| Rated Current In [A]
|
Breaking Capacity (50 Hz) Icu /Ics [kA]
|
Interrupting Rating (60 Hz) [kA]
|
Cat. No.
|
| 220…240V
|
380…415V
|
525V
|
690V
|
240V
|
480V
|
600V
|
| 600
|
85
|
85
|
45
|
45
|
25
|
13
|
20
|
10
|
65
|
35
|
25
|
140U-L3X3
|
| 100
|
100
|
70
|
70
|
35
|
18
|
25
|
13
|
100
|
65
|
35
|
|
140U-L6X3
|
| 200
|
200
|
100
|
100
|
50
|
25
|
30
|
15
|
200
|
100
|
50
|
|
140U-L0X3
|
|
|
| Current Limiting
|
| Thermal-Magnetic
|
| Rated Current In [A]
|
Adjustment Range [A]
|
Cat. No.
|
Thermal Trip Ir = In (Fixed)
|
Magnetic Trip Im = 5…10 x In
|
| 250
|
250
|
1250…2500
|
140U-LTD3-D25
|
| 300
|
300
|
1500…3000
|
140U-LTD3-D30
|
| 350
|
350
|
1750…3500
|
140U-LTD3-D35
|
| 400
|
400
|
2000…4000
|
140U-LTD3-D40
|
| 500
|
500
|
2500…5000
|
140U-LTD3-D50
|
| 600
|
600
|
3000…6000
|
140U-LTD3-D60
|
|
|
| Electronic
|
| Rated Current In [A]
|
Adjustment Range [A]
|
Protection Type
|
Cat. No.
|
Thermal Trip Ir = 0.5…1.0 x In
|
Magnetic Trip Im = 2…10 x In
|
| 250
|
100…250
|
200…2500
|
LS
|
140U-LTL3-D25
|
| LSI
|
140U-LTH3-D25
|
| LSG
|
140U-LTG3-D25
|
| LSIG
|
140U-LTI3-D25
|
| 400
|
160…400
|
320…4000
|
LS
|
140U-LTL3-D40
|
| LSI
|
140U-LTH3-D40
|
| LSG
|
140U-LTG3-D40
|
| LSIG
|
140U-LTI3-D40
|
| 600
|
240…600
|
480…6000
|
LS
|
140U-LTL3-D60
|
| LSI
|
140U-LTH3-D60
|
| LSG
|
140U-LTG3-D60
|
| LSIG
|
140U-LTI3-D60
|
|
|
| Rated Current In [A]
|
Thermal Trip Ir = In
|
Breaking Capacity/Interrupting Rating [kA]T
|
Cat. No.
|
Breaking Capacity/Interrupting Rating [kA]T
|
Cat. No.
|
| 400V
|
480V
|
400V
|
480V
|
| 250
|
250
|
45
|
35
|
140U-L3D3-D25
|
70
|
65
|
140U-L6D3-D25
|
| 300
|
300
|
45
|
35
|
140U-L3D3-D30
|
70
|
65
|
140U-L6D3-D30
|
| 350
|
350
|
45
|
35
|
140U-L3D3-D35
|
70
|
65
|
140U-L6D3-D35
|
| 400
|
400
|
45
|
35
|
140U-L3D3-D40
|
70
|
65
|
140U-L6D3-D40
|
| 500
|
500
|
45
|
35
|
140U-L3D3-D50
|
70
|
65
|
140U-L6D3-D50
|
| 600
|
600
|
45
|
35
|
140U-L3D3-D60
|
70
|
65
|
140U-L6D3-D60
|
|
|
| T Full ratings are found in the breaker frames table on Breaker Frames
|
| Rated Current In [A]
|
Thermal Trip Ir = 0.5…1.0 x In
|
Protection Type
|
Breaking Capacity/ Interrupting Rating [kA]T
|
Cat. No.
|
Breaking Capacity/ Interrupting Rating [kA]T
|
Cat. No.
