Motor Protection Circuit Breakers and Motor Circuit Protectors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Motor Protection Circuit Breakers and Motor Circuit Protectors > Bulletin 140M Application Ratings, Accessories, Specifications, and Approximate Dimensions

Bulletin 140M Application Ratings, Accessories, Specifications, and Approximate Dimensions

Application Ratings Accessories Specifications Approximate Dimensions
Specifications

IEC Performance Data

  Cat. No. 140M-C2E-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 C25 C29 C32
Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25 29 32
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325 406 448
Switching of Standard Three-Phase Motors
AC-3
230/240V [kW] 0.06 0.09 0.18 0.25 0.37 0.75 1.5 2.2 4.0 5.5 5.5 7.5 7.5
400/415V [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75 1.5 2.2 4.0 7.5 10 11 13 15
500V [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1 2.2 3.0 6.3 10 11 15 18.5 20
690V [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8 3.0 4.0 7.5 13 17 22 25 25
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  100 100 125 125
400/415V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  80 100 100 125 125
440/460V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  63 80 80 80 100 100
500V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  80 80 80 80 100 100
690V [A] ⋆  ⋆  ⋆  ⋆  ⋆  16 20 35 50 50 63 63 63 80 80
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 65 65 50 50
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 65 50 15 15 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6 6 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6 6 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3 3 3
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50 25 25
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15 15 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 6 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 6 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3 3 3
  
⋆ No back-up fuse required.

  Cat. No. 140M-D8E- Cat. No. 140M-F8E-
B25 B40 B63 C10 C16 C20 C25 C29 C32 C10 C16 C20 C25 C32 C45
Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 20 25 29 32 10 16 20 25 32 45
Magnetic Release Current [A] 33 52 82 130 208 260 325 406 448 130 208 260 325 416 585
Switching of Standard Three-Phase Motors
AC-3
230/240V [kW] 0.37 0.75 1.5 2.2 4.0 5.5 5.5 7.5 7.5 2.2 4.0 5.5 6.3 7.5 13
400/415V [kW] 0.75 1.5 2.2 4.0 7.5 10 11 13 15 4.0 7.5 10 11 15 22
500V [kW] 1.1 2.2 3.0 6.3 10 11 15 18.5 20 6.3 10 11 15 20 30
690V [kW] 1.8 3.0 4.0 7.5 13 17 22 25 25 7.5 13 17 22 30 40
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆ 
400/415V [A] ⋆  ⋆  ⋆  ⋆  ⋆  100 100 125 125 80 100 100 100 125 125
440/460V [A] ⋆  ⋆  ⋆  ⋆  80 100 100 125 125 80 100 100 100 125 125
500V [A] ⋆  ⋆  ⋆  ⋆  80 80 80 100 100 80 100 100 100 125 125
690V [A] 20 35 50 50 63 63 63 80 80 63 80 80 80 100 100
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 65 65 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 65 50 50 100 100 100 100 65 65
440/460V [kA] 100 100 100 100 50 50 50 25 25 65 65 65 65 65 50
500V [kA] 100 100 100 100 50 50 50 25 25 50 50 50 50 50 50
690V [kA] 10 10 10 6 6 6 6 6 6 10 10 10 10 10 10
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 50 50 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 50 25 25 25 25 50 50 50 50 50 50
440/460V [kA] 100 100 100 100 50 25 25 20 20 50 50 50 50 50 50
500V [kA] 100 100 100 100 50 25 25 20 20 50 50 50 50 50 50
690V [kA] 10 10 10 6 4 4 4 4 4 10 10 10 10 6 6
  
⋆ No back-up fuse required.

