C30 | 65 | — |
| 140M-D8E-C25 | 450 | 100-C23 | 65 | 30 | 65 | 30 | 100-C23 | 30 | — | 100-C30 | 30 | — |
| 140M-D8E-C29 | 450 | 100-C30 | 65 | 30 | 65 | 10 | — | — | — | — | — | — |
| 140M-D8E-C32 | 450 | 100-C37 | 65 | 30 | 65 | 10 | — | — | — | — | — | — |
| F-Frame | ||||||||||||
| 140M-F8E-C10 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C16 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C20 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C25 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C32 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C45 | 600 | 100-C37 | 65 | 18 | 65 | 18 | 100-C37 | 65 | — | 100-C37 | 65 | — |
| CMN-Frame | ||||||||||||
| 140-CMN-2500 | 1000 | 100-C16 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-4000 | 1000 | 100-C30 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-6300 | 1000 | 100-C43 | 42 | 18 | — | — | — | — | — | — | — | — |
| 140-CMN-9000 | 1000 | 100-C72 | 35 | 10 | — | — | — | — | — | — | — | — |
| ♣ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | ||||||||||||
UL Listed Application Ratings - Motor Circuit Protectors with Bulletin 100-C Contactors♣
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type E (Self-Protected) Combination Motor Controller | |||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Group Motor Installation | Motor Disconnect | ||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | |||||
| 480V | 600V | 480V | 600V | 480Y/277V | 600Y/347V | ||||
| C-Frame | |||||||||
| 140M-C2N-A16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A25 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A40 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A63 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B10 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — |
| D-Frame | |||||||||
| 140M-D8N-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — |
| — | — | — | — | — | — | 100-C23 | 65 | 30 | |
| 140M-D8N-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C23 | 65 | 30 |
| 140M-D8N-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C16 | 450 | 100-C12 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C25 | 450 | 100-C23 | 30 | 30 | 30 | 30 | 100-C30 | 65 | — |
| 140M-D8N-C32 | 450 | 100-C37 | 65 | 10 | 65 | 10 | — | — | — |
| F-Frame | |||||||||
| 140M-F8N-C25 | 600 | 100-C23 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8N-C32 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8N-C45 | 600 | 100-C37 | 65 | 18 | 65 | 18 | 100-C37 | 65 | — |
| ♣ Separate overload protection is required. | |||||||||
| For full-voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||
Definition of Type 2 Short Circuit Coordination:
- The contactor or starter must not endanger persons or plant in the event of a short circuit.
- No damage to the motor protection device or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without appreciable deformation (such as with a screwdriver).
In the event of short circuit, fast-opening, current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical, fully short-circuit coordinated starter combinations with Type 2 coordination.
Type 2 Coordination 400V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Motor Protection | High Inrush Motor Protection | Motor Circuit Protection | 400V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 100 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 100 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 100 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 100 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 100 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 100 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 50 | 100-C09 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 50 | 100-C09 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 50 | 100-C09 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 50 | 100-C09 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 50 | 100-C12⋆ |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 50 | 100-C23 |
| 140M-C2E-C25 | — | — | 15 | 100-C30 |
| 140M-C2E-C29 | — | — | 15 | 100-C30 |
| 140M-C2E-C32 | — | — | 15 | 100-C37 |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 100 | 100-C09 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 100 | 100-C09 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 100 | 100-C09 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 65 | 100-C09 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 65 | 100-C12 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 65 | 100-C23 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 50 | 100-C23 |
| 140M-D8E-C29 | — | — | 65 | 100-C30 |
| 140M-D8E-C32 | — | 140M-D8N-C32 | 65 | 100-C37 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 100 | 100-C09 |
| 140M-F8E-C16 | — | — | 100 | 100-C12 |
| 140M-F8E-C20 | — | — | 100 | 100-C23 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 100 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 100 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 100 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 65 | 100-C16 |
