Bulletin 140M Application Ratings, Accessories, Specifications, and Approximate Dimensions
Application RatingsUL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only
| Cat. No. | UL 508 — Manual Motor Controller | UL 508 Self-Protected (Type E) Combination Motor Controller |
UL 489 Inverse Time C.B. w/UL 508 Motor Overload Protection |
||||||||
| Max. Fuse or C.B. per NEC | Group Motor Installation | Motor Disconnect | Tap Conductor Protection | ||||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | |||||||
| 480V | 600V | 480V | 600V | 480V | 600V | 480Y/277V§ | 600Y/347V§ | 480V | 600V | ||
| C-Frame | |||||||||||
| 140M-C2E-A16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A25 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A40 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-A63 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B10 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2E-B25 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-C2E-B40 | 450 | 65 | 25 | 65 | 25 | 65 | 25 | 65 | 25 | — | — |
| 140M-C2E-B63 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-C2E-C10 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-C2E-C16 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — | — | — |
| 140M-C2E-C20 | 450 | 30 | 30 | 10 | 10 | 10 | — | 10 | — | — | — |
| 140M-C2E-C25 | 450 | 25 | 10 | 10 | 5 | — | — | — | — | — | — |
| 140M-C2E-C29 | 450 | 25 | 30 | 10 | — | — | — | — | — | — | — |
| 140M-C2E-C32 | 450 | 25 | 30 | 10 | — | — | — | — | — | — | — |
| D-Frame | |||||||||||
| 140M-D8E-B25 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-B40 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-B63 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C10 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C16 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8E-C20 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — | — | — |
| 140M-D8E-C25 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — | — | — |
| 140M-D8E-C29 | 450 | 30 | 30 | 30 | 18 | — | — | — | — | — | — |
| 140M-D8E-C32 | 450 | 30 | 30 | 30 | 18 | — | — | — | — | — | — |
| F-Frame | |||||||||||
| 140M-F8E-C10 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C16 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C20 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C25 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C32 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8E-C45 | 600 | 65 | 18 | 65 | 18 | 65 | — | 65 | — | — | — |
| CMN-Frame | |||||||||||
| 140-CMN-2500 | 1000 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-4000 | 1000 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-6300 | 1000 | 42 | 18 | — | — | — | — | — | — | — | — |
| 140-CMN-9000 | 1000 | 35 | 10 | — | — | — | — | — | — | — | — |
| I-Frame | |||||||||||
| 140M-I8E-C80 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D10 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D16 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| 140M-I8E-D20 | — | — | — | — | — | — | — | — | — | 65 | 30 |
| J-Frame | |||||||||||
| 140M-J2E-C50 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D10 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D16 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J2E-D25 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-J8E-C50 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D10 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D16 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| 140M-J8E-D25 | — | — | — | — | — | — | — | — | — | 65 | 25 |
| L-Frame | |||||||||||
| 140M-L2E-D25 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L2E-D40 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L2E-D63 | — | — | — | — | — | — | — | — | — | 25 | 18 |
| 140M-L8E-D25 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| 140M-L8E-D40 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| 140M-L8E-D63 | — | — | — | — | — | — | — | — | — | 65 | 35 |
| § For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||||
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Self-Protected (Type E) Combination Motor Controller |
|||||||
| Max. Fuse or C.B. per NEC | Group Motor Installation | Motor Disconnect | Tap Conductor Protection | ||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | ||||||
| 480V | 600V | 480V | 600V | 480V | 600V | 480Y/277V§ | 600Y/347V§ | ||
| C-Frame | |||||||||
| 140M-C2T-A16 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A25 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A40 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-A63 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-B10 | 450 | 65 | 47 | 65 | 47 | 65 | 47 | 65 | 47 |
| 140M-C2T-B16 | 450 | 65 | 47 | 65 | 47 | 65 | 30 | 65 | 30 |
| 140M-C2T-B25 | 450 | 65 | 25 | 65 | 25 | 65 | 25 | 65 | 25 |
| 140M-C2T-B40 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — |
| 140M-C2T-B63 | 450 | 65 | 30 | 65 | 30 | 65 | — | 65 | — |
| 140M-C2T-C10 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — |
| 140M-C2T-C16 | 450 | 30 | 30 | 10 | 10 | 10 | — | 10 | — |
| D-Frame | |||||||||
| 140M-D8T-C16 | 450 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 |
| 140M-D8T-C20 | 450 | 30 | 30 | 30 | 30 | 30 | — | 30 | — |
| F-Frame | |||||||||
| 140M-F8T-C25 | 600 | 65 | 30 | 65 | 30 | 65 | 30 | 65 | 30 |
| 140M-F8T-C32 | 600 | 65 | 18 | 65 | 18 | 65 | 18 | 65 | 18 |
| § For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||
UL Listed Application Ratings — Motor Circuit Protectors Only♣
| Cat. No. | UL 508 Manual Motor Controller | UL 489 Instantaneous Trip Circuit Breaker (Magnetic Only) | |||||
| Max. Fuse or C.B. per NEC | Group Motor Installation | Motor Disconnect | Motor Circuit Protector | ||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA]§ | |||||
| 480V | 600V | 480V | 600V | 480V | 600V | ||
| C-Frame | |||||||
| 140M-C2N-A16 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A25 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A40 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-A63 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B10 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B16 | 450 | 65 | 47 | 65 | 47 | — | — |
