Motor Protection Circuit Breakers and Motor Circuit Protectors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Motor Protection Circuit Breakers and Motor Circuit Protectors > Bulletin 140M Application Ratings, Accessories, Specifications, and Approximate Dimensions

Bulletin 140M Application Ratings, Accessories, Specifications, and Approximate Dimensions

Application Ratings Accessories Specifications Approximate Dimensions
Application Ratings

UL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only

Cat. No. UL 508 — Manual Motor Controller UL 508 Self-Protected
(Type E) Combination
Motor Controller
UL 489 Inverse Time
C.B. w/UL 508 Motor Overload Protection
Max. Fuse or C.B. per NEC Group Motor Installation Motor Disconnect Tap Conductor Protection
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Max. Short Circuit Current [kA]
480V 600V 480V 600V 480V 600V 480Y/277V§  600Y/347V§  480V 600V
C-Frame
140M-C2E-A16 450 65 47 65 47 65 47 65 47
140M-C2E-A25 450 65 47 65 47 65 47 65 47
140M-C2E-A40 450 65 47 65 47 65 47 65 47
140M-C2E-A63 450 65 47 65 47 65 47 65 47
140M-C2E-B10 450 65 47 65 47 65 47 65 47
140M-C2E-B16 450 65 47 65 47 65 47 65 47
140M-C2E-B25 450 65 30 65 30 65 30 65 30
140M-C2E-B40 450 65 25 65 25 65 25 65 25
140M-C2E-B63 450 65 30 65 30 65 65
140M-C2E-C10 450 65 30 65 30 65 65
140M-C2E-C16 450 30 30 30 30 30 30
140M-C2E-C20 450 30 30 10 10 10 10
140M-C2E-C25 450 25 10 10 5
140M-C2E-C29 450 25 30 10
140M-C2E-C32 450 25 30 10
D-Frame
140M-D8E-B25 450 65 30 65 30 65 30 65 30
140M-D8E-B40 450 65 30 65 30 65 30 65 30
140M-D8E-B63 450 65 30 65 30 65 30 65 30
140M-D8E-C10 450 65 30 65 30 65 30 65 30
140M-D8E-C16 450 65 30 65 30 65 30 65 30
140M-D8E-C20 450 65 30 65 30 65 65
140M-D8E-C25 450 30 30 30 30 30 30
140M-D8E-C29 450 30 30 30 18
140M-D8E-C32 450 30 30 30 18
F-Frame
140M-F8E-C10 600 65 30 65 30 65 30 65 30
140M-F8E-C16 600 65 30 65 30 65 30 65 30
140M-F8E-C20 600 65 30 65 30 65 30 65 30
140M-F8E-C25 600 65 30 65 30 65 30 65 30
140M-F8E-C32 600 65 30 65 30 65 30 65 30
140M-F8E-C45 600 65 18 65 18 65 65
CMN-Frame
140-CMN-2500 1000 65 42
140-CMN-4000 1000 65 42
140-CMN-6300 1000 42 18
140-CMN-9000 1000 35 10
I-Frame
140M-I8E-C80 65 30
140M-I8E-D10 65 30
140M-I8E-D16 65 30
140M-I8E-D20 65 30
J-Frame
140M-J2E-C50 25 18
140M-J2E-D10 25 18
140M-J2E-D16 25 18
140M-J2E-D25 25 18
140M-J8E-C50 65 25
140M-J8E-D10 65 25
140M-J8E-D16 65 25
140M-J8E-D25 65 25
L-Frame
140M-L2E-D25 25 18
140M-L2E-D40 25 18
140M-L2E-D63 25 18
140M-L8E-D25 65 35
140M-L8E-D40 65 35
140M-L8E-D63 65 35
  
§  For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

Cat. No. UL 508 Manual Motor Controller UL 508 Self-Protected
(Type E) Combination
Motor Controller
Max. Fuse or C.B. per NEC Group Motor Installation Motor Disconnect Tap Conductor Protection
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Max. Short Circuit Current [kA]
480V 600V 480V 600V 480V 600V 480Y/277V§  600Y/347V§ 
C-Frame
140M-C2T-A16 450 65 47 65 47 65 47 65 47
140M-C2T-A25 450 65 47 65 47 65 47 65 47
140M-C2T-A40 450 65 47 65 47 65 47 65 47
140M-C2T-A63 450 65 47 65 47 65 47 65 47
140M-C2T-B10 450 65 47 65 47 65 47 65 47
140M-C2T-B16 450 65 47 65 47 65 30 65 30
140M-C2T-B25 450 65 25 65 25 65 25 65 25
140M-C2T-B40 450 65 30 65 30 65 65
140M-C2T-B63 450 65 30 65 30 65 65
140M-C2T-C10 450 30 30 30 30 30 30
140M-C2T-C16 450 30 30 10 10 10 10
D-Frame
140M-D8T-C16 450 65 30 65 30 65 30 65 30
140M-D8T-C20 450 30 30 30 30 30 30
F-Frame
140M-F8T-C25 600 65 30 65 30 65 30 65 30
140M-F8T-C32 600 65 18 65 18 65 18 65 18
  
