Catalogs > Industrial Controls Catalog > Motor Control, IEC > Motor Protection Circuit Breakers and Motor Circuit Protectors > Bulletin 140A Manual Motor Starters
Bulletin 140A Manual Motor Starters
SpecificationsIEC Performance Data
| Cat. No. 140A-C2A-… | ||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | ||
| Rated Operational Current Ie | [A] | 0.16 | 0.25 | 0.4 | 0.63 | 1.0 | 1.6 | 2.5 | 4.0 | 6.3 | 10 | 16 |
| Magnetic Release Current | [A] | 1.8 | 2.8 | 4.4 | 6.9 | 11 | 18 | 28 | 44 | 69 | 110 | 176 |
| Switching of Standard Three-Phase Motors ¬ | ||||||||||||
| AC-2, AC-3 | ||||||||||||
| 230/240V | [kW] | — | — | — | 0.06/0.09 | 0.12 | 0.18/0.25 | 0.37 | 0.55/0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 |
| 400/415V | [kW] | 0.02 | 0.06 | 0.09 | 0.18/0.25 | 0.25 | 0.37/0.55 | 0.75 | 1.1/1.5 | 2.2 | 3.0/4.0 | 5.5/7.5 |
| 500V | [kW] | — | — | — | 0.18 | 0.25/0.37 | 0.55/0.75 | 1.1 | 1.5/2.2 | 2.5/3.0 | 4.0/6.3 | 7.5/10 |
| 690V | [kW] | — | — | — | 0.25 | 0.37/0.55 | 0.75/1.1 | 1.8 | 2.2/3.0 | — | — | — |
| Back-Up Fuses | ||||||||||||
| gG, aM, only if Icc³Icu | ||||||||||||
| 230/240V | [A] | No fuses required | 50 | |||||||||
| 400/415V | [A] | 63 | 50 | |||||||||
| 500V | [A] | 63 | 50 | 50 | ||||||||
| 690V | [A] | 25 | 35 | — | — | — | ||||||
| Ultimate- (Icu) and Rated Service (Ics) Short Circuit Breaking Capacity | ||||||||||||
| Icu = Ics | ||||||||||||
| 230/240V | [kA] | 65 | 65 | 65 | 65 | 65 | 65 | 50 | 50 | 50 | 50 | 3 |
| 400/415V | [kA] | 65 | 65 | 65 | 65 | 65 | 65 | 50 | 10 | 10 | 8 | 6 |
| 500V | [kA] | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 3 | 10 | 4.5 | 4.5 |
| 690V | [kA] | 50 | 50 | 50 | 50 | 50 | 50 | 4.5 | 2 | — | — | — |
| ¬ Power ratings: Preferred values according to IEC 60072-1 | ||||||||||||
UL / CSA Performance Data
Manual Motor Controller
(UL 508, CSA C22.2 No.14, for group installation, in combination with a short-circuit protection device)
| Cat. No. 140A-C2A-… | ||||||||||||
| A16 | A25 | A40 | A63 | B10 | B16 | B25 | B40 | B63 | C10 | C16 | ||
| Max. short-circuit current | ||||||||||||
| 480V | [kA] | 42 | 42 | 42 | 42 | 42 | 42 | 42 | 18 | 18 | 10 | 5 |
| 600V | [kA] | 42 | 42 | 42 | 42 | 42 | 42 | 10 | 5 | 5 | 5 | 5 |
| Motor load | ||||||||||||
| 1-phase | ||||||||||||
| 115V | [HP] | — | — | — | — | — | — | 1/10 | 1/8 | 1/4 | 1/2 | 1 |
| 230V | [HP] | — | — | — | — | — | 1/10 | 1/6 | 1/3 | 3/4 | 1-1/2 | 3 |
| 3-phase | ||||||||||||
| 200V | [HP] | — | — | — | — | — | — | 1/2 | 3/4 | 1-1/2 | 2 | 3 |
| 230V | [HP] | — | — | — | — | — | — | 3/4 | 1 | 2 | 3 | 5 |
| 460V | [HP] | — | — | — | — | 1/2 | 1 | 1-1/2 | 3 | 5 | 7-1/2 | 10 |
| 575V | [HP] | — | — | — | — | 3/4 | 1 | 2 | 3 | 5 | 10 | 15 |
| Maximum rated current of protection device | ||||||||||||
| [A] | 175 | |||||||||||
Specifications
General Data
| Cat. No. | 140A-C2A | |
| Rated Insulation Voltage Ui | ||
| EN/IEC | [V] | 690 |
| UL, CSA | [V] | 600 |
| Overvoltage Category / Pollution degree | lll / 3 | |
| Rated Impulse Withstand Voltage Uimp | ||
| Main circuits | 6 kV | |
| Auxiliary circuits | 6 kV | |
| Rated Frequency | [Hz] | 40…60 |
| Life Span | ||
| Mechanical | [operations] | 100000 |
| Electrical (Ie max.) | [operations] | 50000 |
| Switching Frequency | [operations/h] | max. 30 |
| Ambient Temperature | ||
| Storage | [°C] | - 25…+ 80 |
| Operation | [°C] | - 25…+ 60 |
| Resistance to Climatic Stress | C IV (according to IEC 68) | |
| Moisture/heat resistance | 40 °C, 92 %, 56 days | |
| Moisture/change resistance | 23 °C, 83 %/40 °C, 93 %, 56 cycles |
|
| Site Altitude | [m] | £ 2000 |
| Protection Class | IP20, when wired | |
| Resistance to Shock | [g] | 50, 11ms |
| Resistance to Vibration | ||
| Frequency range | [Hz] | 10…150 |
| in all directions | [g] | 7.5 |
| Rated Thermal Current Ith | ||
| IEC | ||
| up to 40°C ambient temperature | [A] | 0.1…16 |