Cat. No. 140-CMN-…
-2500 -4000 -6300 -9000
Rated Operational Current, Ie [A] 25 40 63 90
Magnetic Release Current [A] 350 560 890 1260
Switching of Standard Three-Phase Motors
AC-3
230/240V‡  [kW] 5.5/7.5 10/11 13/20 22/25
400/415V‡  [kW] 7.5/13 15/22 25/32 37/45
500V‡  [kW] 11/15 18.5/25 30/40 45/55
690V‡  [kW] 15/22 25/30 37/55 63/75
Back-up fuses
gG, gL,, only if Icc ³ Icu
230/240V [A] ⋆  ⋆  ⋆  ⋆ 
400/415V [A] 160 160 160 160
500V [A] 160 160 160 160
690V [A] 160 160 160 160
Ultimate short-circuit breaking capacity Icu
230/240V [kA] 100 100 100 100
400/415V [kA] 65 65 65 50
500V [kA] 50 30 30 25
690V [kA] 15 8 8 6
Rated service short-circuit breaking capacity Ics
230/240V [kA] 100 100 100 100
400/415V [kA] 65 50 50 25
500V [kA] 50 25 25 13
690V [kA] 15 8 6 6
  
⋆ No back-up fuse required.
‡ Power ratings: Preferred values according to IEC 60072-1.

IEC Performance Data, Continued

  Cat. No. 140M-C2N-
A16 A25 A40 A63 B10 B16 B25
Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5
Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 32
Switching of Standard Three-Phase Motors
AC-3
230/240V [kW] 0.06 0.09 0.18 0.25 0.37
400/415V [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75
500V [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1
690V [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8
Back-Up Fuses
gG, gL, only if Icc³Icu⋆ 
230/240V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆ 
400/415V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆ 
440/460V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆ 
500V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆ 
690V [A] ⋆  ⋆  ⋆  ⋆  ⋆  16 20
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 10 8
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100
440/460V [kA] 100 100 100 100 100 100 100
500V [kA] 100 100 100 100 100 100 100
690V [kA] 100 100 100 100 100 8 8
  
⋆ No back-up fuse required.

  Cat. No. 140M-D8N- Cat. No. 140M-F8N-
B25 B40 B63 C10 C16 C25 C32 C25 C32 C45
Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 25 32 25 32 45
Magnetic Release Current [A] 32 52 82 130 208 325 448 325 416 585
Switching of Standard Three-Phase Motors
AC-3
230/240V [kW] 0.37 0.75 1.5 2.2 4.0 5.5 7.5 6.3 7.5 13
400/415V [kW] 0.75 1.5 2.2 4.0 7.5 11 15 11 15 22
500V [kW] 1.1 2.2 3.0 6.3 10 15 20 15 20 30
690V [kW] 1.8 3.0 4.0 7.5 13 22 25 22 30 40
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  100 125 125
400/415V [A] ⋆  ⋆  ⋆  ⋆  ⋆  100 125 100 125 125
440/460V [A] ⋆  ⋆  ⋆  ⋆  80 100 125 100 125 125
500V [A] ⋆  ⋆  ⋆  ⋆  80 80 100 100 125 125
690V [A] 20 35 50 50 63 63 80 80 100 100
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 65 100 100 100
400/415V [kA] 100 100 100 100 100 65 50 100 65 65
440/460V [kA] 100 100 100 100 50 50 25 65 65 50
500V [kA] 100 100 100 100 50 25 25 50 50 50
690V [kA] 10 10 10 6 6 6 6 10 10 10
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 50 100 100 100
400/415V [kA] 100 100 100 100 50 25 25 50 50 50
440/460V [kA] 100 100 100 100 50 25 20 50 50 50
500V [kA] 100 100 100 100 50 25 20 50 50 50
690V [kA] 10 10 10 6 4 4 4 10 6 6
  
⋆ No back-up fuse required.

