Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140U M-Frame
Bulletin 140U M-Frame
| Product Selection — 800 A, M-Frame | Accessories — 800 A, M-Frame | Approximate Dimensions — 800 A, M-Frame |
|
- UL 489
- CSA 22.2, No. 5
- IEC 60947-2
- CE
- KEMA
- CCC
Note: Terminal box lugs must be ordered separately. See
Breaker Frames
| Rated Current In [A] | Breaking Capacity (50 Hz) Icu /Ics [kA] | Interrupting Rating (60 Hz) [kA] | Cat. No. | |||||||||
| 220…240V | 380…415V | 525V | 690V | 240V | 480V | 600V | ||||||
| 800 | 65 | 65 | 50 | 50 | 50 | 25 | 20 | 10 | 65 | 50 | 25 | 140U-M5X3 |
| 100 | 100 | 70 | 70 | 70 | 50 | 25 | 13 | 100 | 65 | 35 | 140U-M6X3 | |
Trip Units and Rating Plugs
| Thermal-Magnetic | |||
| Rated Current In [A] | Adjustment Range [A] | Cat. No. | |
| Thermal Trip Ir = In |
Magnetic Trip Im = 5…10 x In |
||
| 300 | 300 | 1500…3000 | 140U-MTD3-D30 |
| 350 | 350 | 1750…3500 | 140U-MTD3-D35 |
| 400 | 400 | 2000…4000 | 140U-MTD3-D40 |
| 450 | 450 | 2250…4500 | 140U-MTD3-D45 |
| 500 | 500 | 2500…5000 | 140U-MTD3-D50 |
| 600 | 600 | 3000…6000 | 140U-MTD3-D60 |
| 700 | 700 | 3500…7000 | 140U-MTD3-D70 |
| 800 | 800 | 4000…8000 | 140U-MTD3-D80 |
| Electronic | ||||
| Rated Current In [A] | Adjustment Range [A] | Protection Type | Cat. No. | |
| Thermal Trip Ir = 0.5…1.0 x In |
Magnetic Trip Im = 2…8 x In |
|||
| 800A | 400…800⋆ | 800…6400 | 400…800 A LS Electronic Trip Unit | 140U-MTL3-D80 |
| 400…800 A LSI Electronic Trip Unit | 140U-MTH3-D80 | |||
| 400…800 A LSG Electronic Trip Unit | 140U-MTG3-D80 | |||
| 400…800 A LSIG Electronic Trip Unit | 140U-MTI3-D80 | |||
| Select proper rating plug to cover thermal trip requirement. | ||||
| Rating Plugs | |||
| Thermal Trip In [A] |
Cat. No. | Thermal Trip In [A] |
Cat. No. |
| 400 | 140U-MRP3-D40 | 700 | 140U-MRP3-D70 |
| 500 | 140U-MRP3-D50 | 800 | 140U-MRP3-D80 |
| 600 | 140U-MRP3-D60 | — | — |
Assembled Circuit Breakers, Thermal-Magnetic Trip Units
| Rated Current In [A] | Thermal Trip Ir = In |
Breaking Capacity/Interrupting Rating [kA] | Cat. No. | Breaking Capacity/Interrupting Rating [kA] | Cat. No. | ||
| 400V | 480V | 400V | 480V | ||||
| 300 | 300 | 50 | 50 | 140U-M5D3-D30 | 70 | 65 | 140U-M6D3-D30 |
| 350 | 350 | 50 | 50 | 140U-M5D3-D35 | 70 | 65 | 140U-M6D3-D35 |
| 400 | 400 | 50 | 50 | 140U-M5D3-D40 | 70 | 65 | 140U-M6D3-D40 |
| 450 | 450 | 50 | 50 | 140U-M5D3-D45 | 70 | 65 | 140U-M6D3-D45 |
| 500 | 500 | 50 | 50 | 140U-M5D3-D50 | 70 | 65 | 140U-M6D3-D50 |
| 600 | 600 | 50 | 50 | 140U-M5D3-D60 | 70 | 65 | 140U-M6D3-D60 |
| 700 | 700 | 50 | 50 | 140U-M5D3-D70 | 70 | 65 | 140U-M6D3-D70 |
| 800 | 800 | 50 | 50 | 140U-M5D3-D80 | 70 | 65 | 140U-M6D3-D80 |
| Interrupting ratings shown are for 400V and 480V, respectively. The complete range of ratings can be found in the frame rating table on Breaker Frames | |||||||
Assembled Circuit Breakers, Electronic Trip Units
| Rated Current In [A] | Thermal Trip Ir = 0.5…1.0 x In |
Protection Type | Breaking Capacity/ Interrupting Rating [kA] |
Cat. No. | Breaking Capacity/ Interrupting Rating [kA] |
Cat. No. | ||
| 400V | 480V | 400V | 480V | |||||
| 800 | 400…800⋆ | LS | 50 | 50 | 140U-M5L3-D80 | 70 | 65 | 140U-M6L3-D80 |
| LSI | 50 | 50 | 140U-M5H3-D80 | 70 | 65 | 140U-M6H3-D80 | ||
| LSG | 50 | 50 | 140U-M5G3-D80 | 70 | 65 | 140U-M6G3-D80 | ||
| ⋆ Select proper rating plug to cover thermal trip requirement. | ||||||||
| Interrupting ratings shown are for 400V and 480V, respectively. The complete range of ratings can be found in the frame rating table on Breaker Frames. | ||||||||
Molded Case Switch — UL 489
| Rated Current In [A] | Magnetic Trip [A] Im = 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] | Interrupting Rating (60 Hz) [kA] | Cat. No. | |||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600V | |||||||
| 800 | 8000 | 100 | 100 | 70 | 70 | 70 | 50 | 25 | 13 | 100 | 65 | 35 | 140U-M6S3-D80 |