| 140M-C2N-B25 | 450 | 65 | 30 | 65 | 30 | — | — |
| D-Frame | |||||||
| 140M-D8N-B25 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-B40 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-B63 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C10 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C16 | 450 | 65 | 30 | 65 | 30 | — | — |
| 140M-D8N-C25 | 450 | 30 | 30 | 30 | 30 | — | — |
| 140M-D8N-C32 | 450 | 30 | 30 | 30 | 18 | — | — |
| F-Frame | |||||||
| 140M-F8N-C25 | 600 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8N-C32 | 600 | 65 | 30 | 65 | 30 | — | — |
| 140M-F8N-C45 | 600 | 65 | 18 | 65 | 18 | — | — |
| H-Frame | |||||||
| 140M-H8P-B30 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-B70 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C15 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C30 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C50 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-C70 | — | — | — | — | — | 65 | 30 |
| 140M-H8P-D10 | — | — | — | — | — | 65 | 30 |
| 140M-H8R-D10 | — | — | — | — | — | 65 | 30 |
| J-Frame | |||||||
| 140M-J8P-C70 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-C90 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D10 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D12 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D15 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D17 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D20 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D22 | — | — | — | — | — | 65 | 30 |
| 140M-J8P-D25 | — | — | — | — | — | 65 | 30 |
| L-Frame | |||||||
| 140M-L8P-D22 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D25 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D30 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D35 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D40 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D45 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D50 | — | — | — | — | — | 65 | 30 |
| 140M-L8P-D60 | — | — | — | — | — | 65 | 30 |
| N-Frame | |||||||
| 140M-N8P-D80 | — | — | — | — | — | 65 | 35 |
| 140M-N8P-E12 | — | — | — | — | — | 65 | 35 |
| ♣ Separate overload protection is required. | |||||||
| § The interrupting rating for MCPs is dependent upon the controller used. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information. | |||||||
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-K Contactors
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type F Combination Motor Controller |
UL 508 Type E Self-Protected Combination Motor Controller |
|||||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Group Motor Installation | Motor Disconnect | |||||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | |||||||
| 480V | 600V | 480V | 600V | 480Y/277V♣ | 600Y/347V♣ | 480Y/277V♣ | 600Y/347V♣ | |||||
| C-Frame | ||||||||||||
| 140M-C2E-A16 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A25 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A40 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-A63 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B10 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B16 | 450 | 100-K05 | 65 | 47 | 65 | 47 | 100-K05 | 65 | 47 | — | — | — |
| 140M-C2E-B25 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-C2E-B40 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-C2E-B63 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | — | — | — | — |
| 140M-C2E-C10 | 450 | 100-K09 | 65 | 30 | 65 | 30 | 100-K09 | 65 | — | — | — | — |
| 140M-C2E-C16 | 450 | 100-K12 | 30 | 30 | 30 | 30 | 100-K12 | 30 | — | — | — | — |
| D-Frame | ||||||||||||
| 140M-D8E-B25 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-B40 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-B63 | 450 | 100-K05 | 65 | 30 | 65 | 30 | 100-K05 | 65 | 30 | — | — | — |
| 140M-D8E-C10 | 450 | 100-K09 | 65 | 30 | 65 | 30 | 100-K09 | 65 | 30 | — | — | — |
| 140M-D8E-C16 | 450 | 100-K12 | 65 | 30 | 65 | 30 | 100-K12 | 65 | 30 | — | — | — |
| ♣ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | ||||||||||||
UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-C Contactors
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type F Combination Motor Controller |
UL 508 Type E Self-Protected Combination Motor Controller |
|||||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Group Motor Installation | Motor Disconnect | |||||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | |||||||
| 480V | 600V | 480V | 600V | 480Y/277V♣ | 600Y/347V♣ | 480Y/277V♣ | 600Y/347V♣ | |||||
| C-Frame | ||||||||||||
| 140M-C2E-A16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A25 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A40 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-A63 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B10 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2E-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C09 | 65 | 30 |
| 140M-C2E-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | — | 65 | 25 |
| 140M-C2E-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — | — | 65 | — |
| 140M-C2E-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — | — | 65 | — |
| 140M-C2E-C16 | 450 | 100-C12 | 30 | 30 | 30 | 25 | 100-C12 | 30 | — | — | 30 | — |
| 140M-C2E-C20 | 450 | 100-C16 | 30 | 30 | 30 | 30 | 100-C23 | 10 | — | — | 10 | — |
| 140M-C2E-C25 | 450 | 100-C23 | 30 | 30 | 10 | 10 | — | — | — | — | — | — |
| 450 | 100-C30 | 30 | 30 | 30 | 30 | — | — | — | — | — | — | |
| 140M-C2E-C29 | 450 | 100-C30 | 30 | 30 | 10 | 10 | — | — | — | — | — | — |
| 140M-C2E-C32 | 450 | 100-C37 | 30 | 30 | 10 | 10 | — | — | — | — | — | — |
| D-Frame | ||||||||||||
| 140M-D8E-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C09 | 65 | 30 |
| — | — | — | — | — | — | — | — | — | 100-C23 | 65 | 30 | |
| 140M-D8E-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C23 | 65 | 30 |