  Cat. No. 140M-C2T-
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16
Rated Operational Current, Ie [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 10 16
Magnetic Release Current [A] 3.2 5.2 8.2 13 21 32 52 82 130 208 260
Switching of Standard Three-Phase Motors
AC-3
230/240V [kW] 0.06 0.09 0.18 0.25 0.37 0.75 1.5 2.2 4.0
400/415V [kW] 0.02 0.04 0.09 0.18 0.25 0.55 0.75 1.5 2.2 4.0 7.5
500V [kW] 0.06 0.09 0.12 0.18 0.37 0.75 1.1 2.2 3.0 6.3 10
690V [kW] 0.06 0.09 0.18 0.25 0.55 1.1 1.8 3.0 4.0 7.5 13
Back-Up Fuses
gG, gL, only if Icc³Icu
230/240V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆ 
400/415V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  80
440/460V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  63 80
500V [A] ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  ⋆  80 80
690V [A] ⋆  ⋆  ⋆  ⋆  ⋆  16 20 35 50 50 63
Ultimate Short Circuit Breaking Capacity
Icu
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10
500V [kA] 100 100 100 100 100 100 100 100 100 50 10
690V [kA] 100 100 100 100 100 8 8 8 4 4 3
Rated Service Short Circuit Breaking Capacity
Ics
230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100
400/415V [kA] 100 100 100 100 100 100 100 100 100 100 15
440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6
500V [kA] 100 100 100 100 100 100 100 100 100 50 6
690V [kA] 100 100 100 100 100 8 8 8 4 4 3
  
⋆ No back-up fuse required.

  Cat. No. 140M-D8T- Cat. No. 140M-F8T-
C16 C20 C25 C32
Rated Operational Current, Ie [A] 16 20 25 32
Magnetic Release Current [A] 260 325 416 585
Switching of Standard Three-Phase Motors
AC-3
230/240V ‡  [kW] 4.0 5.5 6.3 7.5
400/415V ‡  [kW] 7.5 10 11 15
500V ‡  [kW] 10 11 15 20
690V ‡  [kW] 13 17 22 30
Back-up fuses
gG, gL,, only if Icc ³ Icu
230/240V [A] ⋆  ⋆  ⋆  ⋆ 
400/415V [A] 80 100 100 125
440/460V [A] 80 100 100 125
500V [A] 80 80 100 125
690V [A] 63 63 80 100
Ultimate short-circuit breaking capacity
Icu
230/240V [kA] 100 100 100 100
400/415V [kA] 100 65 65 65
440/460V [kA] 50 25 65 65
500V [kA] 50 25 50 50
690V [kA] 6 6 10 10
Rated service short-circuit breaking capacity Ics
Ics
230/240V [kA] 100 100 100 100
400/415V [kA] 25 25 50 50
440/460V [kA] 25 25 50 50
500V [kA] 25 25 50 50
690V [kA] 4 4 6 6
  