§  For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

UL Listed Application Ratings — Motor Circuit Protectors Only♣ 

Cat. No. UL 508 Manual Motor Controller UL 489 Instantaneous Trip Circuit Breaker (Magnetic Only)
Max. Fuse or C.B. per NEC Group Motor Installation Motor Disconnect Motor Circuit Protector
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Max. Short Circuit Current [kA]§ 
480V 600V 480V 600V 480V 600V
C-Frame
140M-C2N-A16 450 65 47 65 47
140M-C2N-A25 450 65 47 65 47
140M-C2N-A40 450 65 47 65 47
140M-C2N-A63 450 65 47 65 47
140M-C2N-B10 450 65 47 65 47
140M-C2N-B16 450 65 47 65 47
140M-C2N-B25 450 65 30 65 30
D-Frame
140M-D8N-B25 450 65 30 65 30
140M-D8N-B40 450 65 30 65 30
140M-D8N-B63 450 65 30 65 30
140M-D8N-C10 450 65 30 65 30
140M-D8N-C16 450 65 30 65 30
140M-D8N-C25 450 30 30 30 30
140M-D8N-C32 450 30 30 30 18
F-Frame
140M-F8N-C25 600 65 30 65 30
140M-F8N-C32 600 65 30 65 30
140M-F8N-C45 600 65 18 65 18
H-Frame
140M-H8P-B30 65 30
140M-H8P-B70 65 30
140M-H8P-C15 65 30
140M-H8P-C30 65 30
140M-H8P-C50 65 30
140M-H8P-C70 65 30
140M-H8P-D10 65 30
140M-H8R-D10 65 30
J-Frame
140M-J8P-C70 65 30
140M-J8P-C90 65 30
140M-J8P-D10 65 30
140M-J8P-D12 65 30
140M-J8P-D15 65 30
140M-J8P-D17 65 30
140M-J8P-D20 65 30
140M-J8P-D22 65 30
140M-J8P-D25 65 30
L-Frame
140M-L8P-D22 65 30
140M-L8P-D25 65 30
140M-L8P-D30 65 30
140M-L8P-D35 65 30
140M-L8P-D40 65 30
140M-L8P-D45 65 30
140M-L8P-D50 65 30
140M-L8P-D60 65 30
N-Frame
140M-N8P-D80 65 35
140M-N8P-E12 65 35
  
♣ Separate overload protection is required.
§ The interrupting rating for MCPs is dependent upon the controller used. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information.

UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-K Contactors

Cat. No. UL 508 Manual Motor Controller UL 508 Type F
Combination
Motor Controller
UL 508 Type E
Self-Protected Combination
Motor Controller
Max. Fuse or C.B. per NEC Minimum Contactor Size Group Motor Installation Motor Disconnect
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Minimum Contactor Size Max. Short Circuit Current [kA] Minimum Contactor Size Max. Short Circuit Current [kA]
480V 600V 480V 600V 480Y/277V♣  600Y/347V♣  480Y/277V♣  600Y/347V♣ 
C-Frame
140M-C2E-A16 450 100-K05 65 47 65 47 100-K05 65 47
140M-C2E-A25 450 100-K05 65 47 65 47 100-K05 65 47
140M-C2E-A40 450 100-K05 65 47 65 47 100-K05 65 47
140M-C2E-A63 450 100-K05 65 47 65 47 100-K05 65 47
140M-C2E-B10 450 100-K05 65 47 65 47 100-K05 65 47
140M-C2E-B16 450 100-K05 65 47 65 47 100-K05 65 47
140M-C2E-B25 450 100-K05 65 30 65 30 100-K05 65 30
140M-C2E-B40 450 100-K05 65 30 65 30 100-K05 65 30
140M-C2E-B63 450 100-K05 65 30 65 30 100-K05 65
140M-C2E-C10 450 100-K09 65 30 65 30 100-K09 65
140M-C2E-C16 450 100-K12 30 30 30 30 100-K12 30
D-Frame
140M-D8E-B25 450 100-K05 65 30 65 30 100-K05 65 30
140M-D8E-B40 450 100-K05 65 30 65 30 100-K05 65 30
140M-D8E-B63 450 100-K05 65 30 65 30 100-K05 65 30
140M-D8E-C10 450 100-K09 65 30 65 30 100-K09 65 30
140M-D8E-C16 450 100-K12 65 30 65 30 100-K12 65 30
  