| 140M-D8E-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C16 | 450 | 100-C12 | 65 | 30 | 65 | 30 | 100-C12 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8E-C20 | 450 | 100-C23 | 65 | 30 | 65 | 30 | 100-C23 | 65 | — | 100-C30 | 65 | — |
| 140M-D8E-C25 | 450 | 100-C23 | 65 | 30 | 65 | 30 | 100-C23 | 30 | — | 100-C30 | 30 | — |
| 140M-D8E-C29 | 450 | 100-C30 | 65 | 30 | 65 | 10 | — | — | — | — | — | — |
| 140M-D8E-C32 | 450 | 100-C37 | 65 | 30 | 65 | 10 | — | — | — | — | — | — |
| F-Frame | ||||||||||||
| 140M-F8E-C10 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C16 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C20 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C25 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C32 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8E-C45 | 600 | 100-C37 | 65 | 18 | 65 | 18 | 100-C37 | 65 | — | 100-C37 | 65 | — |
| CMN-Frame | ||||||||||||
| 140-CMN-2500 | 1000 | 100-C16 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-4000 | 1000 | 100-C30 | 65 | 42 | — | — | — | — | — | — | — | — |
| 140-CMN-6300 | 1000 | 100-C43 | 42 | 18 | — | — | — | — | — | — | — | — |
| 140-CMN-9000 | 1000 | 100-C72 | 35 | 10 | — | — | — | — | — | — | — | — |
| ♣ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | ||||||||||||
UL Listed Application Ratings - Motor Circuit Protectors with Bulletin 100-C Contactors♣
| Cat. No. | UL 508 Manual Motor Controller | UL 508 Type E (Self-Protected) Combination Motor Controller | |||||||
| Max. Fuse or C.B. per NEC | Minimum Contactor Size | Group Motor Installation | Motor Disconnect | ||||||
| Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | Minimum Contactor Size | Max. Short Circuit Current [kA] | Max. Short Circuit Current [kA] | |||||
| 480V | 600V | 480V | 600V | 480Y/277V | 600Y/347V | ||||
| C-Frame | |||||||||
| 140M-C2N-A16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A25 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A40 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-A63 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B10 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B16 | 450 | 100-C09 | 65 | 47 | 65 | 47 | 100-C09 | 65 | 47 |
| 140M-C2N-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — |
| D-Frame | |||||||||
| 140M-D8N-B25 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C09 | 65 | — |
| — | — | — | — | — | — | 100-C23 | 65 | 30 | |
| 140M-D8N-B40 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C23 | 65 | 30 |
| 140M-D8N-B63 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C10 | 450 | 100-C09 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C16 | 450 | 100-C12 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-D8N-C25 | 450 | 100-C23 | 30 | 30 | 30 | 30 | 100-C30 | 65 | — |
| 140M-D8N-C32 | 450 | 100-C37 | 65 | 10 | 65 | 10 | — | — | — |
| F-Frame | |||||||||
| 140M-F8N-C25 | 600 | 100-C23 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8N-C32 | 600 | 100-C30 | 65 | 30 | 65 | 30 | 100-C30 | 65 | 30 |
| 140M-F8N-C45 | 600 | 100-C37 | 65 | 18 | 65 | 18 | 100-C37 | 65 | — |
| ♣ Separate overload protection is required. | |||||||||
| For full-voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. | |||||||||
Definition of Type 2 Short Circuit Coordination:
- The contactor or starter must not endanger persons or plant in the event of a short circuit.
- No damage to the motor protection device or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without appreciable deformation (such as with a screwdriver).
In the event of short circuit, fast-opening, current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical, fully short-circuit coordinated starter combinations with Type 2 coordination.
Type 2 Coordination 400V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Motor Protection | High Inrush Motor Protection | Motor Circuit Protection | 400V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 100 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 100 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 100 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 100 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 100 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 100 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 50 | 100-C09 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 50 | 100-C09 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 50 | 100-C09 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 50 | 100-C09 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 50 | 100-C12⋆ |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 50 | 100-C23 |
| 140M-C2E-C25 | — | — | 15 | 100-C30 |
| 140M-C2E-C29 | — | — | 15 | 100-C30 |
| 140M-C2E-C32 | — | — | 15 | 100-C37 |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 100 | 100-C09 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 100 | 100-C09 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 100 | 100-C09 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 65 | 100-C09 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 65 | 100-C12 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 65 | 100-C23 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 50 | 100-C23 |
| 140M-D8E-C29 | — | — | 65 | 100-C30 |
| 140M-D8E-C32 | — | 140M-D8N-C32 | 65 | 100-C37 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 100 | 100-C09 |
| 140M-F8E-C16 | — | — | 100 | 100-C12 |
| 140M-F8E-C20 | — | — | 100 | 100-C23 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 100 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 100 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 100 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 65 | 100-C16 |
| 140-CMN-4000 | — | — | 65 | 100-C30 |
| 140-CMN-6300 | — | — | 42 | 100-C43 |
| 140-CMN-9000 | — | — | 35 | 100-C72 |
| ⋆ Cat. No. 100-C16 contactors Type 1 only | ||||