⋆ No back-up fuse required.
‡ Consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Cat. No. 140M-C 140M-D 140M-F 140-CMN
Rated Insulation Voltage Ui
IEC, SEV, VDE 0660 [V] 690 690
UL, CSA [V] 600 600
Rated Impulse Withstand Voltage Uimp
Pollution degree 3 3
Main circuits Uimp /Overvoltage Category 6 kV/III 6 kV/III
Auxiliary circuits Uimp /Overvoltage Category 6 kV/III 6 kV/III
Rated Frequency [Hz] 50/60 40…60
Utilization Category
IEC 60947-2 (Circuit breaker) A A
IEC 60947-4-1 (Motor starter) AC-3 AC-3
Life Span
Mechanical [operations] 100 000 30 000 30 000
Electrical (Ie max.) [operations] 100 000 30 000 10 000 (up to 63 A)
5 000 (up to 90 A)
Switching Frequency [operations/h] max. 25 max. 20
Ambient Temperature
Storage [°C] -40 … +80 -25… +80
Operation [°C] -25… +60
Climatic resistance
Moisture change climate (600068-2-30) 23 °C / 83 % relative humidity and 40 °C / 92 % relative humidity, 56 cycles
Dry heat (60086-2-2) 100 °C, relative humidity <50 %, 7 days
Moisture heat (60068-2-3) 40 °C, relative humidity 93 %, 56 days
Site Altitude [m] to 2000 N.N.  
Protection Class IP2X, when wired
Resistance to Shock, Transport (60068-2-27) 30 g, 11 ms, all axes 30, 11 ms
Resistance to Vibration, Opertion (60068-2-6) 5 g  
Rated Thermal Current Ith
up to 40 °C ambient temperature [A] 0.1…32 1.6…32 6.3…45 16… 90
up to 60 °C ambient temperature [A] 0.1…32 1.6…32 6.3…45 16… 90
Rated Supply Current Ie [A] 0.1…32 1.6…32 6.3…45 16… 90
Dependence on Temperature
40 °C [A] no reduction
50 °C [A] no reduction
60 °C [A] no reduction
70 °C [A] 15 % current reduction of the upper rated current Ie
Overload Protection
Characteristics IEC 60947-4-1 Motor protection
(except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N)
IEC 60947
Ambient Temperature Compensation [°C] -20 …+60
Phase-loss Protection Differential release
Trip class 10 (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) fixed setting 10
Magnetic Release
Release current (+/-20 %)
fixed setting
13…14 x Ie max. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N)
16…21 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T)
Ie max. = maximum values of setting ranges
fixed setting
14 x Ie max.
Total Power loss Pv
Circuit Breaker at rated load operating temperature [W] 6…11.5 6…11.6 9…16 33
Main Disconnect Switch Application Yes, with accessories
Application Conditions For utilization outside North America, assemblies (of products) shall comply to the IEC 61439-1 requirements
140M manual motor starters are intended for use in closed areas without hazardous operating conditions such as dust or explosive or corrosive gases. Enclosures of appropriate manner need to be in place to protect devices in such environments.
  

General Data, Continued

Cat. No. 140M-C… 140M-D… 140M-F… 140-CMN
Conformity to Standards IEC 60947-1; -2; -4-1;
EN 60947-1; -2; -4-1;
UL 508; CSA 22.2, No. 14
IEC 60947-1; -2;
EN 60947-1; -2;
UL 508; CSA 22.2, No. 14
Approvals CE, UL, CSA CE, UL, CSA
Terminal Parts
    Type of terminals
Click to enlarge - 140M-29-1 Click to enlarge - 140M-29-2 Click to enlarge - 140M-29-3
Screwdriver Pozidriv No. 2/Blade No. 3 Pozidriv No. 2/Blade No. 3
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1…6/No. 16…10
1…4/No. 16…10
2.5…25/No. 14…4
2.5…25/No. 14…4
2.5…35
Click to enlarge - Conductor_var2 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1…6/No. 16…10
1…6/No. 16…10
2.5…25/No. 14…4
2.5…25/No. 14…4
2.5…35
Click to enlarge - 140M-29-5 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1.5…6/No. 16…8
1.5…6/No. 16…8
16…25/No. 14…4
16…25/No. 14…4
4…50 / 12…2
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1…6/No. 16…10
1…6/No. 16…10
2.5…10/No. 14…8
2.5…10/No. 14…8
4…50 / 12…2
Tightening torque [Nm]/[lb•in] 2…2.5/18…22 3…3.5/27…30 6…10/55…90
  

Screwless

Cat. No. 140M-RC…
Terminal Parts
    Type of terminals
Click to enlarge - 140M-RC_Screwless
Screwdriver Click to enlarge - 140M-RC_Screwless_1
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
0.5…2.5/—
0.5…2.5/—
Click to enlarge - Conductor_var2 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
0.5…2.5/No. 18…12
0.5…2.5/No. 18…12
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
1…4/No. 16…12
1…4/No. 16…12
  

Accessories for Bulletin 140M Motor Protection Circuit Breakers

  Auxiliary Contact Blocks for
Front Mounting
Cat. No. 140M-C-AFA…, 140M-C-AFAR…
Auxiliary Contact Blocks for
Right-Side Mounting
Cat. No. 140M-C-ASA…, 140M-C-ASAR…
Rated Thermal Current Ith
at 40 °C ambient temperature
at 60 °C ambient temperature

