Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140UE H-Frame
Bulletin 140UE H-Frame
Product Selection — 160 A, H-Frame
|
- IEC 60947-2
- CE
- KEMA-KEUR
Note: Terminal box lugs and mounting hardware provided as standard
18 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic
| Rated Current In [A] | Thermal Trip [A] Ir =In |
Magnetic Trip [A] Im = 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
NEMA Interrupt Rating (60 Hz) [kA] |
Cat. No. | ||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600/347V | 3-Pole | 4-Pole | |||||||
| 16 | 16 | 500 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C16 | — |
| 20 | 20 | 500 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C20 | — |
| 25 | 25 | 500 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C25 | — |
| 32 | 32 | 500 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C32 | — |
| 40 | 40 | 500 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C40 | — |
| 50 | 50 | 500 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C50 | — |
| 63 | 63 | 630 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C63 | — |
| 80 | 80 | 860 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-C80 | — |
| 100 | 100 | 1000 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-D10 | — |
| 125 | 125 | 1250 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-D12 | — |
| 160 | 160 | 1600 | 25 | 13 | 18 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1C3-D16 | — |
18 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic
| Rated Current In [A] | Thermal Trip [A] Ir = 0.8…1.0 x In |
Magnetic Trip [A] Im = 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
NEMA Interrupt Rating (60 Hz) [kA] |
Cat. No. | ||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600/347V | 3-Pole | 4-Pole | |||||||
| 20 | 16…20 | 500 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-C20 | 140UE-H1E4-C20 |
| 25 | 20…25 | 500 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-C25 | 140UE-H1E4-C25 |
| 32 | 25…32 | 500 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-C32 | 140UE-H1E4-C32 |
| 40 | 32…40 | 500 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-C40 | 140UE-H1E4-C40 |
| 50 | 40…50 | 500 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-C50 | 140UE-H1E4-C50 |
| 63 | 50…63 | 630 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-C63 | 140UE-H1E4-C63 |
| 80 | — | 800 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-C80 | 140UE-H1E4-C80 |
| 100 | — | 1000 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-D10 | 140UE-H1E4-D10 |
| 125 | — | 1250 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-D12 | 140UE-H1E4-D12 |
| 160 | — | 1600 | 25 | 13 | 16 | 9 | — | — | — | — | 25 | 14 | 10 | 140UE-H1E3-D16 | 140UE-H1E4-D16 |
25 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic
| Rated Current In [A] | Thermal Trip [A] Ir = 0.8…1.0 x In |
Magnetic Trip [A] Im = 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
NEMA Interrupt Rating (60 Hz) [kA] |
Cat. No. | ||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600/347V | 3-Pole | 4-Pole | |||||||
| 20 | 16…20 | 500 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-C20 | 140UE-H2E4-C20 |
| 25 | 20…25 | 500 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-C25 | 140UE-H2E4-C25 |
| 32 | 25…32 | 500 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-C32 | 140UE-H2E4-C32 |
| 40 | 32…40 | 500 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-C40 | 140UE-H2E4-C40 |
| 50 | 40…50 | 500 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-C50 | 140UE-H2E4-C50 |
| 63 | 50…63 | 630 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-C63 | 140UE-H2E4-C63 |
| 80 | 63…80 | 800 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-C80 | 140UE-H2E4-C80 |
| 100 | 80…100 | 1000 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-D10 | 140UE-H2E4-D10 |
| 125 | 100…125 | 1250 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-D12 | 140UE-H2E4-D12 |
| 160 | 125…160 | 1600 | 35 | 18 | 25 | 13 | — | — | — | — | 35 | 22 | 10 | 140UE-H2E3-D16 | 140UE-H2E4-D16 |
40 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic
| Rated Current In [A] | Thermal Trip [A] Ir = 0.8…1.0 x In |
Magnetic Trip [A] Im = 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
NEMA Interrupt Rating (60 Hz) [kA] |
Cat. No. | ||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600/347V | 3-Pole | 4-Pole | |||||||
| 20 | 16…20 | 500 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-C20 | 140UE-H4E4-C20 |
| 25 | 20…25 | 500 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-C25 | 140UE-H4E4-C25 |
| 32 | 25…32 | 500 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-C32 | 140UE-H4E4-C32 |
| 40 | 32…40 | 500 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-C40 | 140UE-H4E4-C40 |
| 50 | 40…50 | 500 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-C50 | 140UE-H4E4-C50 |
| 63 | 50…63 | 630 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-C63 | 140UE-H4E4-C63 |
| 80 | 63…80 | 800 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-C80 | 140UE-H4E4-C80 |
| 100 | 80…100 | 1000 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-D10 | 140UE-H4E4-D10 |
| 125 | 100…125 | 1250 | 85 | 43 | 40 | 30 | 25 | 18 | 4 | 3 | 85 | 35 | 22 | 140UE-H4E3-D12 | 140UE-H4E4-D12 |
70 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic
| Rated Current In [A] | Thermal Trip [A] Ir = 0.8…1.0 x In |
Magnetic Trip [A] Im = 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
NEMA Interrupt Rating (60 Hz) [kA] |
Cat. No. | ||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600/347V | 3-Pole | 4-Pole | |||||||
| 20 | 16…20 | 500 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-C20 | 140UE-H7E4-C20 |
| 25 | 20…25 | 500 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-C25 | 140UE-H7E4-C25 |
| 30 | 25…32 | 500 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-C32 | 140UE-H7E4-C32 |
| 40 | 32…40 | 500 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-C40 | 140UE-H7E4-C40 |
| 50 | 40…50 | 500 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-C50 | 140UE-H7E4-C50 |
| 63 | 50…63 | 630 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-C63 | 140UE-H7E4-C63 |
| 80 | 63…80 | 800 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-C80 | 140UE-H7E4-C80 |
| 100 | 80…100 | 1000 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-D10 | 140UE-H7E4-D10 |
| 125 | 100…125 | 1250 | 100 | 50 | 70 | 35 | 35 | 18 | 6 | 3 | 100 | 65 | 25 | 140UE-H7E3-D12 | 140UE-H7E4-D12 |
Isolation Disconnector — IEC 60947-3
| Rated Current In [A] | Thermal Trip [A] Ir = In (Fixed) |
Magnetic Trip [A] Im = 10 x In |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
NEMA Interrupt Rating (60 Hz) [kA] |
Cat. No. | ||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600/347V | 3-Pole | 4-Pole | |||||||
| 160 | — | 1600 | 35 | 18 | 25 | 25 | — | — | 3 | 3 | 25 | 25 | — | 140UE-H2S3-D16 | 140UE-H2S4-D16 |