Type 2 Coordination 480V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Motor Protection | High Inrush Motor Protection | Motor Circuit Protection | 480V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 65 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 65 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 65 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 65 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 65 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 65 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 50 | 100-C16 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 50 | 100-C30 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 50 | 100-C30 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 50 | 100-C30 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 10 | 100-C30 |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 10 | 100-C30 |
| 140M-C2E-C25 | — | — | 10 | 100-C30 |
| 140M-C2E-C29 | — | — | 10 | 100-C30 |
| 140M-C2E-C32 | — | — | 10 | 100-C37 |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 65 | 100-C09 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 65 | 100-C09 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 65 | 100-C09 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 65 | 100-C09 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 65 | 100-C12 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 65 | 100-C23 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 65 | 100-C23 |
| 140M-D8E-C29 | — | — | 65 | 100-C30 |
| 140M-D8E-C32 | — | 140M-D8N-C32 | 65 | 100-C37 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 65 | 100-C09 |
| 140M-F8E-C16 | — | — | 65 | 100-C12 |
| 140M-F8E-C20 | — | — | 65 | 100-C23 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 65 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 65 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 65 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 65 | 100-C16 |
| 140-CMN-4000 | — | — | 65 | 100-C30 |
| 140-CMN-6300 | — | — | 42 | 100-C43 |
| 140-CMN-9000 | — | — | 35 | 100-C72 |
Type 2 Coordination 600V
| Cat. No. | Max. Short Circuit Current [kA] | For Use With Contactors Below (or larger) | ||
| Standard Motor Protection | High Inrush Motor Protection | Motor Circuit Protection | 600V | |
| C-Frame | ||||
| 140M-C2E-A16 | — | 140M-C2N-A16 | 47 | 100-C09 |
| 140M-C2E-A25 | 140M-C2T-A16 | 140M-C2N-A25 | 47 | 100-C09 |
| 140M-C2E-A40 | 140M-C2T-A25 | 140M-C2N-A40 | 47 | 100-C09 |
| 140M-C2E-A63 | 140M-C2T-A40 | 140M-C2N-A63 | 47 | 100-C09 |
| 140M-C2E-B10 | 140M-C2T-A63 | 140M-C2N-B10 | 47 | 100-C09 |
| 140M-C2E-B16 | 140M-C2T-B10 | 140M-C2N-B16 | 47 | 100-C09 |
| 140M-C2E-B25 | 140M-C2T-B16 | 140M-C2N-B25 | 10 | 100-C16 |
| 140M-C2E-B40 | 140M-C2T-B25 | — | 10 | 100-C16 |
| 140M-C2E-B63 | 140M-C2T-B40 | — | 5 | 100-C23 |
| 140M-C2E-C10 | 140M-C2T-B63 | — | 5 | 100-C30 |
| 140M-C2E-C16 | 140M-C2T-C10 | — | 5 | 100-C30 |
| 140M-C2E-C20 | 140M-C2T-C16 | — | 5 | 100-C30 |
| 140M-C2E-C25 | — | — | 5 | 100-C30 |
| 140M-C2E-C29 | — | — | 5 | 100-C30 |
| 140M-C2E-C32 | — | — | 5 | 100-C37 |
| D-Frame | ||||
| 140M-D8E-B25 | — | 140M-D8N-B25 | 30 | 100-C30 |
| 140M-D8E-B40 | — | 140M-D8N-B40 | 30 | 100-C30 |
| 140M-D8E-B63 | — | 140M-D8N-B63 | 30 | 100-C30 |
| 140M-D8E-C10 | — | 140M-D8N-C10 | 30 | 100-C30 |
| 140M-D8E-C16 | — | 140M-D8N-C16 | 30 | 100-C30 |
| 140M-D8E-C20 | 140M-D8T-C16 | — | 5 | 100-C30 |
| 140M-D8E-C25 | 140M-D8T-C20 | 140M-D8N-C25 | 5 | 100-C30 |
| 140M-D8E-C29 | — | — | 10 | 100-C30 |
| 140M-D8E-C32 | — | 140M-D8N-C32 | 10 | 100-C37 |
| F-Frame | ||||
| 140M-F8E-C10 | — | — | 30 | 100-C30 |
| 140M-F8E-C16 | — | — | 30 | 100-C30 |
| 140M-F8E-C20 | — | — | 30 | 100-C30 |
| 140M-F8E-C25 | — | 140M-F8N-C25 | 30 | 100-C30 |
| 140M-F8E-C32 | 140M-F8T-C25 | 140M-F8N-C32 | 30 | 100-C30 |
| 140M-F8E-C45 | 140M-F8T-C32 | 140M-F8N-C45 | 10 | 100-C37 |
| CMN-Frame | ||||
| 140-CMN-2500 | — | — | 42 | 100-C16 |
| 140-CMN-4000 | — | — | 42 | 100-C30 |
| 140-CMN-6300 | — | — | 18 | 100-C43 |
| 140-CMN-9000 | — | — | 10 | 100-C72 |
Accessories
Accessories — Screwless
Notes: 1. See Bulletin 140U for Internal and External Accessories for Bulletin 140M-H, J, L and N frames.
2. Bulletin 140M-I frame Accessories such as auxiliaries, alarms, undervoltage and shunt trips are only available as factory installed modifications. See 140M Factory Modifications (Open).
Internal Control Modules — Field Installed
Terminal Lugs
Terminal Lugs, Continued
140M Factory Modifications (Open)
Note: For modifications add (option code _) for desired features to cat. no. Available in North America only.
| f | ||
| Miscellaneous | ||
| Code | Description | Frame Size |
| KN(1) | Black Lockable Knob | C, D, F, CMN |
| KRY(1) | Red/Yellow Lockable Knob | C, D, F, CMN |
| TE(1) | Spacing Adapter for Self-Protected Starters (Type E) | C, D, F |
| MT | STD Bus Bar Mount, Top | C, D, F, H, CMN |
| MU | STD Bus Bar Mount, Universal | J, K, L |
| g | |||
| Aux / Trip Contacts - C, D, F | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Right Side | ||
| X | Placeholder | X | Placeholder |
| A | 1 N.C. | C | 1 N.O. + 1 N.C. |
| B | 1 N.O. | D | 2 N.O. |
| C | 1 N.O. + 1 N.C. | E | 2 N.C. |
| D | 2 N.O. | K | 1 N.C. (SC+OL) + 1 N.C. (SC) |
| E | 2 N.C. | L | 1 N.O. (SC+OL) + 1 N.O. (SC) |
| R | 1 N.C. + 1 N.O. (SC+OL) | M | 1 N.C. (SC+OL) + 1 N.O. (SC) |
| S | 1 N.O. + 1 N.O. (SC+OL) | N | 1 N.O. (SC+OL) + 1 N.C. (SC) |
| Q | 1 N.O. (SC) + 1 N.C. (SC) | ||
| g | |||
| Aux / Trip Contacts - CMN | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Top Front§ | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | K | 1 N.C. (OL) + 1 N.C. (SC) |
| D | 2 N.O. | L | 1 N.O. (OL) + 1 NO (SC) |
| E | 2 N.C. | M | 1 N.C. (OL) + 1 N.O. (SC) |
| N | 1 N.O. (OL) + 1 N.C. (SC) | ||
§ Cannot be combined with option "h".
| g | |||
| Aux / Trip Contacts - H, J, L | |||
| 1st Code | Description | 2nd Code | Description |
| Bottom Front | Right Side | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | ||
| R | 1 N.O. + 1 N.C. (Overload Function) | ||
| F⋆ | 2 N.O. + 2 N.C. | ||
| N⋆ | 1 N.O. (SC+OL) + 1 N.C. (SC) | ||
| T⋆ | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) | ||
⋆ Only available on MCPs.
