Bulletin 140UE H-Frame

Product Selection — 160 A, H-Frame

Click to enlarge - 140U-39-2



Note: Terminal box lugs and mounting hardware provided as standard

18 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic

Rated Current In [A] Thermal Trip [A]
Ir =In
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600/347V 3-Pole 4-Pole
16 16 500 25 13 18 9 25 14 10 140UE-H1C3-C16
20 20 500 25 13 18 9 25 14 10 140UE-H1C3-C20
25 25 500 25 13 18 9 25 14 10 140UE-H1C3-C25
32 32 500 25 13 18 9 25 14 10 140UE-H1C3-C32
40 40 500 25 13 18 9 25 14 10 140UE-H1C3-C40
50 50 500 25 13 18 9 25 14 10 140UE-H1C3-C50
63 63 630 25 13 18 9 25 14 10 140UE-H1C3-C63
80 80 860 25 13 18 9 25 14 10 140UE-H1C3-C80
100 100 1000 25 13 18 9 25 14 10 140UE-H1C3-D10
125 125 1250 25 13 18 9 25 14 10 140UE-H1C3-D12
160 160 1600 25 13 18 9 25 14 10 140UE-H1C3-D16
  

18 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic

Rated Current In [A] Thermal Trip [A]
Ir = 0.8…1.0 x In
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600/347V 3-Pole 4-Pole
20 16…20 500 25 13 16 9 25 14 10 140UE-H1E3-C20 140UE-H1E4-C20
25 20…25 500 25 13 16 9 25 14 10 140UE-H1E3-C25 140UE-H1E4-C25
32 25…32 500 25 13 16 9 25 14 10 140UE-H1E3-C32 140UE-H1E4-C32
40 32…40 500 25 13 16 9 25 14 10 140UE-H1E3-C40 140UE-H1E4-C40
50 40…50 500 25 13 16 9 25 14 10 140UE-H1E3-C50 140UE-H1E4-C50
63 50…63 630 25 13 16 9 25 14 10 140UE-H1E3-C63 140UE-H1E4-C63
80 800 25 13 16 9 25 14 10 140UE-H1E3-C80 140UE-H1E4-C80
100 1000 25 13 16 9 25 14 10 140UE-H1E3-D10 140UE-H1E4-D10
125 1250 25 13 16 9 25 14 10 140UE-H1E3-D12 140UE-H1E4-D12
160 1600 25 13 16 9 25 14 10 140UE-H1E3-D16 140UE-H1E4-D16
  

25 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic

Rated Current In [A] Thermal Trip [A]
Ir = 0.8…1.0 x In
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600/347V 3-Pole 4-Pole
20 16…20 500 35 18 25 13 35 22 10 140UE-H2E3-C20 140UE-H2E4-C20
25 20…25 500 35 18 25 13 35 22 10 140UE-H2E3-C25 140UE-H2E4-C25
32 25…32 500 35 18 25 13 35 22 10 140UE-H2E3-C32 140UE-H2E4-C32
40 32…40 500 35 18 25 13 35 22 10 140UE-H2E3-C40 140UE-H2E4-C40
50 40…50 500 35 18 25 13 35 22 10 140UE-H2E3-C50 140UE-H2E4-C50
63 50…63 630 35 18 25 13 35 22 10 140UE-H2E3-C63 140UE-H2E4-C63
80 63…80 800 35 18 25 13 35 22 10 140UE-H2E3-C80 140UE-H2E4-C80
100 80…100 1000 35 18 25 13 35 22 10 140UE-H2E3-D10 140UE-H2E4-D10
125 100…125 1250 35 18 25 13 35 22 10 140UE-H2E3-D12 140UE-H2E4-D12
160 125…160 1600 35 18 25 13 35 22 10 140UE-H2E3-D16 140UE-H2E4-D16
  

