Bulletin 140U Product Line Overview

Click to enlarge - 140U_Fam_1


Bulletin 140U Molded Case Circuit Breakers


Standards Compliance and Certifications

Standards Compliance

UL 489
CSA C22.2, No. 5
EN/IEC 60947-2
CCC (most frame sizes)


Certifications

UL Listed
CSA Certified
CE Marked
KEMA


Product Line Overview

  Click to enlarge - 140U-D6D3_L Click to enlarge - 140U_G_breaker Click to enlarge - 140U-39-2 Click to enlarge - 140U-39-3 Click to enlarge - 140U-39-4 Click to enlarge - 140UE-L6-09189_bw Click to enlarge - 140U-39-6 Click to enlarge - 140U-39-7 Click to enlarge - 140U-R_center2
Frame Reference D-Frame G-Frame H-Frame J-Frame K-Frame L-Frame M-Frame N-Frame R-Frame
Max. Current In 30 A 100 A 125 A 250 A 400 A 600 A 800 A 1200 A 2500 A
Current Range 0.5…30 A 15…100 A 15…125 A 70…250 A 100…400 A 300…600 A 300…800 A 600…1200 A 800…2500 A
Thermal Magnetic ü ü ü ü ü ü ü
Electronic:
LS ü ü ü ü ü ü
LSI ü ü ü ü ü ü
LSII ü ü
LSG ü ü ü ü ü ü
LSIG ü ü ü ü ü ü
LSIIG ü ü
Interrupting Ratings:
380…415V (Icu) see
selection
table
14    22 25    40    70 25    40    70    100 40    65    100 45    70    100 50    70 50    70    100
480V 14    22 25    35    65    100 25    35    65    100 35    65    100 35    65    100 50    65 50    65    100 65    100
600V 18    22    25    35 18    18    25    35 25    35    50 25    35    50 25    35 25    35    50
690V (Icu)  3     4     6  6     6     7    12 10    13    18 20    25    15 20    25 20    25    30
Molded Case Switches ü ü ü ü ü ü ü
Flex Cable Operators ü ü ü ü ü ü ü
Rotary Operators ü ü ü ü ü ü ü ü ü
Internal Control Modules
(Field installed)
ü ü ü ü ü ü ü ü ü
Standards Compliance (For information regarding specific breakers, please consult www.ab.com. Standards compliance varies by catalog number.)
UL 489 ü ü ü ü ü ü ü ü ü
UL File Nos. E334037,
E33916
E197878, Guide No. DIV Q
CSA C22.2, No. 5 ü ü ü ü ü ü ü ü ü
CSA File Nos. 216034, 216035, 219884 Class No. 1432-01
IEC 60947-2 ü ü ü ü ü ü ü ü
CE ü ü ü ü ü ü ü
KEMA ü ü ü ü ü ü
CCC ü ü ü ü ü ü
 

Catalog Number Explanation

Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options.

Complete Circuit Breaker Assemblies

140U H    6    C    3 C50 H      
a    b    c    d    e    f    g    h

a    b    c    d
Bulletin Number Frame/Rating Interrupting Rating/Breaking Capacity
(based on Ic at 480V)
Protection Type
Code Description Code Description Code Description Code Description
140U Molded Case Circuit Breaker D 30 A 2 20…29 kA C Fixed thermal/fixed magnetic
  G 100 A 3 30…39 kA D Fixed thermal/adjust magnetic
H 125 A 5 50…59 kA E Adjust thermal/fixed magnetic
J 250 A 6 60…69 kA F Adjust thermal/adjust magnetic
K 400 A 8 80…89 kA G Electronic (LSG — long, short,
ground fault)
L 600 A 0 ³100 kA H Electronic (LSI — long, short,
high instant)
M 800 A   I Electronic (LSIG — long, short,
high instant, ground fault)
N 1200 A J Electronic (LSII — long, short,
high instant, instantaneous maintenance mode)
R 2500 A K Electronic (LSIIG — long, short,
high instant, instantaneous maintenance mode, ground fault)
  L Electronic (LS — long and short time)
S Molded case switch (Isolator)
  
e    f    g    h
Poles Current Range Internal Control Modules Voltage Code
Code Description Code Description Code Description See the following for voltage code descriptions:
1 1 poles C 10 rr. A A 1 auxiliary contact All frame sizes Internal Control Modules — Factory Installed
For use with H-, J-, K-, L-, M-, and N-Frame Molded Case Circuit Breakers
2 2 poles D 100 rr0 A B 2 auxiliary contacts  
3 3 poles E 1000 rr00 A D 1 alarm contact
    F 1 auxiliary + 1 alarm contact
G Undervoltage release only
P Shunt trip only
Control Module Combinations
Code Description
H 1 auxiliary contact + undervoltage release
J 2 auxiliary contacts + undervoltage release
L 1 auxiliary + 1 alarm contact + undervoltage release
N 1 alarm contact + undervoltage release
Q 1 auxiliary contact + shunt trip
R 2 auxiliary contacts + shunt trip
T 1 auxiliary + 1 alarm contact + shunt trip
V 1 alarm contact + shunt trip

Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options.

Frames

140U J    3    X    3
a    b    c    d    e

a    b    c    d
Bulletin Number Frame/Rating Interrupting Rating / Breaking Capacity Protection Type
Code Description Code Description Code Description Code Description
140U Molded Case Circuit Breaker J 250 A 2 20…29 kA X Frame Only
  K 400 A 3 30…39 kA  
Q 600 A 5 50…59 kA
M 800 A 6 60…69 kA
  8 80…89 kA
0 ³100 kA
  
e     
Poles
Code Description
3 3 poles

Trip Units

140U J    T    D    3 D25
a    b    c    d    e    f

a    b    c    d
Bulletin Number Frame/Rating Trip Unit Protection Type
Code Description Code Description Code Description Code Description
140U Molded Case Circuit Breaker J 250 A T Trip unit C Fixed thermal/fixed magnetic
  K 400 A   D Fixed thermal/adjust magnetic
L 600 A E Adjust thermal/fixed magnetic
M 800 A F Adjust thermal/adjust magnetic
  G Electronic (LSG — long, short,
ground fault)
H Electronic (LSI — long, short,
high instant)
I Electronic (LSIG — long, short,
high instant, ground fault)
J Electronic (LSII — long, short,
high instant, instantaneous maintenance mode)
K Electronic (LSIIG — long, short,
high instant, instantaneous maintenance mode, ground fault)
L Electronic (LS — long and short time)
S Molded case switch (Isolator)
  
e    f     
Poles Current Range
Code Description Code Description
3 3 poles C 10 rr. A
  D 100 rr0 A
E 1000 rr00 A