♣ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-C Contactors

Cat. No. UL 508 Manual Motor Controller UL 508 Type F
Combination
Motor Controller
UL 508 Type E
Self-Protected Combination
Motor Controller
Max. Fuse or C.B. per NEC Minimum Contactor Size Group Motor Installation Motor Disconnect
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Minimum Contactor Size Max. Short Circuit Current [kA] Minimum Contactor Size Max. Short Circuit Current [kA]
480V 600V 480V 600V 480Y/277V♣  600Y/347V♣  480Y/277V♣  600Y/347V♣ 
C-Frame
140M-C2E-A16 450 100-C09 65 47 65 47 100-C09 65 47 100-C09 65 47
140M-C2E-A25 450 100-C09 65 47 65 47 100-C09 65 47 100-C09 65 47
140M-C2E-A40 450 100-C09 65 47 65 47 100-C09 65 47 100-C09 65 47
140M-C2E-A63 450 100-C09 65 47 65 47 100-C09 65 47 100-C09 65 47
140M-C2E-B10 450 100-C09 65 47 65 47 100-C09 65 47 100-C09 65 47
140M-C2E-B16 450 100-C09 65 47 65 47 100-C09 65 47 100-C09 65 47
140M-C2E-B25 450 100-C09 65 30 65 30 100-C09 65 30 100-C09 65 30
140M-C2E-B40 450 100-C09 65 30 65 30 100-C09 65 30 65 25
140M-C2E-B63 450 100-C09 65 30 65 30 100-C09 65 65
140M-C2E-C10 450 100-C09 65 30 65 30 100-C09 65 65
140M-C2E-C16 450 100-C12 30 30 30 25 100-C12 30 30
140M-C2E-C20 450 100-C16 30 30 30 30 100-C23 10 10
140M-C2E-C25 450 100-C23 30 30 10 10
450 100-C30 30 30 30 30
140M-C2E-C29 450 100-C30 30 30 10 10
140M-C2E-C32 450 100-C37 30 30 10 10
D-Frame
140M-D8E-B25 450 100-C09 65 30 65 30 100-C09 65 30 100-C09 65 30
100-C23 65 30
140M-D8E-B40 450 100-C09 65 30 65 30 100-C09 65 30 100-C23 65 30
140M-D8E-B63 450 100-C09 65 30 65 30 100-C09 65 30 100-C30 65 30
140M-D8E-C10 450 100-C09 65 30 65 30 100-C09 65 30 100-C30 65 30
140M-D8E-C16 450 100-C12 65 30 65 30 100-C12 65 30 100-C30 65 30
140M-D8E-C20 450 100-C23 65 30 65 30 100-C23 65 100-C30 65
140M-D8E-C25 450 100-C23 65 30 65 30 100-C23 30 100-C30 30
140M-D8E-C29 450 100-C30 65 30 65 10
140M-D8E-C32 450 100-C37 65 30 65 10
F-Frame
140M-F8E-C10 600 100-C30 65 30 65 30 100-C30 65 30 100-C30 65 30
140M-F8E-C16 600 100-C30 65 30 65 30 100-C30 65 30 100-C30 65 30
140M-F8E-C20 600 100-C30 65 30 65 30 100-C30 65 30 100-C30 65 30
140M-F8E-C25 600 100-C30 65 30 65 30 100-C30 65 30 100-C30 65 30
140M-F8E-C32 600 100-C30 65 30 65 30 100-C30 65 30 100-C30 65 30
140M-F8E-C45 600 100-C37 65 18 65 18 100-C37 65 100-C37 65
CMN-Frame
140-CMN-2500 1000 100-C16 65 42
140-CMN-4000 1000 100-C30 65 42
140-CMN-6300 1000 100-C43 42 18
140-CMN-9000 1000 100-C72 35 10
  
♣ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

UL Listed Application Ratings - Motor Circuit Protectors with Bulletin 100-C Contactors♣ 