40 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic

Rated Current In [A] Thermal Trip [A]
Ir = 0.8…1.0 x In
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600/347V 3-Pole 4-Pole
20 16…20 500 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-C20 140UE-H4E4-C20
25 20…25 500 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-C25 140UE-H4E4-C25
32 25…32 500 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-C32 140UE-H4E4-C32
40 32…40 500 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-C40 140UE-H4E4-C40
50 40…50 500 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-C50 140UE-H4E4-C50
63 50…63 630 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-C63 140UE-H4E4-C63
80 63…80 800 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-C80 140UE-H4E4-C80
100 80…100 1000 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-D10 140UE-H4E4-D10
125 100…125 1250 85 43 40 30 25 18 4 3 85 35 22 140UE-H4E3-D12 140UE-H4E4-D12
  

70 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic

Rated Current In [A] Thermal Trip [A]
Ir = 0.8…1.0 x In
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600/347V 3-Pole 4-Pole
20 16…20 500 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-C20 140UE-H7E4-C20
25 20…25 500 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-C25 140UE-H7E4-C25
30 25…32 500 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-C32 140UE-H7E4-C32
40 32…40 500 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-C40 140UE-H7E4-C40
50 40…50 500 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-C50 140UE-H7E4-C50
63 50…63 630 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-C63 140UE-H7E4-C63
80 63…80 800 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-C80 140UE-H7E4-C80
100 80…100 1000 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-D10 140UE-H7E4-D10
125 100…125 1250 100 50 70 35 35 18 6 3 100 65 25 140UE-H7E3-D12 140UE-H7E4-D12
  

Isolation Disconnector — IEC 60947-3

Rated Current In [A] Thermal Trip
[A]
Ir = In (Fixed)
Magnetic
Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600/347V 3-Pole 4-Pole
160 1600 35 18 25 25 3 3 25 25 140UE-H2S3-D16 140UE-H2S4-D16
  

Accessories

Internal Control Modules — Field Installed

  Description Mounting Location Diagram Cat. No.
Click to enlarge - 140U-43-1 Auxiliary Contact (AX)
Electrically indicates "ON/OFF" status of breakers
(1) 1a-1b Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-3 140U-H-EA1
(2) 1a-1b Right Side Only 140U-H-EA2
Alarm Contact (AL)
Electrically indicates when the breaker is in the "TRIPPED" state
(1) 1M (make)-1B (break) Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-5 140U-H-ER1
Right Side Only
Click to enlarge - 140U-43-6 Auxiliary/Alarm Contact (AX/AL)
Combination

Combination of auxiliary contact and alarm contact
(1) 1a-1b
(1) 1M (make)-1B (break)
Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-8 140U-H-EA1R1
Right Side Only
Click to enlarge - 140U-43-9 Shunt Trip (SNT)
Provides remote tripping of the circuit breaker
Undervoltage trip not available when shunt trip is used
24…60 V, 50/60/DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-11 140U-H-SNJ
110…240V, 50/60/DC 140U-H-SND
380…600V, 50/60 Hz Left Side Only 140U-H-SNB
Undervoltage Release (UVT)
Automatically trips breaker when voltage falls between preset value, 35…70%
Shunt trip is not available when undervoltage release is used
24V, 50/60Hz AC; 24V DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-13 140U-H-UJ
110…127V, 50/60 Hz 140U-H-UD
208…240V, 50/60 Hz 140U-H-UA
380…500V, 50/60 Hz 140U-H-UB
525…600V, 50/60 Hz Left Side Only 140U-H-UC
  

Internal Control Modules — Factory Installed

Left side only

Mounting Location

Right side only

Click to enlarge - 140U-43-14
(1) Shunt Trip (SNT)or(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or(2) Auxiliary contacts (AX)or(1) Alarm contact (AL)or(1) Alarm contact (AL) + Auxiliary contact (AX)


Auxiliary and
Alarm Contacts
Suffix
(1) AX - A
(2) AX - B
(1) AL - D
(1) AX + (1) AL - F
  

Shunt Trip
Combinations
Suffix
(1) SNT only - PÄ
(1) AX + (1) SNT - QÄ
(2) AX + (1) SNT - RÄ
(1) AX + (1) AL + (1) SNT - TÄ
(1) AL + (1) SNT - VÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24…60 110…240 380…600
AC,
50/60 Hz
J D B
DC J D
  

Undervoltage Release Combinations Suffix
(1) UVT only - GÄ
(1) AX + (1) UVT - HÄ
(2) AX + (1) UVT - JÄ
(1) AX + (1) AL + (1) UVT - LÄ
(1) AL + (1) UVT - NÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24 110…127 208…240 380…500 525…600
AC,
50/60 Hz
J D A B C
DC J
  

¬  For additional voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.