| 140-CMN-4000 | — | — | 65 | 100-C30 |
| 140-CMN-6300 | — | — | 42 | 100-C43 |
| 140-CMN-9000 | — | — | 35 | 100-C72 |
| ⋆ Cat. No. 100-C16 contactors Type 1 only | ||||
Type 2 Coordination 480V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Motor Protection | High Inrush Motor Protection | Motor Circuit Protection | 480V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 65 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 65 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 65 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 65 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 65 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 65 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 50 | 100-C16 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 50 | 100-C30 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 50 | 100-C30 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 50 | 100-C30 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 10 | 100-C30 |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 10 | 100-C30 |
| 140M-C2E-C25 | — | — | 10 | 100-C30 |
| 140M-C2E-C29 | — | — | 10 | 100-C30 |
| 140M-C2E-C32 | — | — | 10 | 100-C37 |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 65 | 100-C09 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 65 | 100-C09 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 65 | 100-C09 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 65 | 100-C09 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 65 | 100-C12 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 65 | 100-C23 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 65 | 100-C23 |
| 140M-D8E-C29 | — | — | 65 | 100-C30 |
| 140M-D8E-C32 | — | 140M-D8N-C32 | 65 | 100-C37 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 65 | 100-C09 |
| 140M-F8E-C16 | — | — | 65 | 100-C12 |
| 140M-F8E-C20 | — | — | 65 | 100-C23 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 65 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 65 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 65 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 65 | 100-C16 |
| 140-CMN-4000 | — | — | 65 | 100-C30 |
| 140-CMN-6300 | — | — | 42 | 100-C43 |
| 140-CMN-9000 | — | — | 35 | 100-C72 |
Type 2 Coordination 600V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Motor Protection | High Inrush Motor Protection | Motor Circuit Protection | 600V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 47 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 47 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 47 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 47 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 47 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 47 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 10 | 100-C16 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 10 | 100-C16 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 5 | 100-C23 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 5 | 100-C30 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 5 | 100-C30 |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 5 | 100-C30 |
| 140M-C2E-C25 | — | — | 5 | 100-C30 |
| 140M-C2E-C29 | — | — | 5 | 100-C30 |
| 140M-C2E-C32 | — | — | 5 | 100-C37 |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 30 | 100-C30 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 30 | 100-C30 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 30 | 100-C30 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 30 | 100-C30 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 30 | 100-C30 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 5 | 100-C30 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 5 | 100-C30 |
| 140M-D8E-C29 | — | — | 10 | 100-C30 |
| 140M-D8E-C32 | — | 140M-D8N-C32 | 10 | 100-C37 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 30 | 100-C30 |
| 140M-F8E-C16 | — | — | 30 | 100-C30 |
| 140M-F8E-C20 | — | — | 30 | 100-C30 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 30 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 30 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 10 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 42 | 100-C16 |
| 140-CMN-4000 | — | — | 42 | 100-C30 |
| 140-CMN-6300 | — | — | 18 | 100-C43 |
| 140-CMN-9000 | — | — | 10 | 100-C72 |
Accessories
Accessories — Screwless
Notes: 1. See Bulletin 140U for Internal and External Accessories for Bulletin 140M-H, J, L and N frames.
2. Bulletin 140M-I frame Accessories such as auxiliaries, alarms, undervoltage and shunt trips are only available as factory installed modifications. See 140M Factory Modifications (Open).
Internal Control Modules — Field Installed
Terminal Lugs
Terminal Lugs, Continued
140M Factory Modifications (Open)
Note: For modifications add (option code _) for desired features to cat. no. Available in North America only.