Cat. No. UL 508 Manual Motor Controller UL 508 Type E (Self-Protected) Combination Motor Controller
Max. Fuse or C.B. per NEC Minimum Contactor Size Group Motor Installation Motor Disconnect
Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Minimum Contactor Size Max. Short Circuit Current [kA] Max. Short Circuit Current [kA]
480V 600V 480V 600V 480Y/277V‡  600Y/347V‡ 
C-Frame
140M-C2N-A16 450 100-C09 65 47 65 47 100-C09 65 47
140M-C2N-A25 450 100-C09 65 47 65 47 100-C09 65 47
140M-C2N-A40 450 100-C09 65 47 65 47 100-C09 65 47
140M-C2N-A63 450 100-C09 65 47 65 47 100-C09 65 47
140M-C2N-B10 450 100-C09 65 47 65 47 100-C09 65 47
140M-C2N-B16 450 100-C09 65 47 65 47 100-C09 65 47
140M-C2N-B25 450 100-C09 65 30 65 30 100-C09 65
D-Frame
140M-D8N-B25 450 100-C09 65 30 65 30 100-C09 65
100-C23 65 30
140M-D8N-B40 450 100-C09 65 30 65 30 100-C23 65 30
140M-D8N-B63 450 100-C09 65 30 65 30 100-C30 65 30
140M-D8N-C10 450 100-C09 65 30 65 30 100-C30 65 30
140M-D8N-C16 450 100-C12 65 30 65 30 100-C30 65 30
140M-D8N-C25 450 100-C23 30 30 30 30 100-C30 65
140M-D8N-C32 450 100-C37 65 10 65 10
F-Frame
140M-F8N-C25 600 100-C23 65 30 65 30 100-C30 65 30
140M-F8N-C32 600 100-C30 65 30 65 30 100-C30 65 30
140M-F8N-C45 600 100-C37 65 18 65 18 100-C37 65
  
♣ Separate overload protection is required.
‡ For full-voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications.

Definition of Type 2 Short Circuit Coordination:


In the event of short circuit, fast-opening, current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical, fully short-circuit coordinated starter combinations with Type 2 coordination.

Type 2 Coordination 400V

Cat. No. Max. Short Circuit Current [kA] For Use With Contactors Below (or larger)
Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 400V
C-Frame
140M-C2E-A16 140M-C2N-A16 100 100-C09
140M-C2E-A25 140M-C2T-A16 140M-C2N-A25 100 100-C09
140M-C2E-A40 140M-C2T-A25 140M-C2N-A40 100 100-C09
140M-C2E-A63 140M-C2T-A40 140M-C2N-A63 100 100-C09
140M-C2E-B10 140M-C2T-A63 140M-C2N-B10 100 100-C09
140M-C2E-B16 140M-C2T-B10 140M-C2N-B16 100 100-C09
140M-C2E-B25 140M-C2T-B16 140M-C2N-B25 50 100-C09
140M-C2E-B40 140M-C2T-B25 50 100-C09
140M-C2E-B63 140M-C2T-B40 50 100-C09
140M-C2E-C10 140M-C2T-B63 50 100-C09
140M-C2E-C16 140M-C2T-C10 50 100-C12⋆ 
140M-C2E-C20 140M-C2T-C16 50 100-C23
140M-C2E-C25 15 100-C30
140M-C2E-C29 15 100-C30
140M-C2E-C32 15 100-C37
D-Frame
140M-D8E-B25 140M-D8N-B25 100 100-C09
140M-D8E-B40 140M-D8N-B40 100 100-C09
140M-D8E-B63 140M-D8N-B63 100 100-C09
140M-D8E-C10 140M-D8N-C10 65 100-C09
140M-D8E-C16 140M-D8N-C16 65 100-C12
140M-D8E-C20 140M-D8T-C16 65 100-C23
140M-D8E-C25 140M-D8T-C20 140M-D8N-C25 50 100-C23
140M-D8E-C29 65 100-C30
140M-D8E-C32 140M-D8N-C32 65 100-C37
F-Frame
140M-F8E-C10 100 100-C09
140M-F8E-C16 100 100-C12
140M-F8E-C20 100 100-C23
140M-F8E-C25 140M-F8N-C25 100 100-C30
140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 100 100-C30
140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 100 100-C37
CMN-Frame
140-CMN-2500 65 100-C16
140-CMN-4000 65 100-C30
140-CMN-6300 42 100-C43
140-CMN-9000 35 100-C72
  