| up to 60°C ambient temperature | [A] | 0.1…16 |
| Rated Supply Current Ie | [A] | 0.1…16 |
| Number of setting ranges | 11 | |
| Dependence on Temperature | ||
| 40 °C | [A] | no reduction |
| 50 °C | [A] | |
| 60 °C | [A] | |
| 70 °C | [A] | 15 % current reduction of the upper rated current Ie |
| Overload Protection | ||
| Characteristics | EN/IEC 60947-4-1 Motor protection |
|
| Ambient Temperature Compensation | [°C] | - 20…+ 60 |
| Trip class | 10 | |
| Magnetic Release | fixed setting | |
| Release current | 11 x Ie max. Ie max. = maximum values of setting ranges |
|
| Total Power dissipation | ||
| Manual motor starter at rated load | [W] | 7 |
| Main Supply Application | Usable as main supply switch according to EN/IEC 60-204 with corresponding accessories | |
Weights
| Description | Cat. No. | Weight |
| Manual Motor Starter | 140A-C2A-… | 290 g |
| Auxiliary Contact Blocks for Flush Mounting | 140A-C-AEA… | 12 g |
| Auxiliary Contact Blocks for Left-side Mounting | 140A-C-ASA… | 35 g |
| Undervoltage Release | 140A-C-UX… | 104 g |
| Shunt Release | 140A-C-SX… | 100 g |
| Bus Bar Feeder Terminal | 140A-C-WT | 36 g |
| Compact Bus Bar | 140A-C-W452 | 42 g |
| 140A-C-W453 | 69 g | |
| 140A-C-W454 | 94 g | |
| 140A-C-W455 | 119 g | |
| 140A-C-W542 | 45 g | |
| 140A-C-W543 | 76 g | |
| 140A-C-W544 | 104 g | |
| 140A-C-W545 | 135 g | |
| Blank Space Cover | 140A-C-WS | 3.3 g |
| Enclosure for Surface Mounting | 140A-C-EA41 | 250 g |
| 140A-C-EA55 | 258 g | |
| Enclosure for Flush Mounting | 140A-C-EE41 | 126 g |
| 140A-C-EE55 | 134 g | |
| Button Membrane | 140A-C-N55 | 8 g |
| Indicator Light | 140-L… | 10 g |
| Hut (DIN) rail Adapter | 140A-C-N12 | 16 g |
| Locking Arrangement | 140A-C-M3E | 19 g |
| 140A-C-M3 | 11 g | |
Specifications
Specifications of Accessories
| Cat. No. 140A-C-W45... Compact Bus Bar |
Cat. No. 140A-C-W54... Compact Bus Bar |
||
| Rated Insulation Voltage Ui | [V] | 690 | 690 |
| Rated Thermal Current Ith | [A] | 63 | 63 |
| Cat. No. 140A-C-EA41 / -EE41 Enclosure |
Cat. No. 140A-C-EA55 / -EE55 Enclosure |
Cat. No. 140-L... Indicator light |
||
| IP Protection | IP41 | IP55 (with seal and protective membrane) |
IP54 | |
| Ambient Temperature | [°C] | - 25…+ 40 | - 25…+ 40 | — |
| Rated Operating Voltage | [V] | — | — | 120, 240, 415, 480 |
Specifications
Cut-off current
The Bulletin 140A-C2A manual motor starter limits short-circuit current Icc (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagram as a function of the system short-circuit current.
|
|
|
Correspondingly the maximum forward i2 dt energy is limited. This value is indicated in the following diagram as a function of the system short-circuit current.
|
1) Operating Current of Thermal Releases:
The adjustable inverse bimetal trip reliability protects motors against overloads. The curve shows the mean operating current at an ambient temperature of 20 °C starting from cold.
In equipment at operating temperature, release time is less than or equal to release time from the cold state.
2) Operating Current of Magnetic Releases:
Electromagnetic instantaneous releases react at a fixed tripping current.
At the upper thermal release setting, this tripping current is 11 times the set current.
Current To Be Set:
Thermal releases meet the requirements for a thermal release of a starter in accordance with IEC 60947-4-1 f. If a different value is specified (such as reduced Ie in motors with an ambient temperature higher than 40 °C or a site altitude >2000 m above sea level), the rated operating current Ie must be adjusted.
-
Performance categories per IEC 60947-2:
Icu
Rated short-circuit breaking capacity Operational after completing O-t-CO test sequence
Ics
Ultimate short-circuit breaking capacity Suitable for normal operation after completing O-t-CO-t-CO test sequence
O
= off
CO
= restart and off
t
= set delay, 3 min