| f | ||
| Miscellaneous | ||
| Code | Description | Frame Size |
| KN(1) | Black Lockable Knob | C, D, F, CMN |
| KRY(1) | Red/Yellow Lockable Knob | C, D, F, CMN |
| TE(1) | Spacing Adapter for Self-Protected Starters (Type E) | C, D, F |
| MT | STD Bus Bar Mount, Top | C, D, F, H, CMN |
| MU | STD Bus Bar Mount, Universal | J, K, L |
| g | |||
| Aux / Trip Contacts - C, D, F | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Right Side | ||
| X | Placeholder | X | Placeholder |
| A | 1 N.C. | C | 1 N.O. + 1 N.C. |
| B | 1 N.O. | D | 2 N.O. |
| C | 1 N.O. + 1 N.C. | E | 2 N.C. |
| D | 2 N.O. | K | 1 N.C. (SC+OL) + 1 N.C. (SC) |
| E | 2 N.C. | L | 1 N.O. (SC+OL) + 1 N.O. (SC) |
| R | 1 N.C. + 1 N.O. (SC+OL) | M | 1 N.C. (SC+OL) + 1 N.O. (SC) |
| S | 1 N.O. + 1 N.O. (SC+OL) | N | 1 N.O. (SC+OL) + 1 N.C. (SC) |
| Q | 1 N.O. (SC) + 1 N.C. (SC) | ||
| g | |||
| Aux / Trip Contacts - CMN | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Top Front§ | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | K | 1 N.C. (OL) + 1 N.C. (SC) |
| D | 2 N.O. | L | 1 N.O. (OL) + 1 NO (SC) |
| E | 2 N.C. | M | 1 N.C. (OL) + 1 N.O. (SC) |
| N | 1 N.O. (OL) + 1 N.C. (SC) | ||
§ Cannot be combined with option "h".
| g | |||
| Aux / Trip Contacts - H, J, L | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Right Side | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | ||
| R | 1 N.O. + 1 N.C. (Overload Function) | ||
| F⋆ | 2 N.O. + 2 N.C. | ||
| N⋆ | 1 N.O. (SC+OL) + 1 N.C. (SC) | ||
| T⋆ | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) | ||
⋆ Only available on MCPs.
J- and L-Frame MPCB only.
| g | |||
| Aux / Trip Contacts - I, N | |||
| 1st Code | Description | 2nd Code | Description |
| Left Side | Right Side | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | C | 1 N.O. + 1 N.C. |
| F | 2 N.O. + 2 N.C. | F⋆ | 2 N.O. + 2 N.C. |
| N | 1 N.O. (SC+OL) + 1 N.C. (SC) | N⋆ | 1 N.O. (SC+OL) + 1 N.C. (SC) |
| T | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) | T⋆ | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) |
⋆ Only available on MCPs.
140M Factory Modifications (Open), Continued
Note: For modifications add (option code *) for desired features to cat. no. Available in North America only.
| h | |||
| UV and Shunt Trips - C, D, F | |||
| 1st Code | Description | 2nd Code | Description |
| Left Side | Voltage | ||
| G | Undervoltage Trip | J | 24V AC, 60 Hz |
| P | Shunt Trip | K | 24V AC, 50 Hz |
| D | 120V AC, 60 Hz | ||
| C | 110V AC, 50 Hz | ||
| H | 208V AC, 60 Hz | ||
| F | 220…230V AC, 50 Hz | ||
| A | 240V AC, 60 Hz | ||
| T | 277V AC, 60 Hz | ||
| N | 380…400V AC, 50 Hz | ||
| B | 480V AC, 60 Hz and 415V AC, 50 Hz | ||
| VC | 600V AC, 60 Hz | ||
| M | 575V AC, 60 Hz and 500V AC, 50 Hz | ||
| ZR | 9V DC | ||
| ZQ | 12V DC | ||
| ZJ | 24V DC | ||
| ZW | 36V DC | ||
| ZY | 48V DC | ||
| ZZ | 60V DC | ||
| ZB | 64V DC | ||
| ZG | 72V DC | ||
| ZE | 80V DC | ||
| h | |||
| UV and Shunt Trips - CMN | |||
| 1st Code | Description | 2nd Code | Description |
| Top Front§ | Voltage | ||
| G | Undervoltage Trip | KJ | 24V AC, 60 Hz and 24V AC, 50 Hz |
| P | Shunt Trip | D | 120V AC, 60 Hz and 110V AC, 50 Hz |
| A | 240V AC, 60 Hz and 220…230V AC, 50 Hz | ||
| h | |||
| UV and Shunt Trips - H, J, L | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC/DC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…500V AC | ||