|
| 400V
|
480V
|
400V
|
480V
|
| 250
|
100…250
|
LS
|
45
|
35
|
140U-L3L3-D25
|
70
|
65
|
140U-L6L3-D25
|
| LSI
|
45
|
35
|
140U-L3H3-D25
|
70
|
65
|
140U-L6H3-D25
|
| LSG
|
45
|
35
|
140U-L3G3-D25
|
70
|
65
|
140U-L6G3-D25
|
| LSIG
|
45
|
35
|
140U-L3I3-D25
|
70
|
65
|
140U-L6I3-D25
|
| 400
|
160…400
|
LS
|
45
|
35
|
140U-L3L3-D40
|
70
|
65
|
140U-L6L3-D40
|
| LSI
|
45
|
35
|
140U-L3H3-D40
|
70
|
65
|
140U-L6H3-D40
|
| LSG
|
45
|
35
|
140U-L3G3-D40
|
70
|
65
|
140U-L6G3-D40
|
| LSIG
|
45
|
35
|
140U-L3I3-D40
|
70
|
65
|
140U-L6I3-D40
|
| 600
|
240…600
|
LS
|
45
|
35
|
140U-L3L3-D60
|
70
|
65
|
140U-L6L3-D60
|
| LSI
|
45
|
35
|
140U-L3H3-D60
|
70
|
65
|
140U-L6H3-D60
|
| LSG
|
45
|
35
|
140U-L3G3-D60
|
70
|
65
|
140U-L6G3-D60
|
| LSIG
|
45
|
35
|
140U-L3I3-D60
|
70
|
65
|
140U-L6I3-D60
|
|
|
| T Full ratings are found in the breaker frames table on Breaker Frames
|
| Rated Current In [A]
|
Magnetic Trip Im = 10 x In [A]
|
Breaking Capacity (50 Hz) Icu /Ics [kA]
|
Interrupting Rating (60 Hz) [kA]
|
Cat. No.
|
| 220…240V
|
380…415V
|
500V
|
690V
|
240V
|
480V
|
600V
|
| 600
|
6000
|
100
|
100
|
70
|
70
|
50
|
38
|
25
|
13
|
100
|
65
|
35
|
140U-L6S3-D63
|
|
|
|
|
Description
|
Cat. No.
|
|
Terminal Lugs
|
Aluminum lug, Al or Cu wire (1) 500…750 MCM or (1) 240…380 mm2
|
Qty: 3 (includes shield)
|
140U-L-TL6A1
|
Copper lug, Cu wire only (1) 500…750 MCM or (1) 240…380 mm2
|
Qty: 3 (includes shield)
|
140U-L-TL6C1
|
Aluminum lug, Al or Cu wire (2) 2…500 MCM or (2) 35…240 mm2
|
Qty: 3 (includes shield)
|
140U-L-TL6A2
|
|
Terminal Lugs
|
Copper lug, Cu wire only (2) 2…500 MCM or (2) 35…240 mm2
|
Qty: 3 (includes shield)
|
140U-L-TL6C2
|
Aluminum lug, Al or Cu wire (1) 2…500 MCM or (1) 35…240 mm2
|
Qty: 1
|
140U-L-TL4A1
|
Copper lug, Cu wire only (1) 2…500 MCM or (1) 35…240 mm2
|
Qty: 1
|
140U-L-TL4C1
|
|
|
|
|
Description
|
|
Diagram
|
Mounting Location
|
Cat. No.
|
|
Auxiliary Contact (AX) Electrically indicates "ON/OFF" status of breakers
|
(1) 1a-1b
|
|
|
140U-H-EA1
|
| (2) 1a-1b
|
Right side ONLY
|
140U-H-EA2
|
Alarm Contact (AL) Electrically indicates when the breaker is in the "TRIPPED" state
|
(1) 1M (make)-1B (break)
|
|
|
140U-J-ER1
|
| Right side ONLY
|
|
Auxiliary/Alarm Contact (AX/AL) Combination Combination of auxiliary contact and alarm contact
|
(1) 1a-1b (1) 1M (make)-1B (break)
|
|
|
140U-J-EA1R1
|
| Right side ONLY
|
|
Shunt Trip (SNT) Provides remote tripping of the circuit breaker Undervoltage trip not available when shunt trip is used
|
24…60 V, 50/60/DC
|
|
|
140U-H-SNJ
|
| 110…240V, 50/60/DC
|
140U-H-SND
|
| 380…600V, 50/60 Hz
|
Left side ONLY
|
140U-H-SNB
|
Undervoltage Release (UVT) Automatically trips breaker when voltage falls between preset value, 35…70% Shunt trip is not available when undervoltage release is used
|
24V, 50/60 Hz
|
|
|
140U-H-UJ
|
| 110…127V, 50/60 Hz
|
140U-H-UD
|
| 208…240V, 50/60 Hz
|
140U-H-UA
|
| 380…500V, 50/60 Hz
|
140U-H-UB
|
| 525…600V, 50/60 Hz
|
Left side ONLY
|
140U-H-UC
|
|
|
|
|
Description
|
Cat. No.