[A]
[A]

5
4

10
6
Contact Class Coordination
According to NEMA
   
(UL/CSA Standards)
AC
DC
B 300
Q 300
B 600
Q 600
Back-Up Fuses gG, gL [A] 10 10
Rated Supply Current [V] 24 120 240 24 120 240 415 690
  AC-15 [A] 4 3 1.5 6 5 3 2 0.7
  DC-13 [V] 24 120 240 24 120 240 415  
  [A] 2 0.5 0.25 2 0.5 0.25 0.15  
Terminal Parts
    Type of terminals
Click to enlarge - 140M-29-1
Screwdriver Pozidriv No. 2/Blade No. 3
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.5…1.5/18…14
0.75…1.5/18…14
0.5…2.5/18…14
0.75…2.5/18…14
Click to enlarge - 140M-29-5 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…1.5/18…14
0.75…1.5/18…14
0.75…2.5/18…14
0.75…2.5/18…14
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…1.5/18…14
0.75…1.5/18…14
0.75…2.5/18…14
0.75…2.5/18…14
Tightening torque [N•m]/[lb•in] 1.2…1.5/10.6…13 1.2…1.5/10.6…13
  

  Undervoltage Trip
for Left-Side Mounting
Cat. No. 140M-C-UX…
Undervoltage Trip
with 2 Auxiliary Contacts
for Left-Side Mounting
Cat. No. 140M-C-UC…
Shunt Trip
for Left-Side Mounting
Cat. No. 140M-C-SN…
Actuating Voltage      
Pull-in
Drop-out
0.85…1.1 x Us
0.7…0.35 x Us
0.85…1.1 x Us
0.7…0.35 x Us
0.7…1.1 x Us
Rated Control Voltage
min.
max.
21V 50 Hz, 24V 60 Hz
600V 50 Hz
21V 50 Hz, 24V 60 Hz
600V 50 Hz
21V 50 Hz, 24V 60 Hz
600V 50 Hz
On-Time 100% 100% 100%
Coil Rating
Pull-in
Hold
8.5 VA, 8 W
4 VA, 2 W
8.5 VA, 8 W
4 VA, 2 W
8.5 VA, 8 W
4 VA, 2 W
Terminal Parts
    Type of terminals
Click to enlarge - 140M-29-1
Screwdriver Pozidriv No. 2/Blade No. 3
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.5…2.5/No. 18…14
0.75…2.5/No. 18…14
Click to enlarge - 140M-29-5 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75…2.5/No. 18…14
0.75…2.5/No. 18…14
Tightening torque [N•m]/[lb•in] 1.2…1.5/10.6…13.3
  

  Compact Busbar Feeder Terminal Compact Busbar Compact Busbar Feeder Block
Rated Thermal Current Ith
at 60 °C ambient temperature
  140M-C-WTN
140M-C-WTEN
140M-F-WTE 140M-C
-W…
140M-F
-W…
140M-C-WBE
L1, L2, L3
140M-C-WBE
T1, T2, T3
140M-F-WBE
L1, L2, L3
140M-F-WBE
T1, T2, T3
[A] 64 120 64 120 64 IEC 120/UL 115
Click to enlarge - 140M-29-4 1. conductor [mm2]/[AWG] 2.5…25/14…4 4…25/10…4 for use with
140M-C-W
4…50/10…4 for use with
140M-F-W
Click to enlarge - 140M-29-5 1. conductor [mm2]/[AWG] 2.5…25/14…4 4…50/12…1/0 4…25/10…4 for use with
140M-C-W
4…25/10…4 for use with
140M-F-W
Click to enlarge - 140M-29-6 1. conductor [mm2]/[AWG] 2.5…25/14…4 2.5…50/12…1/0 2.5…25/14…4 for use with
140M-C-W
2.5…25/14…4 for use with
140M-F-W
Tightening torque [N•m]/[lb•in] 3…3.5/27…31 5…6/45…54 3…3.5/27…31 2.5…3/23…27 5…6/45…54
  