⋆ Cat. No. 100-C16 contactors Type 1 only

Type 2 Coordination 480V

Cat. No. Max. Short Circuit Current [kA] For Use With Contactors Below (or larger)
Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 480V
C-Frame
140M-C2E-A16 140M-C2N-A16 65 100-C09
140M-C2E-A25 140M-C2T-A16 140M-C2N-A25 65 100-C09
140M-C2E-A40 140M-C2T-A25 140M-C2N-A40 65 100-C09
140M-C2E-A63 140M-C2T-A40 140M-C2N-A63 65 100-C09
140M-C2E-B10 140M-C2T-A63 140M-C2N-B10 65 100-C09
140M-C2E-B16 140M-C2T-B10 140M-C2N-B16 65 100-C09
140M-C2E-B25 140M-C2T-B16 140M-C2N-B25 50 100-C16
140M-C2E-B40 140M-C2T-B25 50 100-C30
140M-C2E-B63 140M-C2T-B40 50 100-C30
140M-C2E-C10 140M-C2T-B63 50 100-C30
140M-C2E-C16 140M-C2T-C10 10 100-C30
140M-C2E-C20 140M-C2T-C16 10 100-C30
140M-C2E-C25 10 100-C30
140M-C2E-C29 10 100-C30
140M-C2E-C32 10 100-C37
D-Frame
140M-D8E-B25 140M-D8N-B25 65 100-C09
140M-D8E-B40 140M-D8N-B40 65 100-C09
140M-D8E-B63 140M-D8N-B63 65 100-C09
140M-D8E-C10 140M-D8N-C10 65 100-C09
140M-D8E-C16 140M-D8N-C16 65 100-C12
140M-D8E-C20 140M-D8T-C16 65 100-C23
140M-D8E-C25 140M-D8T-C20 140M-D8N-C25 65 100-C23
140M-D8E-C29 65 100-C30
140M-D8E-C32 140M-D8N-C32 65 100-C37
F-Frame
140M-F8E-C10 65 100-C09
140M-F8E-C16 65 100-C12
140M-F8E-C20 65 100-C23
140M-F8E-C25 140M-F8N-C25 65 100-C30
140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 65 100-C30
140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 65 100-C37
CMN-Frame
140-CMN-2500 65 100-C16
140-CMN-4000 65 100-C30
140-CMN-6300 42 100-C43
140-CMN-9000 35 100-C72
  

Type 2 Coordination 600V

Cat. No. Max. Short Circuit Current [kA] For Use With Contactors Below (or larger)
Standard Motor Protection High Inrush Motor Protection Motor Circuit Protection 600V
C-Frame
140M-C2E-A16 140M-C2N-A16 47 100-C09
140M-C2E-A25 140M-C2T-A16 140M-C2N-A25 47 100-C09
140M-C2E-A40 140M-C2T-A25 140M-C2N-A40 47 100-C09
140M-C2E-A63 140M-C2T-A40 140M-C2N-A63 47 100-C09
140M-C2E-B10 140M-C2T-A63 140M-C2N-B10 47 100-C09
140M-C2E-B16 140M-C2T-B10 140M-C2N-B16 47 100-C09
140M-C2E-B25 140M-C2T-B16 140M-C2N-B25 10 100-C16
140M-C2E-B40 140M-C2T-B25 10 100-C16
140M-C2E-B63 140M-C2T-B40 5 100-C23
140M-C2E-C10 140M-C2T-B63 5 100-C30
140M-C2E-C16 140M-C2T-C10 5 100-C30
140M-C2E-C20 140M-C2T-C16 5 100-C30
140M-C2E-C25 5 100-C30
140M-C2E-C29 5 100-C30
140M-C2E-C32 5 100-C37
D-Frame
140M-D8E-B25 140M-D8N-B25 30 100-C30
140M-D8E-B40 140M-D8N-B40 30 100-C30
140M-D8E-B63 140M-D8N-B63 30 100-C30
140M-D8E-C10 140M-D8N-C10 30 100-C30
140M-D8E-C16 140M-D8N-C16 30 100-C30
140M-D8E-C20 140M-D8T-C16 5 100-C30
140M-D8E-C25 140M-D8T-C20 140M-D8N-C25 5 100-C30
140M-D8E-C29 10 100-C30
140M-D8E-C32 140M-D8N-C32 10 100-C37
F-Frame
140M-F8E-C10 30 100-C30
140M-F8E-C16 30 100-C30
140M-F8E-C20 30 100-C30
140M-F8E-C25 140M-F8N-C25 30 100-C30
140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 30 100-C30
140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 10 100-C37
CMN-Frame
140-CMN-2500 42 100-C16
140-CMN-4000 42 100-C30
140-CMN-6300 18 100-C43
140-CMN-9000 10 100-C72