| C | 525…600V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…60V AC/DC |
| D | 110…240V AC/DC | ||
| B | 380…600V AC | ||
| h | |||
| UV and Shunt Trips - I | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…480V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…24V AC/DC |
| D | 48…127V AC and 48…60V DC | ||
| N | 208…380V AC and 110…127V DC | ||
| B | 415…600V AC and 220…250V DC | ||
| h | |||
| UV and Shunt Trips - N | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…480V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…24V AC/DC |
| D | 110…240V AC and 110…125V DC | ||
| N | 380…440V AC and 220…250V DC | ||
| B | 480…600V AC | ||
Specifications
IEC Performance Data
| Cat. No. 140M-C2E- | ||||||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | C20 | C25 | C29 | C32 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1 | 1.6 | 2.5 | 4 | 6.3 | 10 | 16 | 20 | 25 | 29 | 32 |
| Magnetic Release Current | [A] | 2.1 | 3.3 | 5.2 | 8.2 | 13 | 21 | 33 | 52 | 82 | 130 | 208 | 260 | 325 | 406 | 448 |
| Switching of Standard Three-Phase Motors | ||||||||||||||||
| AC-3 | ||||||||||||||||
| 230/240V | [kW] | — | — | 0.06 | 0.09 | 0.18 | 0.25 | 0.37 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 5.5 | 7.5 | 7.5 |
| 400/415V | [kW] | 0.02 | 0.04 | 0.09 | 0.18 | 0.25 | 0.55 | 0.75 | 1.5 | 2.2 | 4.0 | 7.5 | 10 | 11 | 13 | 15 |
| 500V | [kW] | 0.06 | 0.09 | 0.12 | 0.18 | 0.37 | 0.75 | 1.1 | 2.2 | 3.0 | 6.3 | 10 | 11 | 15 | 18.5 | 20 |
| 690V | [kW] | 0.06 | 0.09 | 0.18 | 0.25 | 0.55 | 1.1 | 1.8 | 3.0 | 4.0 | 7.5 | 13 | 17 | 22 | 25 | 25 |
| Back-Up Fuses | ||||||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 100 | 100 | 125 | 125 |
| 400/415V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 100 | 100 | 125 | 125 |
| 440/460V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 63 | 80 | 80 | 80 | 100 | 100 |
| 500V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 80 | 80 | 80 | 100 | 100 |
| 690V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 16 | 20 | 35 | 50 | 50 | 63 | 63 | 63 | 80 | 80 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||||||
| Icu | ||||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 65 | 50 | 50 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 50 | 15 | 15 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 | 3 | 3 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||||||
| Ics | ||||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 50 | 25 | 25 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 15 | 15 | 15 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 | 3 | 3 |
| ⋆ No back-up fuse required. | ||||||||||||||||
| Cat. No. 140M-D8E- | Cat. No. 140M-F8E- | |||||||||||||||
| B25 | B40 | B63 | C10 | C16 | C20 | C25 | C29 | C32 | C10 | C16 | C20 | C25 | C32 | C45 | ||
| Rated Operational Current, Ie | [A] | 2.5 | 4.0 | 6.3 | 10 | 16 | 20 | 25 | 29 | 32 | 10 | 16 | 20 | 25 | 32 | 45 |
| Magnetic Release Current | [A] | 33 | 52 | 82 | 130 | 208 | 260 | 325 | 406 | 448 | 130 | 208 | 260 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | ||||||||||||||||
| AC-3 | ||||||||||||||||
| 230/240V | [kW] | 0.37 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 5.5 | 7.5 | 7.5 | 2.2 | 4.0 | 5.5 | 6.3 | 7.5 | 13 |
| 400/415V | [kW] | 0.75 | 1.5 | 2.2 | 4.0 | 7.5 | 10 | 11 | 13 | 15 | 4.0 | 7.5 | 10 | 11 | 15 | 22 |
| 500V | [kW] | 1.1 | 2.2 | 3.0 | 6.3 | 10 | 11 | 15 | 18.5 | 20 | 6.3 | 10 | 11 | 15 | ||