Accessories for Bulletin 140M Screwless

Cat. No. 140M-RC…
Terminal Parts
    Type of terminals
Click to enlarge - 140M-RC_Screwless
Screwdriver Click to enlarge - 140M-RC_Screwless_1
Click to enlarge - 140M-29-4 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
0.5…1.5/—
0.5…1.5/—
Click to enlarge - Conductor_var2 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
0.5…1.5/No. 18…14
0.5…1.5/No. 18…14
Click to enlarge - 140M-29-6 1. conductor
2. conductor
[mm2 ]/[AWG]
[mm2 ]/[AWG]
0.5…1.5/No. 18…14
0.5…1.5/No. 18…14
  

Weights

Description Weight [g] Cat.No.
Motor Protection Circuit Breakers 317 140M-C2E-…
373 140M-D8E-…
782 140M-F8E-…
315 140M-C2N-…
365 140M-D8N-…
782 140M-F8N-…
315 140M-C2T-…
365 140M-D8T-…
782 140M-F8T-…
1845 140-CMN-…
Auxiliary Contacts 10 140M-C-AFA10
140M-C-AFA01
140M-C-AFA11
140M-C-AFA20
140M-C-ASA…
15 140M-C-AFAR10A…
140M-C-ASAR…M…
140M-C-ASAM11
31 140-CA…
Undervoltage Trip 108 140M-C-UX…
110 140M-C-SN…
116 140M-C-UC…
94 140-CUV…
Trip Contact Blocks 31 140-CT…
Shunt Trip 94 140-CRT…
  

Description Weight [g] Cat.No.
Anti-Tamper Cover 2 140M-C-CA
Lockable Twist Knob 5 140M-C-KN1
140M-C-KRY1
Locking Tag 30 140M-C-M3
Door Coupling Handle 123 140M-C-DN66
140M-C-NRY66
Extension Shaft 46 140M-C-DS
Legend Plate 4 140M-C-DFC…
Feeder Terminal 51 140M-C-WTEN
172 140M-F-WT
Compact Busbars 27 140M-C-W452N
48 140M-C-W453N
69 140M-C-W454N
90 140M-C-W455N
30 140M-C-W542N
55 140M-C-W543N
80 140M-C-W544N
105 140M-C-W545N
Top Hat Rail Adpapter 6 140-KBH2
  

Accessories for Bulletin 140-CMN Circuit Breakers

  Cat. No. 140-CT
Trip Contact Block for Flush Mounting on Cat.
No. 140-CMN Circuit Breakers
Cat. No. 140-CRT, 140-CUV
Undervoltage Trip and Shunt Trip for Flush Mounting on
Cat. No. 140-CMN Circuit Breakers
Rated Thermal Current Ith
up to 40 °C ambient temperature
up to 60 °C ambient temperature

[A]
[A]

10
6

2
2
NEMA contact class
(UL/CSA-Approval)

AC
DC

B 600 Standard Pilot Duty
R 300 Light Pilot Duty
Make/Break max. voltage
432 VA72 VA480 V
28 VA28 VA250 V
Back-Up Fuse gG, gL 16 A 16 A
Rated Current Ie                      
AC-15: [V]
[A]
230
3
400
2.5
500
1.5
690
0.75
  AC-14: 24
1.5
110
1.5
230
1.0
400
1.0
500
0.75
DC-13: [V]
[A]
24
2
48
0.6
110
0.2
230
0.1
440
0.04
DC 13: 24
1.5
48
0.5
60
0.4
110
0.2
 
Terminals Click to enlarge - 140M-29-1 Click to enlarge - 140M-29-1
Screwdriver    
Click to enlarge - 140M-29-4 1.conductor
2.conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
Click to enlarge - 140M-29-5 1.conductor
2.conductor
[mm2]/[AWG]
[mm2]/[AWG]
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
0.75… 2.5/No. 18… 14
Tightening torque [N•m]/[lb•in] 1… 1.5/8.8… 10.3 1… 1.5/8.8… 10.3
  

