Motor Protection Circuit Breakers and Motor Circuit Protectors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Motor Protection Circuit Breakers and Motor Circuit Protectors > Bulletin 140M Motor Protection Circuit Breakers

Bulletin 140M Motor Protection Circuit Breakers

Introduction Standards Compliance and Certifications Product Line Overview Cat. No. Explanation Wiring Diagrams
Motor Protection Circuit Breakers Application Ratings Accessories Specifications Approximate Dimensions
Motor Protection Circuit Breakers


Click to enlarge - 140M-C2E-C_L Click to enlarge - 140M-D8E_100 Click to enlarge - 140M-F8E_4c Click to enlarge - 140-CMN-9000 Product Shot_BW
Cat. No. 140M-C Cat. No. 140M-D Cat. No. 140M-F Cat. No. 140M-CMN

Rated Operational Current (Ie)
[A]
Motor Current Adjustment Range
[A]
Magnetic Trip Current
[A]
Max. Short Circuit Current [kA] Max. 3-phase Hp Ratings⋆  Max. kW, 3-Phase — AC-3⋆  Cat. No.
400V
(Icu)
480V
(group motor)
200V 230V 460V 575V 230V 400/415V 500V 690V
C-Frame
0.16 0.10…0.16 2.1 100 65 0.02 0.06 0.06 140M-C2E-A16
0.25 0.16…0.25 3.3 100 65 0.04 0.09 0.09 140M-C2E-A25
0.4 0.25…0.40 5.2 100 65 0.25 0.06 0.09 0.12 0.18 140M-C2E-A40
0.63 0.40…0.63 8.2 100 65 0.25 0.33 0.09 0.18 0.18 0.25 140M-C2E-A63
1 0.63…1.0 13 100 65 0.5 0.75 0.18 0.25 0.37 0.55 140M-C2E-B10
1.6 1.0…1.6 21 100 65 0.25 0.33 1 1 0.25 0.55 0.75 1.1 140M-C2E-B16
2.5 1.6…2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-C2E-B25
4 2.5…4.0 52 100 65 1 1 3 3 0.75 1.5 2.2 3 140M-C2E-B40
6.3 4.0…6.3 82 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-C2E-B63
10 6.3…10 130 100 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-C2E-C10
16 10…16 208 65 30 5 5 10 15 4 7.5 10 13 140M-C2E-C16
20 14.5…20 260 50 30 5 7.5 15 20 5.5 10 11 17 140M-C2E-C20
25 18…25 325 15 25 7.5 7.5 20 20 5.5 11 15 22 140M-C2E-C25
29 24…29 406 15 25 7.5 10 20 25 7.5 13 18.5 25 140M-C2E-C29
32 27…32 448 15 25 7.5 10 25 30 7.5 15 20 25 140M-C2E-C32
D-Frame
2.5 1.6…2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-D8E-B25
4 2.5…4.0 52 100 65 1 1 3 3 0.75 1.5 2.2 3 140M-D8E-B40
6.3 4.0…6.3 82 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-D8E-B63
10 6.3…10 130 100 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-D8E-C10
16 10…16 208 100 65 5 5 10 15 4 7.5 10 13 140M-D8E-C16
20 14.5…20 260 100 65 5 7.5 15 20 5.5 10 11 17 140M-D8E-C20
25 18…25 325 65 30 7.5 7.5 20 20 5.5 11 15 22 140M-D8E-C25
29 24…29 406 50 30 7.5 10 20 25 7.5 13 18.5 25 140M-D8E-C29
32 27…32 448 50 30 7.5 10 25 30 7.5 15 20 25 140M-D8E-C32
F-Frame
10 6.3…10 130 100 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-F8E-C10
16 10…16 208 100 65 5 5 10 15 4 7.5 10 13 140M-F8E-C16
20 14.5…20 260 100 65 5 7.5 15 20 5.5 10 11 17 140M-F8E-C20
25 18…25 325 100 65 7.5 10 20 25 6.3 11 15 22 140M-F8E-C25
32 23…32 416 65 65 7.5 10 25 30 7.5 15 20 30 140M-F8E-C32
45 32…45 585 65 65 10 15 30 40 13 22 30 40 140M-F8E-C45
CMN-Frame
25 16…25 350 65 65 5 7.5 15 20 7.5 13 15 22 140-CMN-2500
40 25…40 560 65 65 10 10 30 30 11 22 25 30 140-CMN-4000
63 40…63 882 65 42 20 20 40 60 20 32 40 55 140-CMN-6300
90 63…90 1260 50 35 25 30 60 75 25 45 55 75 140-CMN-9000
  
⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current.

Motor Protection Circuit Breakers


Click to enlarge - 140M-5-9 Click to enlarge - 140M-J (MPCB) Click to enlarge - 140M-L(MPCB)
Cat. No. 140M-I Cat. No. 140M-J Cat. No. 140M-L

Rated Operational Current (Ie)
[A]
Motor Current Adjustment Range
[A]
Magnetic Trip Current
[A]
Ultimate
Interrupting
Current [kA] (Icm)
3-phase Hp Ratings⋆  Max. kW, 3-Phase — AC-3⋆  Cat. No.
400V 480V 200V 230V 460V 575V 230V 400/415V 500V 690V
I-Frame
80 40…80 1200 70‡  65 25 30 60 75 22 37 55 75 140M-I8E-C80‡ § 
100 80…100 1500 70‡  65 30 40 75 100 30 55 55 90 140M-I8E-D10‡ § 
160 100…160 2400 70‡  65 50 60 125 150 45 75 110 132 140M-I8E-D16‡ § 
205 160…205 2665 70‡  65 60 75 150 200 55 110 132 200 140M-I8E-D20‡ ♣ 
J-Frame
50 20…50 700 25 25 25 30 60 75 15 22 30 45 140M-J2E-C50
100 40…100 1400 25 25 30 40 75 100 30 55 55 90 140M-J2E-D10
160 64…160 2240 25 25 50 60 125 150 45 90 110 160 140M-J2E-D16
250 100…250 3500 25 25 75 100 200 250 55 132 160 250 140M-J2E-D25
  
50 20…50 700 70 65 25 30 60 75 15 22 30 45 140M-J8E-C50
100 40…100 1400 70 65 30 40 75 100 30 55 55 90 140M-J8E-D10
160 64…160 2240 70 65 50 60 125 150 45 90 110 160 140M-J8E-D16
250 100…250 3500 70 65 75 100 200 250 55 132 160 250 140M-J8E-D25
L-Frame
250 100…250 3000 40 35 75 100 200 250 55 132 160 250 140M-L2E-D25
400 160…400 4800 40 35 125 150 300 400 132 200 250 400 140M-L2E-D40
630 250…630 7580 40 35 200 250 500 600 200 355 450 630 140M-L2E-D63
  
250 100…250 3000 70 65 75 100 200 250 55 132 160 250 140M-L8E-D25
400 160…400 4800 70 65 150 150 350 450 132 200 250 400 140M-L8E-D40
630 250…630 7560 70 65 200 250 500 600 200 355 450 630 140M-L8E-D63
  
⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current.
‡ For IEC approvals and CE marking, add an "E" to the end of the Cat. No. Example: 140M-18E-C80E.
§ Overload Protection — adjustable Trip Class 5, 10, 15, or 20.
♣ Overload Protection — fixed Trip Class 10.