|
|
Terminal Shields IP20 Ingress Protection Rating
|
140U-L-TS
|
|
Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 1/3/12/4/4X Flange-Mount Operating Handle Non-Metallic
|
4 ft (1.3 m) Cable
|
140U-L-FCX04
|
| 6 ft (1.9 m) Cable
|
140U-L-FCX06
|
| 10 ft (3.0 m) Cable
|
140U-L-FCX10
|
|
Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 4/4X Flange-Mount Operating Handle Stainless Steel
|
4 ft (1.2 m) Cable
|
140U-L-FCS04
|
| 6 ft (1.9 m) Cable
|
140U-L-FCS06
|
| 10 ft (3.0 m) Cable
|
140U-L-FCS10
|
Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted Painted metal — Type 1/12 Flange mount operating handle
|
4 ft (1.2 m) Cable
|
140U-L-FMX04
|
| 6 ft (1.9 m) Cable
|
140U-L-FMX06
|
| 10 ft (3.0 m) Cable
|
140U-L-FMX10
|
|
Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 12 in. (30.48 cm) operating rod
|
Black Handle
|
140U-L-RVM12B
|
| Red/Yellow Handle
|
140U-L-RVM12R
|
Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 21 in. (53.34 cm) operating rod
|
Black Handle
|
140U-L-RVM21B
|
| Red/Yellow Handle
|
140U-L-RVM21R
|
|
Rotary, Variable-Depth Operating Mechanism with Internal NFPA79 Operating Handle External UL Type 3/12/4/4X, IP 66 Rotary Handle 12 in. (30.48 cm) operating rod
|
Black Handle
|
140U-L-NVM12B
|
|
|
Red/Yellow Handle
|
140U-L-NVM12R
|
|
|
Rotary, Variable-Depth Operating Mechanism with Internal NFPA79 Operating Handle External UL Type 3/12/4/4X, IP 66 Rotary Handle 21 in. (53.34 cm) operating rod
|
Black Handle
|
140U-L-NVM21B
|
|
|
Red/Yellow Handle
|
140U-L-NVM21R
|
|
Rotary, Direct Couple Operating Mechanism Breaker Mounted
|
Black Handle
|
140U-L-RMX
|
|
End Cap Kit Provides 3-phase connections for terminal or bolt-on connections Metric hardware provided
|
Qty: 1
|
140U-L-ECM
|
|
Padlock Kit Padlocking Hasp Lock-OFF only
|
Qty: 1
|
140U-L-PL
|
|
Phase Barriers Provides additional phase clearance when special connections that extend past the circuit breaker housing are required
|
Qty: 2
|
140U-K-PB
|
|
Ground Fault Leakage Module Current pickup settings are selectable from 0.03…30 A with time delays up to1.0 s. Time delays are also selectable from Instantaneous…1.0 s for 0.10 A settings and above. A current pickup setting of 0.03 A defaults to an Instantaneous time setting regardless of the time dials position. Two alarm contacts come as standard: a 50% pretrip and a 100% after trip contact, both based only on earth leakage current levels.
|
400 A
|
For use with L-Frame 3-pole MCCBs up to 400 A
|
140U-L-GFP4003
|
| 600 A
|
For use with L-Frame 3-pole MCCBs up to 600 A
|
140U-L-GFP6003
|
|
Motor Operator Remotely opens, closes, and resets the circuit breaker 110…240V AC
|
For use with 3- or 4-Pole MCCBs, 110…240V AC/DC
|
140U-L-EOPD
|
| For use with 3- or 4-Pole MCCBs, 24V DC
|
140U-L-EOPZ
|
|
Replacement Mounting Hardware (4) M5 - 0.8 x 100 mm §
|
For use with 3- or 4-Pole MCCBs
|
140U-L-MHM
|
|
|
| § Supplied with breaker.
|