C-Frame
|
D-Frame
|
F-Frame
|
CMN-Frame
|
I-Frame
|
J-Frame
|
L-Frame
|
| Max. Current Ie
|
32 A
|
32 A
|
45 A
|
90 A
|
205 A
|
250 A
|
630 A
|
| Current Rating
|
0.1…32 A
|
1.6…32 A
|
6.3…45 A
|
16…90 A
|
40…205 A
|
20…250 A
|
100…630 A
|
| Short Circuit Protection
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Standard Magnetic Trip
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| High Magnetic Trip
|
ü
|
ü
|
ü
|
ü
|
—
|
—
|
—
|
| Magnetic Only Trip (MCP)
|
ü
|
ü
|
ü
|
—
|
—
|
ü
|
ü
|
| Overload Protection
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Trip Class
|
10
|
10
|
10
|
10
|
5…20
|
10…30
|
10…30
|
| Standards Compliance:
|
| CSA 22.2, No. 14
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| CSA 22.2, No. 5
|
—
|
—
|
—
|
—
|
ü
|
ü
|
ü
|
| UL 508 (Group Install.)
|
ü (see ratings)
|
ü (see ratings)
|
ü (see ratings)
|
ü (see ratings)
|
—
|
—
|
—
|
| UL 508 Manual, Self Protected (Type E)
|
ü (see ratings)
|
ü (see ratings)
|
ü (see ratings)
|
—
|
—
|
—
|
—
|
| UL 508 (Overload Protection)
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| UL 489
|
—
|
—
|
—
|
—
|
ü
|
ü
|
ü
|
| IEC 60947-1, -2
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| IEC 60947-4-1
|
ü
|
ü
|
ü
|
—
|
ü
|
ü
|
ü
|
| CE
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| ATEX (IEC 60079-14)
|
ü (up to 25 A)
|
ü (up to 25 A)
|
—
|
—
|
—
|
—
|
—
|
| CCC
|
ü (up to 25 A)
|
ü (up to 25 A)
|
ü
|
—
|
—
|
—
|
—
|
| Accessories
|
| Ext. Rotary Operator
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Flex Cable Operator
|
—
|
—
|
—
|
—
|
ü
|
ü
|
ü
|
| Auxiliary Contacts
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Trip Indication Contacts
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
ü
|
|
|