Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140U D-Frame
Bulletin 140U D-Frame
Product Selection — 30 A, D-Frame
|
-
Standards
- UL 489
- CSA C22.2, No. 5
- IEC / EN 60947-1, -2
Ratings
- HACR
2-Pole Thermal-Magnetic, Fixed Thermal-Fixed Magnetic
| Rated Current In |
Thermal Trip (Fixed) Ir = In |
Magnetic Trip Im = |
Breaking Capacity (50 Hz) [kA] |
Interrupting Rating (60 Hz) [kA] |
Cat. No. ⋆ | |||||||||
| 230…240V | 400…415V | 525V | 690V | 240V AC | 480Y/277V AC | 600Y/347V AC | ||||||||
| [A] | [A] | [A] | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | ||||
| 0.5 | 0.5 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 50 | 50 | 100 | 100 | 50 | 140U-D6D2-A50 |
| 1 | 1 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 50 | 50 | 100 | 100 | 50 | 140U-D6D2-B10 |
| 2 | 2 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D2-B20 |
| 3 | 3 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D2-B30 |
| 4 | 4 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D2-B40 |
| 5 | 5 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D2-B50 |
| 6 | 6 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D2-B60 |
| 8 | 8 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 10 | 6 | 100 | 100 | 50 | 140U-D6D2-B80 |
| 10 | 10 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 10 | 6 | 100 | 100 | 50 | 140U-D6D2-C10 |
| 12 | 12 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 50 | 10 | 6 | 65 | 65 | 35 | 140U-D6D2-C12 |
| 15 | 15 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 50 | 10 | 6 | 65 | 65 | 35 | 140U-D6D2-C15 |
| 20 | 20 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 50 | 10 | 6 | 65 | 65 | 35 | 140U-D6D2-C20 |
| 25 | 25 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 25 | 10 | 6 | 65 | 65 | 35 | 140U-D6D2-C25 |
| 30 | 30 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 25 | 10 | 6 | 65 | 65 | 35 | 140U-D6D2-C30 |
| ⋆ Current limiting | ||||||||||||||
3-Pole Thermal-Magnetic, Fixed Thermal-Fixed Magnetic
| Rated Current In |
Thermal Trip (Fixed) Ir = In |
Magnetic Trip Im = |
Breaking Capacity (50 Hz) [kA] |
Interrupting Rating (60 Hz) [kA] |
Cat. No. ⋆ | |||||||||
| 230…240V | 400…415V | 525V | 690V | 240V AC | 480Y/277V AC | 600Y/347V AC | ||||||||
| [A] | [A] | [A] | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | ||||
| 0.5 | 0.5 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 50 | 50 | 100 | 100 | 50 | 140U-D6D3-A50 |
| 1 | 1 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 50 | 50 | 100 | 100 | 50 | 140U-D6D3-B10 |
| 2 | 2 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D3-B20 |
| 3 | 3 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D3-B30 |
| 4 | 4 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D3-B40 |
| 5 | 5 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D3-B50 |
| 6 | 6 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 18 | 10 | 100 | 100 | 50 | 140U-D6D3-B60 |
| 8 | 8 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 10 | 6 | 100 | 100 | 50 | 140U-D6D3-B80 |
| 10 | 10 | 15…20 x In | 100 | 100 | 100 | 65 | 65 | 65 | 10 | 6 | 100 | 100 | 50 | 140U-D6D3-C10 |
| 12 | 12 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 50 | 10 | 6 | 65 | 65 | 35 | 140U-D6D3-C12 |
| 15 | 15 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 50 | 10 | 6 | 65 | 65 | 35 | 140U-D6D3-C15 |
| 20 | 20 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 50 | 10 | 6 | 65 | 65 | 35 | 140U-D6D3-C20 |
| 25 | 25 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 25 | 10 | 6 | 65 | 65 | 35 | 140U-D6D3-C25 |
| 30 | 30 | 15…20 x In | 100 | 100 | 65 | 50 | 65 | 25 | 10 | 6 | 65 | 65 | 35 | 140U-D6D3-C30 |
| ⋆ Current limiting | ||||||||||||||