Molded Case Circuit Breakers

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140U M-Frame

Bulletin 140U M-Frame

Product Selection — 800 A, M-Frame Accessories — 800 A, M-Frame Approximate Dimensions — 800 A, M-Frame
Product Selection — 800 A, M-Frame

Click to enlarge - 140U-39-6



Note: Terminal box lugs must be ordered separately. See

Breaker Frames

Rated Current In [A] Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] Cat. No.
220…240V 380…415V 525V 690V 240V 480V 600V
800 65 65 50 50 50 25 20 10 65 50 25 140U-M5X3
100 100 70 70 70 50 25 13 100 65 35 140U-M6X3
  

Trip Units and Rating Plugs

Thermal-Magnetic
Rated Current In [A] Adjustment Range [A] Cat. No.
Thermal Trip
Ir = In
Magnetic Trip
Im = 5…10 x In
300 300 1500…3000 140U-MTD3-D30
350 350 1750…3500 140U-MTD3-D35
400 400 2000…4000 140U-MTD3-D40
450 450 2250…4500 140U-MTD3-D45
500 500 2500…5000 140U-MTD3-D50
600 600 3000…6000 140U-MTD3-D60
700 700 3500…7000 140U-MTD3-D70
800 800 4000…8000 140U-MTD3-D80

Electronic
Rated Current In [A] Adjustment Range [A] Protection Type Cat. No.
Thermal Trip
Ir = 0.5…1.0 x In
Magnetic Trip
Im = 2…8 x In
800A 400…800¬  800…6400 400…800 A LS Electronic Trip Unit 140U-MTL3-D80
400…800 A LSI Electronic Trip Unit 140U-MTH3-D80
400…800 A LSG Electronic Trip Unit 140U-MTG3-D80
400…800 A LSIG Electronic Trip Unit 140U-MTI3-D80
  
Select proper rating plug to cover thermal trip requirement.

Rating Plugs
Thermal Trip
In [A]
Cat. No. Thermal Trip
In [A]
Cat. No.
400 140U-MRP3-D40 700 140U-MRP3-D70
500 140U-MRP3-D50 800 140U-MRP3-D80
600 140U-MRP3-D60
  

Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Current In [A] Thermal Trip
Ir = In
Breaking Capacity/Interrupting Rating [kA]T  Cat. No. Breaking Capacity/Interrupting Rating [kA]T  Cat. No.
400V 480V 400V 480V
300 300 50 50 140U-M5D3-D30 70 65 140U-M6D3-D30
350 350 50 50 140U-M5D3-D35 70 65 140U-M6D3-D35
400 400 50 50 140U-M5D3-D40 70 65 140U-M6D3-D40
450 450 50 50 140U-M5D3-D45 70 65 140U-M6D3-D45
500 500 50 50 140U-M5D3-D50 70 65 140U-M6D3-D50
600 600 50 50 140U-M5D3-D60 70 65 140U-M6D3-D60
700 700 50 50 140U-M5D3-D70 70 65 140U-M6D3-D70
800 800 50 50 140U-M5D3-D80 70 65 140U-M6D3-D80
  
T Full ratings are found in the breaker frames table on Breaker Frames

Assembled Circuit Breakers, Electronic Trip Units

Rated Current In [A] Thermal Trip
Ir = 0.5…1.0 x In
Protection Type Breaking Capacity/
Interrupting Rating [kA]T 
Cat. No. Breaking Capacity/
Interrupting Rating [kA]T 
Cat. No.
400V 480V 400V 480V
800 200…800¬  LS 50 50 140U-M5L3-D80 70 65 140U-M6L3-D80
LSI 50 50 140U-M5H3-D80 70 65 140U-M6H3-D80
LSG 50 50 140U-M5G3-D80 70 65 140U-M6G3-D80
  
¬ Select proper rating plug to cover thermal trip requirement.
T Full ratings are found in the breaker frames table on Breaker Frames

Molded Case Switch — UL 489

Rated Current In [A] Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V
800 8000 100 100 70 70 70 50 25 13 100 65 35 140U-M6S3-D80