Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140U K-Frame
Bulletin 140U K-Frame
| Product Selection — 400 A, K-Frame | Accessories — 400 A, K-Frame | Approximate Dimensions — 400 A, K-Frame |
|
- UL 489
- CSA 22.2, No. 5
- IEC 157-1
- KEMA-KEUR
Note: Terminal lugs must be ordered separately. See Optional Terminal Lug Kits
Breaker Frames
| Rated Current In [A] | Breaking Capacity (50 Hz) Icu /Ics [kA] |
Interrupting Rating (60 Hz) [kA] | Cat. No. | |||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600V | ||||||
| 400 | 65 | 65 | 40 | 40 | 30 | 30 | 10 | 5 | 65 | 35 | 25 | 140U-K3X3 |
| 100 | 100 | 35 | 35 | 50 | 38 | 13 | 6 | 100 | 65 | 35 | 140U-K6X3 | |
| 200 | 200 | 100 | 100 | 65 | 49 | 18 | 9 | 200 | 100 | 65 | 140U-K0X3 | |
Trip Units and Rating Plugs
| Thermal-Magnetic | |||
| Rated Current In [A] | Adjustment Range [A] | Cat. No. | |
| Thermal Trip [A] Ir = In (Fixed) |
Magnetic Trip Im = 5…10 x In |
||
| 100 | 100 | 500…1000 | 140U-KTD3-D10 |
| 125 | 125 | 625…1250 | 140U-KTD3-D12 |
| 150 | 150 | 750…1500 | 140U-KTD3-D15 |
| 175 | 175 | 895…1750 | 140U-KTD3-D17 |
| 200 | 200 | 1000…2000 | 140U-KTD3-D20 |
| 225 | 225 | 1125…2250 | 140U-KTD3-D22 |
| 250 | 250 | 1250…2500 | 140U-KTD3-D25 |
| 300 | 300 | 1500…3000 | 140U-KTD3-D30 |
| 350 | 350 | 1750…3500 | 140U-KTD3-D35 |
| 400 | 400 | 2000…4000 | 140U-KTD3-D40 |
| Electronic | ||||
| Rated Current In [A] | Adjustment Range [A] | Protection Type | Cat. No. | |
| Thermal Trip Ir = 0.5…1.0 x In |
Magnetic Trip Im = 2…8 x Ir |
|||
| 400 | 200…400¬ | 400…3200 | LS | 140U-KTL3-D40 |
| LSI | 140U-KTH3-D40 | |||
| LSG | 140U-KTG3-D40 | |||
| LSIG | 140U-KTI3-D40 | |||
| Electronic trip units require the use of a rating plug. Select proper rating plug to cover thermal trip requirement. | ||||
| Rating Plugs | |||
| Thermal Trip In [A] | Cat. No. | Thermal Trip In [A] | Cat. No. |
| 200 | 140U-KRP3-D20 | 300 | 140U-KRP3-D30 |
| 225 | 140U-KRP3-D22 | 350 | 140U-KRP3-D35 |
| 250 | 140U-KRP3-D25 | 400 | 140U-KRP3-D40 |
Assembled Circuit Breakers, Thermal-Magnetic Trip Units
| Rated Current In [A] | Breaking Capacity/ Interrupting Rating [kA]T |
Cat. No. | Breaking Capacity/ Interrupting Rating [kA]T |
Cat. No. | Breaking Capacity/ Interrupting Rating [kA]T |
Cat. No. | |||
| 400V | 480V | 400V | 480V | 400V | 480V | ||||
| 100 | 40 | 35 | 140U-K3D3-D10 | 65 | 65 | 140U-K6D3-D10 | 100 | 100 | 140U-K0D3-D10 |
| 125 | 40 | 35 | 140U-K3D3-D12 | 65 | 65 | 140U-K6D3-D12 | 100 | 100 | 140U-K0D3-D12 |
| 150 | 40 | 35 | 140U-K3D3-D15 | 65 | 65 | 140U-K6D3-D15 | 100 | 100 | 140U-K0D3-D15 |
| 175 | 40 | 35 | 140U-K3D3-D17 | 65 | 65 | 140U-K6D3-D17 | 100 | 100 | 140U-K0D3-D17 |
| 200 | 40 | 35 | 140U-K3D3-D20 | 65 | 65 | 140U-K6D3-D20 | 100 | 100 | 140U-K0D3-D20 |
| 225 | 40 | 35 | 140U-K3D3-D22 | 65 | 65 | 140U-K6D3-D22 | 100 | 100 | 140U-K0D3-D22 |
| 250 | 40 | 35 | 140U-K3D3-D25 | 65 | 65 | 140U-K6D3-D25 | 100 | 100 | 140U-K0D3-D25 |
| 300 | 40 | 35 | 140U-K3D3-D30 | 65 | 65 | 140U-K6D3-D30 | 100 | 100 | 140U-K0D3-D30 |
| 350 | 40 | 35 | 140U-K3D3-D35 | 65 | 65 | 140U-K6D3-D35 | 100 | 100 | 140U-K0D3-D35 |
| 400 | 40 | 35 | 140U-K3D3-D40 | 65 | 65 | 140U-K6D3-D40 | 100 | 100 | 140U-K0D3-D40 |
| Assembled circuit breakers can be created by adding a trip unit and rating plugs (electronic only) to a circuit breaker frame. Example: Cat. No. 140U-K3X3 + 140U-KTL3-D40 + 140U-KRP3-D35 | |||||||||
| T Full ratings are found in the breaker frames table on Breaker Frames | |||||||||
Assembled Circuit Breakers, Electronic Trip Units
| Rated Current In [A] | Thermal Trip Ir = 0.5…1.0 x In |
Protection Type | Breaking Capacity/ Interrupting Rating [kA]T |
Cat. No. | Breaking Capacity/ Interrupting Rating [kA]T |
Cat. No. | Breaking Capacity/ Interrupting Rating [kA]T |
Cat. No. | |||
| 400V | 480V | 400V | 480V | 400V | 480V | ||||||
| 400 | 100…400¬ | LS | 40 | 35 | 140U-K3L3-D40 | 65 | 65 | 140U-K6L3-D40 | 100 | 100 | 140U-K0L3-D40 |
| LSI | 40 | 35 | 140U-K3H3-D40 | 65 | 65 | 140U-K6H3-D40 | 100 | 100 | 140U-K0H3-D40 | ||
| LSG | 40 | 35 | 140U-K3G3-D40 | 65 | 65 | 140U-K6G3-D40 | 100 | 100 | 140U-K0G3-D40 | ||
| ¬ Select proper rating plug to cover thermal trip requirement. | |||||||||||
| T Full ratings are found in the breaker frames table on Breaker Frames | |||||||||||
Molded Case Switch — UL 489
| Rated Current In [A] | Magnetic Trip 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] | Interrupting Rating (60 Hz) [kA] | Cat. No. | |||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600V | |||||||
| 400 | 4000 | 100 | 100 | 65 | 65 | 50 | 38 | 13 | 6 | 100 | 65 | 35 | 140U-K6S3-D40 |
Optional Terminal Lug Kits