  Cat. No. 140-CUV…
Undervoltage Trip Unit for Right-Side Mounting on
Cat. No. 140-CMN Circuit Breakers
Cat. No. 140-CRT...
Shunt Trip for Flush Mounting on
Cat. No. 140-CMN Circuit Breakers
Operating Voltage    
Pick-up 0.8… 1.1 x Us 0.7… 1.1 x Us
Drop-out 0.7… 0.35 x Us
Duty cycle 100 % ED 100 % ED
Control Voltage    
  min. 12 V 50 Hz/14 V 60 Hz 12 V 50 Hz/14 V 60 Hz
    max. 600 V 50 Hz 600 V 50 Hz
Coil Performance    
Pick-up
Drop-out
[VA/W]
[VA/W]
11 / 8
4 / 1
12 / 7
6 / 2
Terminals
Terminal type
Click to enlarge - 140M-29-1 Click to enlarge - 140M-29-1
Click to enlarge - 140M-29-4 Fine-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5
Click to enlarge - 140M-29-5 Coarse-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5
Tightening torque [Nm] 1… 1.5 1… 1.5
Click to enlarge - 140M-29-5 Coarse-stranded [AWG] No. 18…. 14 No. 18…. 12
Tightening torque [lb•in] 8.8… 10.3 8.8… 10.3
  

Cut-off current

Click to enlarge - 140M-32-1


The Bulletin 140-M limits solid short-circuit current ICC (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system short-circuit current.

Bulletin 140M-C Circuit Breaker (Maximum Cut-Off Current)

Click to enlarge - Cut-Off Current 140M-C2E_400V


Click to enlarge - Cut-Off Current 140M-C2E_500V


Click to enlarge - Cut-Off Current 140M-C2E_690V


Bulletin 140M-D Circuit Breaker (Maximum Cut-Off Current)

Click to enlarge - Cut-Off Current 140M-D8E_400V


Click to enlarge - Cut-Off Current 140M-D8E_500V


Click to enlarge - Cut-Off Current 140M-D8E_690V


Bulletin 140M-F Circuit Breaker (Maximum Cut-Off Current)

Click to enlarge - Cut-Off Current 140M-F8E_400V


Click to enlarge - Cut-Off Current 140M-F8E_500V


Click to enlarge - Cut-Off Current 140M-F8E_690V


Bulletin 140M-C Circuit Breaker (Maximum Let-Through-Energy)

Click to enlarge - Let-Through-Energy 140M-C2E_400V


Click to enlarge - Let-Through-Energy 140M-C2E_500V


Click to enlarge - Let-Through-Energy 140M-C2E_690V


Bulletin 140M-D Circuit Breaker (Maximum Let-Through-Energy)

Click to enlarge - Let-Through-Energy 140M-D8E_400V


Click to enlarge - Let-Through-Energy 140M-D8E_500V


Click to enlarge - Let-Through-Energy 140M-D8E_690V


Bulletin 140M-F Circuit Breaker (Maximum Let-Through-Energy)

Click to enlarge - Let-Through-Energy 140M-F8E_400V


Click to enlarge - Let-Through-Energy 140M-F8E_500V


Click to enlarge - Let-Through-Energy 140M-F8E_690V


Time-Current Characteristic

Bulletin 140M-C, -D, -F Motor Protection Circuit Breakers

Click to enlarge - 140M-C_D19_EN


Bulletin 140-CMN Motor Protector

Click to enlarge - 140M-34-1


1) Thermal Release Trip Current

The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20 °C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single-phasing. The overload characteristic is also valid for transformer protection.

2) Magnetic Release Trip Current

The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13…14 times the maximum value of setting range. (Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher.

Current Setting IeF

The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC947-4-1. If a different value is prescribed (e.g., reduced Ie for cooling medium having a temperature higher than 40 °C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current Ie of the motor.