Bulletin 140U N-Frame
Product Selection — 1200 A, N-Frame
|
- UL 489
- CSA 22.2, No. 5
- IEC 60947-2
- CE
- KEMA
- CCC
Note: Terminal box lugs must be ordered separately. See Terminal Lugs
Assembled Circuit Breakers, Electronic Trip Units
| Rated Current | Adjustment Range Ir [A] | Protect. Type |
Breaking Capacity (50 Hz) | Interrupting Rating (60 Hz) [kA] | Cat. No. | |||||||||||
| Oper. In [A] |
Instant. Maint. Mode 2.5…4.0 x In [A] |
Thermal Trip Ir = 0.5…1.0 x In |
Magnetic Trip Im = 2…8 x In |
Icu /Ics [kA] | ||||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600V | ||||||||||
| 1200 | — | 600…1200⋆ | 2400…9600 | LS | 85 | 85 | 50 | 50 | 40 | 20 | 20 | 10 | 65 | 50 | 25 | 140U-N5L3-E12 |
| 1200 | — | 600…1200⋆ | 2400…9600 | LS | 100 | 100 | 70 | 50 | 50 | 25 | 25 | 13 | 100 | 65 | 35 | 140U-N6L3-E12 |
| — | LSI | 100 | 100 | 70 | 50 | 50 | 25 | 25 | 13 | 100 | 65 | 35 | 140U-N6H3-E12 | |||
| 3000…4800 | 2400…10800♣ | LSII§ | 100 | 100 | 70 | 50 | 50 | 25 | 25 | 13 | 100 | 65 | 35 | 140U-N6J3-E12 | ||
| — | 2400…9600 | LSG | 100 | 100 | 70 | 50 | 50 | 25 | 25 | 13 | 100 | 65 | 35 | 140U-N6G3-E12 | ||
| — | LSIG | 100 | 100 | 70 | 50 | 50 | 25 | 25 | 13 | 100 | 65 | 35 | 140U-N6I3-E12 | |||
| 3000…4800 | 2400…10800♣ | LSIIG§ | 100 | 100 | 70 | 50 | 50 | 25 | 25 | 13 | 100 | 65 | 35 | 140U-N6K3-E12 | ||
| 1200 | — | 600…1200⋆ | 2400…9600 | LS | 200 | 100 | 100 | 50 | 65 | 33 | 35 | 18 | 200 | 100 | 50 | 140U-N0L3-E12 |
| — | LSI | 200 | 100 | 100 | 50 | 65 | 33 | 35 | 18 | 200 | 100 | 50 | 140U-N0H3-E12 | |||
| 3000…4800 | 2400…10800♣ | LSII§ | 200 | 100 | 100 | 50 | 65 | 33 | 35 | 18 | 200 | 100 | 50 | 140U-N0J3-E12 | ||
| — | 2400…9600 | LSG | 200 | 100 | 100 | 50 | 65 | 33 | 35 | 18 | 200 | 100 | 50 | 140U-N0G3-E12 | ||
| — | LSIG | 200 | 100 | 100 | 50 | 65 | 33 | 35 | 18 | 200 | 100 | 50 | 140U-N0I3-E12 | |||
| 3000…4800 | 2400…10800♣ | LSIIG§ | 200 | 100 | 100 | 50 | 65 | 33 | 35 | 18 | 200 | 100 | 50 | 140U-N0K3-E12 | ||
| ⋆ Select proper rating plug to cover thermal trip equipment. | ||||||||||||||||
| § Rating plug not required with IMM trip module. | ||||||||||||||||
| ♣ Magnetic trip adjustment range for MCCBs with IMM trip modules is 2…9 x In. | ||||||||||||||||
Rating Plugs
| Rated Current In [A] | Cat. No. | Rated Operational Current In [A] |
Cat. No. |
| 600 | 140U-NRP3-D60 | 900 | 140U-NRP3-D90 |
| 700 | 140U-NRP3-D70 | 1000 | 140U-NRP3-E10 |
| 800 | 140U-NRP3-D80 | 1200 | 140U-NRP3-E12 |
Molded Case Switch — UL 489
| Rated Current In [A] | Magnetic Trip 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] | Interrupting Rating (60 Hz) [kA] | Cat. No. | |||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600V | |||||||
| 1200 | 12000 | 100 | 100 | 70 | 50 | 50 | 25 | 25 | 13 | 100 | 65 | 35 | 140U-N6S3-E12 |
Accessories
Pictures shown are representative. Actual product may differ from product shown.
Internal Control Modules — Field Installed
Note: For Factory-Installed internal control modules, please see Internal Control Modules — Factory Installed
For use with H-, J-, K-, L-, M-, and N-Frame Molded Case Circuit Breakers.
Pictures shown are representative. Actual product may differ from product shown.
External Accessories
Terminal Lugs
Approximate Dimensions
Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
|