J- and L-Frame MPCB only.
| g | |||
| Aux / Trip Contacts - I, N | |||
| 1st Code | Description | 2nd Code | Description |
| Left Side | Right Side | ||
| X | Placeholder | X | Placeholder |
| C | 1 N.O. + 1 N.C. | C | 1 N.O. + 1 N.C. |
| F | 2 N.O. + 2 N.C. | F⋆ | 2 N.O. + 2 N.C. |
| N | 1 N.O. (SC+OL) + 1 N.C. (SC) | N⋆ | 1 N.O. (SC+OL) + 1 N.C. (SC) |
| T | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) | T⋆ | 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) |
⋆ Only available on MCPs.
140M Factory Modifications (Open), Continued
Note: For modifications add (option code *) for desired features to cat. no. Available in North America only.
| h | |||
| UV and Shunt Trips - C, D, F | |||
| 1st Code | Description | 2nd Code | Description |
| Left Side | Voltage | ||
| G | Undervoltage Trip | J | 24V AC, 60 Hz |
| P | Shunt Trip | K | 24V AC, 50 Hz |
| D | 120V AC, 60 Hz | ||
| C | 110V AC, 50 Hz | ||
| H | 208V AC, 60 Hz | ||
| F | 220…230V AC, 50 Hz | ||
| A | 240V AC, 60 Hz | ||
| T | 277V AC, 60 Hz | ||
| N | 380…400V AC, 50 Hz | ||
| B | 480V AC, 60 Hz and 415V AC, 50 Hz | ||
| VC | 600V AC, 60 Hz | ||
| M | 575V AC, 60 Hz and 500V AC, 50 Hz | ||
| ZR | 9V DC | ||
| ZQ | 12V DC | ||
| ZJ | 24V DC | ||
| ZW | 36V DC | ||
| ZY | 48V DC | ||
| ZZ | 60V DC | ||
| ZB | 64V DC | ||
| ZG | 72V DC | ||
| ZE | 80V DC | ||
| h | |||
| UV and Shunt Trips - CMN | |||
| 1st Code | Description | 2nd Code | Description |
| Top Front§ | Voltage | ||
| G | Undervoltage Trip | KJ | 24V AC, 60 Hz and 24V AC, 50 Hz |
| P | Shunt Trip | D | 120V AC, 60 Hz and 110V AC, 50 Hz |
| A | 240V AC, 60 Hz and 220…230V AC, 50 Hz | ||
| h | |||
| UV and Shunt Trips - H, J, L | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC/DC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…500V AC | ||
| C | 525…600V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…60V AC/DC |
| D | 110…240V AC/DC | ||
| B | 380…600V AC | ||
| h | |||
| UV and Shunt Trips - I | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…480V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…24V AC/DC |
| D | 48…127V AC and 48…60V DC | ||
| N | 208…380V AC and 110…127V DC | ||
| B | 415…600V AC and 220…250V DC | ||
| h | |||
| UV and Shunt Trips - N | |||
| 1st Code | Description | 2nd Code | Description |
| Left Front | UV Voltage | ||
| G | Undervoltage Trip | J | 24V AC |
| D | 110…127V AC | ||
| A | 208…240V AC | ||
| B | 380…480V AC | ||
| Left Front | Shunt Voltage | ||
| P | Shunt Trip | J | 12…24V AC/DC |
| D | 110…240V AC and 110…125V DC | ||
| N | 380…440V AC and 220…250V DC | ||
| B | 480…600V AC | ||
Specifications
IEC Performance Data
| Cat. No. 140M-C2E- | ||||||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | C20 | C25 | C29 | C32 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1 | 1.6 | 2.5 | 4 | 6.3 | 10 | 16 | 20 | 25 | 29 | 32 |
| Magnetic Release Current | [A] | 2.1 | 3.3 | 5.2 | 8.2 | 13 | 21 | 33 | 52 | 82 | 130 | 208 | 260 | 325 | 406 | 448 |
| Switching of Standard Three-Phase Motors | ||||||||||||||||
| AC-3 | ||||||||||||||||
| 230/240V | [kW] | — | — | 0.06 | 0.09 | 0.18 | 0.25 | 0.37 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 5.5 | 7.5 | 7.5 |
| 400/415V | [kW] | 0.02 | 0.04 | 0.09 | 0.18 | 0.25 | 0.55 | 0.75 | 1.5 | 2.2 | 4.0 | 7.5 | 10 | 11 | 13 | 15 |
| 500V | [kW] | 0.06 | 0.09 | 0.12 | 0.18 | 0.37 | 0.75 | 1.1 | 2.2 | 3.0 | 6.3 | 10 | 11 | 15 | 18.5 | 20 |
| 690V | [kW] | 0.06 | 0.09 | 0.18 | 0.25 | 0.55 | 1.1 | 1.8 | 3.0 | 4.0 | 7.5 | 13 | 17 | 22 | 25 | 25 |
| Back-Up Fuses | ||||||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 100 | 100 | 125 | 125 |
| 400/415V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 100 | 100 | 125 | 125 |
| 440/460V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 63 | 80 | 80 | 80 | 100 | 100 |
| 500V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 80 | 80 | 80 | 100 | 100 |
| 690V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 16 | 20 | 35 | 50 | 50 | 63 | 63 | 63 | 80 | 80 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||||||
| Icu | ||||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 65 | 50 | 50 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 50 | 15 | 15 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 | 6 | 6 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 | 3 | 3 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||||||