High Inrush Motor Protection Circuit Breakers


Click to enlarge - 140M-C2E-C_L Click to enlarge - 140M-D8E_100 Click to enlarge - 140M-F8E_4c
Cat. No. 140M-C Cat. No. 140M-D Cat. No. 140M-F

Rated Operational Current (Ie)
[A]
Motor Current Adjustment Range
[A]
Magnetic Trip Current
[A]
Max. Short Circuit Current [kA] Max. 3-phase Hp Ratings⋆  Max kW, 3-Phase — AC-3⋆  Cat. No.
400V
(Icu)
480V
(group motor)
200V 230V 460V 575V 230V 400/415V 500V 690V
C-Frame
0.16 0.10…0.16 3.3 100 65 0.02 0.06 0.06 140M-C2T-A16
0.25 0.16…0.25 5.2 100 65 0.04 0.09 0.09 140M-C2T-A25
0.4 0.25…0.40 8.2 100 65 0.25 0.06 0.09 0.12 0.18 140M-C2T-A40
0.63 0.40…0.63 13 100 65 0.25 0.33 0.09 0.18 0.18 0.25 140M-C2T-A63
1 0.63…1.0 21 100 65 0.5 0.75 0.18 0.25 0.37 0.55 140M-C2T-B10
1.6 1.0…1.6 33 100 65 0.25 0.33 1 1 0.25 0.55 0.75 1.1 140M-C2T-B16
2.5 1.6…2.5 52 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-C2T-B25
4 2.5…4 82 100 65 1 1 3 3 0.75 1.5 2.2 3 140M-C2T-B40
6.3 4…6.3 130 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-C2T-B63
10 6.3…10 208 100 30 3 3 7.5 10 2.2 4 6.3 7.5 140M-C2T-C10
16 10…16 260 50 30 5 5 10 15 4 7.5 10 13 140M-C2T-C16
D-Frame
16 10…16 260 100 65 5 5 10 15 4 7.5 10 13 140M-D8T-C16
20 14.5…20 325 65 30 5 7.5 15 20 5.5 10 11 17 140M-D8T-C20
F-Frame
25 18…25 416 65 65 7.5 10 20 25 6.3 11 15 22 140M-F8T-C25
32 23…32 585 65 65 7.5 10 25 30 7.5 15 20 30 140M-F8T-C32
  
⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current.

Motor Protection Circuit Breakers — Screwless


Click to enlarge - 140M-RC2E-C16 Product Shot_BW


Rated Operational Current (Ie)
[A]
Motor Current Adjustment Range
[A]
Magnetic Trip Current
[A]
Max. Short Circuit Current [kA] Max. 3-phase Hp Ratings⋆  Max. kW, 3-Phase — AC-3⋆  Cat. No.
400V
(Icu)
480V
(group motor)
200V 230V 460V 575V 230V 400/415V 500V 690V
C-Frame
0.16 0.10…0.16 2.1 100 65 0.02 0.06 0.06 140M-RC2E-A16
0.25 0.16…0.25 3.3 100 65 0.04 0.09 0.09 140M-RC2E-A25
0.4 0.25…0.40 5.2 100 65 0.25 0.06 0.09 0.12 0.18 140M-RC2E-A40
0.63 0.40…0.63 8.2 100 65 0.25 0.33 0.09 0.18 0.18 0.25 140M-RC2E-A63
1 0.63…1.0 13 100 65 0.5 0.75 0.18 0.25 0.37 0.55 140M-RC2E-B10
1.6 1.0…1.6 21 100 65 0.25 0.33 1 1 0.25 0.55 0.75 1.1 140M-RC2E-B16
2.5 1.6…2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-RC2E-B25
4 2.5…4.0 52 100 65 1 1 3 3 0.75 1.5 2.2 3.0 140M-RC2E-B40
6.3 4.0…6.3 82 100 65 1.5 2 5 5 1.5 2.2 3.0 4.0 140M-RC2E-B63
10 6.3…10 130 100 65 3 3 7.5 10 2.2 4.0 6.3 7.5 140M-RC2E-C10
16 10…16 208 65 30 5 5 10 15 4.0 7.5 10 13 140M-RC2E-C16
  
⋆ Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current.