Molded Case Circuit Breakers

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140U K-Frame

Bulletin 140U K-Frame

Product Selection — 400 A, K-Frame Accessories — 400 A, K-Frame Approximate Dimensions — 400 A, K-Frame
Product Selection — 400 A, K-Frame

Click to enlarge - 140U-39-4



Note: Terminal lugs must be ordered separately. See Optional Terminal Lug Kits

Breaker Frames

Rated Current In [A] Breaking Capacity (50 Hz)
Icu /Ics [kA]
Interrupting Rating (60 Hz) [kA] Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V
400 65 65 40 40 30 30 10 5 65 35 25 140U-K3X3
100 100 35 35 50 38 13 6 100 65 35 140U-K6X3
200 200 100 100 65 49 18 9 200 100 65 §  140U-K0X3
  
§ Current limiting.

Trip Units and Rating Plugs

Thermal-Magnetic
Rated Current In [A] Adjustment Range [A] Cat. No.
Thermal Trip [A]
Ir = In (Fixed)
Magnetic Trip
Im = 5…10 x In
100 100 500…1000 140U-KTD3-D10
125 125 625…1250 140U-KTD3-D12
150 150 750…1500 140U-KTD3-D15
175 175 895…1750 140U-KTD3-D17
200 200 1000…2000 140U-KTD3-D20
225 225 1125…2250 140U-KTD3-D22
250 250 1250…2500 140U-KTD3-D25
300 300 1500…3000 140U-KTD3-D30
350 350 1750…3500 140U-KTD3-D35
400 400 2000…4000 140U-KTD3-D40
  

Electronic
Rated Current In [A] Thermal Trip‡ 
Ir = 0.5…1.0 x In
Magnetic Trip
Im = 2…8 x Ir
Protection Type Cat. No.
400 200…400 400…3200 LS 140U-KTL3-D40
LSI 140U-KTH3-D40
LSG 140U-KTG3-D40
LSIG 140U-KTI3-D40
  
‡ Electronic trip units require the use of a rating plug. Thermal trip rating is determined by the rating plug selection and is not adjustable.

Rating Plugs
Thermal Trip In [A] Cat. No. Thermal Trip In [A] Cat. No.
200 140U-KRP3-D20 300 140U-KRP3-D30
225 140U-KRP3-D22 350 140U-KRP3-D35
250 140U-KRP3-D25 400 140U-KRP3-D40
  

Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Current In [A] Breaking Capacity/
Interrupting Rating [kA]§ 
Cat. No. Breaking Capacity/
Interrupting Rating [kA]§ 
Cat. No. Breaking Capacity/
Interrupting Rating [kA]§ 
Cat. No.
400V 480V 400V 480V 400V 480V
100 40 35 140U-K3D3-D10 65 65 140U-K6D3-D10 100 100 140U-K0D3-D10
125 40 35 140U-K3D3-D12 65 65 140U-K6D3-D12 100 100 140U-K0D3-D12
150 40 35 140U-K3D3-D15 65 65 140U-K6D3-D15 100 100 140U-K0D3-D15
175 40 35 140U-K3D3-D17 65 65 140U-K6D3-D17 100 100 140U-K0D3-D17
200 40 35 140U-K3D3-D20 65 65 140U-K6D3-D20 100 100 140U-K0D3-D20
225 40 35 140U-K3D3-D22 65 65 140U-K6D3-D22 100 100 140U-K0D3-D22
250 40 35 140U-K3D3-D25 65 65 140U-K6D3-D25 100 100 140U-K0D3-D25
300 40 35 140U-K3D3-D30 65 65 140U-K6D3-D30 100 100 140U-K0D3-D30
350 40 35 140U-K3D3-D35 65 65 140U-K6D3-D35 100 100 140U-K0D3-D35
400 40 35 140U-K3D3-D40 65 65 140U-K6D3-D40 100 100 140U-K0D3-D40
  
Assembled circuit breakers can be created by adding a trip unit and rating plugs (electronic only) to a circuit breaker frame. Example: Cat. No. 140U-K3X3 + 140U-KTL3-D40 + 140U-KRP3-D35
§ Interrupting ratings shown are for 400V and 480V, respectively. The complete range of ratings can be found in the frame rating table on Breaker Frames.

Assembled Circuit Breakers, Electronic Trip Units

Rated Current In [A] Thermal Trip⋆ 
Ir = 0.5…1.0 x In
Protection Type Breaking Capacity/
Interrupting Rating [kA]‡ 
Cat. No. Breaking Capacity/
Interrupting Rating [kA]‡ 
Cat. No. Breaking Capacity/
Interrupting Rating [kA]‡ 
Cat. No.
400V 480V 400V 480V 400V 480V
400 200…400 LS 40 35 140U-K3L3-D40 65 65 140U-K6L3-D40 100 100 140U-K0L3-D40
LSI 40 35 140U-K3H3-D40 65 65 140U-K6H3-D40 100 100 140U-K0H3-D40
LSG 40 35 140U-K3G3-D40 65 65 140U-K6G3-D40 100 100 140U-K0G3-D40
  
⋆ Electronic trip units require the use of a rating plug. Thermal trip rating is determined by the rating plug selection and is not adjustable.
‡ Interrupting ratings shown are for 400V and 480V, respectively. The complete range of ratings can be found in the frame rating table on Breaker Frames

Molded Case Switch — UL 489

Rated Current In [A] Magnetic Trip
10 x In
Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V
400 4000 100 100 65 65 50 38 13 6 100 65 35 140U-K6S3-D40
  

Optional Terminal Lug Kits

Pictures shown are representative. Actual product may differ from product shown.


  Description Pkg. Quantity Cat. No.
Click to enlarge - 140U_K_TLA1A_right Terminal Lugs Aluminum lug, Al or Cu wire
(1) 3…350 MCM
or (1) 30…185 mm2
1 140U-K-TLA1A
Aluminum lug, Al or Cu wire
(1) 250…500 MCM
or (1) 120…240 mm2
140U-K-TLA1
Aluminum lug, Al or Cu wire
(2) 3/0…250 MCM
or (2) 95…120 mm2
3 (includes shield) 140U-K-TLA2
Click to enlarge - 140U_K_TLA2_right Terminal Lugs Copper lug, Cu wire only
(1) 3…350 MCM
or (1) 30…185 mm2
1 140U-K-TLC1A
Copper lug, Cu wire only
(1) 250…500 MCM
or (1) 120…240 mm2
140U-K-TLC1
Copper lug, Cu wire only
(2) 3/0…250 MCM
or (2) 95…120 mm2
3 (includes shield) 140U-K-TLC2
Aluminum lug, Al or Cu wire
(2) 2/0…250 MCM
or (1) 2/0…500 MCM,
(2) 70…120 mm2
or (1) 70…240 mm2
3 (includes shield) 140U-K-TLA2A
Aluminum lug, Al or Cu wire
(1) 500…750 MCM
or (1) 300…400 mm2
140U-K-TLA1B
Click to enlarge - 140U_K_TLC1B_right Terminal Lugs Copper lug, Cu wire only
(1) 500…750 MCM
or (1) 300…400 mm2
3 (includes shield) 140U-K-TLC1B
Click to enlarge - 140U_H_MTL3AN_right Multi-Tap Terminal Lug Kit — with IP20 terminal cover (3) #14…2/0 AWG
or (3) 4…67 mm2
3 140U-K-MTL3A
(6) #14…3 AWG
or (6) 2.5…33 mm2
3 140U-K-MTL6A