| Ics | ||||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 50 | 25 | 25 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 15 | 15 | 15 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 | 6 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 | 6 | 6 | 6 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 | 3 | 3 | 3 | 3 |
| ⋆ No back-up fuse required. | ||||||||||||||||
| Cat. No. 140M-D8E- | Cat. No. 140M-F8E- | |||||||||||||||
| B25 | B40 | B63 | C10 | C16 | C20 | C25 | C29 | C32 | C10 | C16 | C20 | C25 | C32 | C45 | ||
| Rated Operational Current, Ie | [A] | 2.5 | 4.0 | 6.3 | 10 | 16 | 20 | 25 | 29 | 32 | 10 | 16 | 20 | 25 | 32 | 45 |
| Magnetic Release Current | [A] | 33 | 52 | 82 | 130 | 208 | 260 | 325 | 406 | 448 | 130 | 208 | 260 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | ||||||||||||||||
| AC-3 | ||||||||||||||||
| 230/240V | [kW] | 0.37 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 5.5 | 7.5 | 7.5 | 2.2 | 4.0 | 5.5 | 6.3 | 7.5 | 13 |
| 400/415V | [kW] | 0.75 | 1.5 | 2.2 | 4.0 | 7.5 | 10 | 11 | 13 | 15 | 4.0 | 7.5 | 10 | 11 | 15 | 22 |
| 500V | [kW] | 1.1 | 2.2 | 3.0 | 6.3 | 10 | 11 | 15 | 18.5 | 20 | 6.3 | 10 | 11 | 15 | 20 | 30 |
| 690V | [kW] | 1.8 | 3.0 | 4.0 | 7.5 | 13 | 17 | 22 | 25 | 25 | 7.5 | 13 | 17 | 22 | 30 | 40 |
| Back-Up Fuses | ||||||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ |
| 400/415V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 100 | 100 | 125 | 125 | 80 | 100 | 100 | 100 | 125 | 125 |
| 440/460V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 100 | 100 | 125 | 125 | 80 | 100 | 100 | 100 | 125 | 125 |
| 500V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 80 | 80 | 100 | 100 | 80 | 100 | 100 | 100 | 125 | 125 |
| 690V | [A] | 20 | 35 | 50 | 50 | 63 | 63 | 63 | 80 | 80 | 63 | 80 | 80 | 80 | 100 | 100 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||||||
| Icu | ||||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 65 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 50 | 50 | 100 | 100 | 100 | 100 | 65 | 65 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 50 | 50 | 25 | 25 | 65 | 65 | 65 | 65 | 65 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 50 | 50 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 6 | 6 | 6 | 6 | 6 | 10 | 10 | 10 | 10 | 10 | 10 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||||||
| Ics | ||||||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 50 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 25 | 25 | 50 | 50 | 50 | 50 | 50 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 20 | 20 | 50 | 50 | 50 | 50 | 50 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 20 | 20 | 50 | 50 | 50 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 4 | 4 | 4 | 4 | 4 | 10 | 10 | 10 | 10 | 6 | 6 |
| ⋆ No back-up fuse required. | ||||||||||||||||
| Cat. No. | 140-CMN-… | ||||
| -2500 | -4000 | -6300 | -9000 | ||
| Rated Operational Current, Ie | [A] | 25 | 40 | 63 | 90 |
| Magnetic Release Current | [A] | 350 | 560 | 890 | 1260 |
| Switching of Standard Three-Phase Motors | |||||
| AC-3 | |||||
| 230/240V | [kW] | 5.5/7.5 | 10/11 | 13/20 | 22/25 |
| 400/415V | [kW] | 7.5/13 | 15/22 | 25/32 | 37/45 |
| 500V | [kW] | 11/15 | 18.5/25 | 30/40 | 45/55 |
| 690V | [kW] | 15/22 | 25/30 | 37/55 | 63/75 |
| Back-up fuses | |||||
| gG, gL,, only if Icc ³ Icu | |||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ |
| 400/415V | [A] | 160 | 160 | 160 | 160 |
| 500V | [A] | 160 | 160 | 160 | 160 |
| 690V | [A] | 160 | 160 | 160 | 160 |
| Ultimate short-circuit breaking capacity Icu | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 65 | 65 | 65 | 50 |
| 500V | [kA] | 50 | 30 | 30 | 25 |
| 690V | [kA] | 15 | 8 | 8 | 6 |
| Rated service short-circuit breaking capacity Ics | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 65 | 50 | 50 | 25 |
| 500V | [kA] | 50 | 25 | 25 | 13 |
| 690V | [kA] | 15 | 8 | 6 | 6 |
| ⋆ No back-up fuse required. | |||||
| Power ratings: Preferred values according to IEC 60072-1. | |||||
IEC Performance Data, Continued
| Cat. No. 140M-C2N- | ||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1 | 1.6 | 2.5 |
| Magnetic Release Current | [A] | 2.1 | 3.3 | 5.2 | 8.2 | 13 | 21 | 32 |
| Switching of Standard Three-Phase Motors | ||||||||
| AC-3 | ||||||||
| 230/240V | [kW] | — | — | 0.06 | 0.09 | 0.18 | 0.25 | 0.37 |
| 400/415V | [kW] | 0.02 | 0.04 | 0.09 | 0.18 | 0.25 | 0.55 | 0.75 |
| 500V | [kW] | 0.06 | 0.09 | 0.12 | 0.18 | 0.37 | 0.75 | 1.1 |
| 690V | [kW] | 0.06 | 0.09 | 0.18 | 0.25 | 0.55 | 1.1 | 1.8 |
| Back-Up Fuses | ||||||||
| gG, gL, only if Icc³Icu⋆ | ||||||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ |
| 400/415V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ |
| 440/460V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ |
| 500V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ |
| 690V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 16 | 20 |
| Ultimate Short Circuit Breaking Capacity | ||||||||
| Icu | ||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 10 | 8 |
| Rated Service Short Circuit Breaking Capacity | ||||||||
| Ics | ||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 |
| ⋆ No back-up fuse required. | ||||||||
| Cat. No. 140M-D8N- | Cat. No. 140M-F8N- | ||||||||||
| B25 | B40 | B63 | C10 | C16 | C25 | C32 | C25 | C32 | C45 | ||
| Rated Operational Current, Ie | [A] | 2.5 | 4.0 | 6.3 | 10 | 16 | 25 | 32 | 25 | 32 | 45 |
| Magnetic Release Current | [A] | 32 | 52 | 82 | 130 | 208 | 325 | 448 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | |||||||||||
| AC-3 | |||||||||||
| 230/240V | [kW] | 0.37 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 6.3 | 7.5 | 13 |
| 400/415V | [kW] | 0.75 | 1.5 | 2.2 | 4.0 | 7.5 | 11 | 15 | 11 | 15 | 22 |
| 500V | [kW] | 1.1 | 2.2 | 3.0 | 6.3 | 10 | 15 | 20 | 15 | 20 | 30 |
| 690V | [kW] | 1.8 | 3.0 | 4.0 | 7.5 | 13 | 22 | 25 | 22 | 30 | 40 |
| Back-Up Fuses | |||||||||||
| gG, gL, only if Icc³Icu | |||||||||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 100 | 125 | 125 |
| 400/415V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 100 | 125 | 100 | 125 | 125 |
| 440/460V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 100 | 125 | 100 | 125 | 125 |
| 500V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 80 | 100 | 100 | 125 | 125 |
| 690V | [A] | 20 | 35 | 50 | 50 | 63 | 63 | 80 | 80 | 100 | 100 |
| Ultimate Short Circuit Breaking Capacity | |||||||||||
| Icu | |||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 65 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 65 | 50 | 100 | 65 | 65 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 50 | 25 | 65 | 65 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 6 | 6 | 6 | 10 | 10 | 10 |
| Rated Service Short Circuit Breaking Capacity | |||||||||||
| Ics | |||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 25 | 50 | 50 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 20 | 50 | 50 | 50 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 50 | 25 | 20 | 50 | 50 | 50 |
| 690V | [kA] | 10 | 10 | 10 | 6 | 4 | 4 | 4 | 10 | 6 | 6 |
| ⋆ No back-up fuse required. | |||||||||||
| Cat. No. 140M-C2T- | ||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | ||
| Rated Operational Current, Ie | [A] | 0.16 | 0.25 | 0.40 | 0.63 | 1.0 | 1.6 | 2.5 | 4.0 | 6.3 | 10 | 16 |
| Magnetic Release Current | [A] | 3.2 | 5.2 | 8.2 | 13 | 21 | 32 | 52 | 82 | 130 | 208 | 260 |
| Switching of Standard Three-Phase Motors | ||||||||||||
| AC-3 | ||||||||||||
| 230/240V | [kW] | — | — | 0.06 | 0.09 | 0.18 | 0.25 | 0.37 | 0.75 | 1.5 | 2.2 | 4.0 |
| 400/415V | [kW] | 0.02 | 0.04 | 0.09 | 0.18 | 0.25 | 0.55 | 0.75 | 1.5 | 2.2 | 4.0 | 7.5 |
| 500V | [kW] | 0.06 | 0.09 | 0.12 | 0.18 | 0.37 | 0.75 | 1.1 | 2.2 | 3.0 | 6.3 | 10 |
| 690V | [kW] | 0.06 | 0.09 | 0.18 | 0.25 | 0.55 | 1.1 | 1.8 | 3.0 | 4.0 | 7.5 | 13 |
| Back-Up Fuses | ||||||||||||
| gG, gL, only if Icc³Icu | ||||||||||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ |
| 400/415V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 80 |
| 440/460V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 63 | 80 |
| 500V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 80 | 80 |
| 690V | [A] | ⋆ | ⋆ | ⋆ | ⋆ | ⋆ | 16 | 20 | 35 | 50 | 50 | 63 |
| Ultimate Short Circuit Breaking Capacity | ||||||||||||
| Icu | ||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 10 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 |
| Rated Service Short Circuit Breaking Capacity | ||||||||||||
| Ics | ||||||||||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 15 |
| 440/460V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 |
| 500V | [kA] | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 50 | 6 |
| 690V | [kA] | 100 | 100 | 100 | 100 | 100 | 8 | 8 | 8 | 4 | 4 | 3 |
| ⋆ No back-up fuse required. | ||||||||||||
| Cat. No. 140M-D8T- | Cat. No. 140M-F8T- | ||||
| C16 | C20 | C25 | C32 | ||
| Rated Operational Current, Ie | [A] | 16 | 20 | 25 | 32 |
| Magnetic Release Current | [A] | 260 | 325 | 416 | 585 |
| Switching of Standard Three-Phase Motors | |||||
| AC-3 | |||||
| 230/240V | [kW] | 4.0 | 5.5 | 6.3 | 7.5 |
| 400/415V | [kW] | 7.5 | 10 | 11 | 15 |
| 500V | [kW] | 10 | 11 | 15 | 20 |
| 690V | [kW] | 13 | 17 | 22 | 30 |
| Back-up fuses | |||||
| gG, gL,, only if Icc ³ Icu | |||||
| 230/240V | [A] | ⋆ | ⋆ | ⋆ | ⋆ |
| 400/415V | [A] | 80 | 100 | 100 | 125 |
| 440/460V | [A] | 80 | 100 | 100 | 125 |
| 500V | [A] | 80 | 80 | 100 | 125 |
| 690V | [A] | 63 | 63 | 80 | 100 |
| Ultimate short-circuit breaking capacity | |||||
| Icu | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 100 | 65 | 65 | 65 |
| 440/460V | [kA] | 50 | 25 | 65 | 65 |
| 500V | [kA] | 50 | 25 | 50 | 50 |
| 690V | [kA] | 6 | 6 | 10 | 10 |
| Rated service short-circuit breaking capacity Ics | |||||
| Ics | |||||
| 230/240V | [kA] | 100 | 100 | 100 | 100 |
| 400/415V | [kA] | 25 | 25 | 50 | 50 |
| 440/460V | [kA] | 25 | 25 | 50 | 50 |
| 500V | [kA] | 25 | 25 | 50 | 50 |
| 690V | [kA] | 4 | 4 | 6 | 6 |
| ⋆ No back-up fuse required. | |||||
| Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||
| Cat. No. | 140M-C | 140M-D | 140M-F | 140-CMN | |
| Rated Insulation Voltage Ui | |||||
| IEC, SEV, VDE 0660 | [V] | 690 | 690 | ||
| UL, CSA | [V] | 600 | 600 | ||
| Rated Impulse Withstand Voltage Uimp | |||||
| Pollution degree | 3 | 3 | |||
| Main circuits Uimp /Overvoltage Category | 6 kV/III | 6 kV/III | |||
| Auxiliary circuits Uimp /Overvoltage Category | 6 kV/III | 6 kV/III | |||
| Rated Frequency | [Hz] | 50/60 | 40…60 | ||
| Utilization Category | |||||
| IEC 60947-2 (Circuit breaker) | A | A | |||
| IEC 60947-4-1 (Motor starter) | AC-3 | AC-3 | |||
| Life Span | |||||
| Mechanical | [operations] | 100 000 | 30 000 | 30 000 | |
| Electrical (Ie max.) | [operations] | 100 000 | 30 000 | 10 000 (up to 63 A) 5 000 (up to 90 A) |
|
| Switching Frequency | [operations/h] | max. 25 | max. 20 | ||
| Ambient Temperature | |||||
| Storage | [°C] | -40 … +80 | -25… +80 | ||
| Operation | [°C] | -25… +60 | |||
| Climatic resistance | |||||
| Moisture change climate (600068-2-30) | 23 °C / 83 % relative humidity and 40 °C / 92 % relative humidity, 56 cycles | ||||
| Dry heat (60086-2-2) | 100 °C, relative humidity <50 %, 7 days | ||||
| Moisture heat (60068-2-3) | 40 °C, relative humidity 93 %, 56 days | ||||
| Site Altitude | [m] | to 2000 N.N. | |||
| Protection Class | IP2X, when wired | ||||
| Resistance to Shock, Transport (60068-2-27) | 30 g, 11 ms, all axes | 30, 11 ms | |||
| Resistance to Vibration, Opertion (60068-2-6) | 5 g | ||||
| Rated Thermal Current Ith | |||||
| up to 40 °C ambient temperature | [A] | 0.1…32 | 1.6…32 | 6.3…45 | 16… 90 |
| up to 60 °C ambient temperature | [A] | 0.1…32 | 1.6…32 | 6.3…45 | 16… 90 |
| Rated Supply Current Ie | [A] | 0.1…32 | 1.6…32 | 6.3…45 | 16… 90 |
| Dependence on Temperature | |||||
| 40 °C | [A] | no reduction | |||
| 50 °C | [A] | no reduction | |||
| 60 °C | [A] | no reduction | |||
| 70 °C | [A] | 15 % current reduction of the upper rated current Ie | |||
| Overload Protection | |||||
| Characteristics | IEC 60947-4-1 Motor protection (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) |
IEC 60947 | |||
| Ambient Temperature Compensation | [°C] | -20 …+60 | |||
| Phase-loss Protection | Differential release | ||||
| Trip class | 10 (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) fixed setting | 10 | |||
| Magnetic Release Release current (+/-20 %) |
fixed setting 13…14 x Ie max. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N) 16…21 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T) Ie max. = maximum values of setting ranges |
fixed setting 14 x Ie max. |
|||
| Total Power loss Pv | |||||
| Circuit Breaker at rated load operating temperature | [W] | 6…11.5 | 6…11.6 | 9…16 | 33 |
| Main Disconnect Switch Application | Yes, with accessories | ||||
| Application Conditions | For utilization outside North America, assemblies (of products) shall comply to the IEC 61439-1 requirements | ||||
| 140M manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments. | |||||
General Data, Continued
Screwless
Accessories for Bulletin 140M Motor Protection Circuit Breakers
| Undervoltage Trip for Left-Side Mounting Cat. No. 140M-C-UX… |
Undervoltage Trip with 2 Auxiliary Contacts for Left-Side Mounting Cat. No. 140M-C-UC… |
Shunt Trip for Left-Side Mounting Cat. No. 140M-C-SN… |
|||
| Actuating Voltage | |||||
| Pull-in Drop-out |
0.85…1.1 x Us 0.7…0.35 x Us |
0.85…1.1 x Us 0.7…0.35 x Us |
|||