External Accessories

  Description For Use With Cat. No.
Click to enlarge - 140U-44-1 Terminal End Cover
6.4 mm (0.25 in.) diameter cable entry
Qty: 1 3-Pole MCCBs 140U-H-TC2
Terminal End Cover
10.4 mm (0.41 in.) diameter cable entry
3-Pole MCCBs 140U-H-TC4
Click to enlarge - 140M-20-1 Terminal Shields
IP20 Ingress Protection Rating
Qty: 1 3-Pole MCCBs 140U-H-TS
Qty: 1 4-Pole MCCBs 140U-H-TS4
Click to enlarge - lockout sml_bw Rotary, Variable-Depth Operating Mechanism
Rotary handle - IP66, UL Type 3/12/4/4X
21 in. (53.34 cm) operating rod
Black Handle
12 in. (30.5 cm)Shaft
3- or 4-Pole MCCBs 140U-H-RVM12B
Red/Yellow Handle
12 in. (30.5 cm)Shaft
140U-H-RVM12R
Black Handle
21 in. (53.4 cm)Shaft
140U-H-RVM21B
Red/Yellow Handle
21 in. (53.4 cm)Shaft
140U-H-RVM21R
Click to enlarge - ab_cable_bw Flex-Cable Operating Mechanism
Includes handle, cable, operating, and bail mechanism
Pre-assembled and adjusted
Non-Metallic - UL IP66, Type 1/3/12/4/4X
Flange Mount Operating Handle
1.5 ft (0.46 m) Cable 3-Pole MCCBs 140U-H-FCX01
3 ft (0.9 m) Cable 140U-H-FCX03
4 ft (1.3 m) Cable 140U-H-FCX04
6 ft (1.8 m) Cable 140U-H-FCX06
10 ft (3.0 m) Cable 140U-H-FCX10
Click to enlarge - 140U-44-6 Rotary, Direct Couple Operating
Mechanism

Rotary handle - IP42 UL Type 1
Breaker mounted
Black Handle 3- or 4-Pole MCCBs 140U-H-RCB
Red/Yellow Handle 140U-H-RCR
Click to enlarge - 140M-20-4 End Cap Kit
Provides three-phase connections for terminal or bolt-on connections
Metric hardware provided
Qty: 1 3-Pole MCCBs 140U-H-ECM
Qty: 1 4-Pole MCCBs 140U-H-ECM4
Click to enlarge - 140U_H_MTL3AN_right_bw Multi-Tap Terminal Lugs (3) #14…2 AWG
or (3) 2.5…35 mm2
Qty: 3 3-Pole MCCBs 140U-H-MTL3AN
(6) #14…6 AWG
or (6) 2.5…10 mm2
Qty: 3 3-Pole MCCBs 140U-H-MTL6AN
(3) #14…2 AWG
or (3) 2.5…35 mm2
Qty: 3 with terminal shield 3-Pole MCCBs 140U-H-MTL3A
(6) #14…6 AWG
or (6) 2.5…10 mm2
Qty: 3 with terminal shield 3-Pole MCCBs 140U-H-MTL6A
Cat. No. 140U-H-MTL3AN (3) #14…2 AWG
or (3) 2.5…35 mm2
Qty: 4 4-Pole MCCBs 140U-H-MTL3A4
  (6) #14…6 AWG
or (6) 2.5…10 mm2
Qty: 4 4-Pole MCCBs 140U-H-MTL6A4
  

External Accessories, Continued

  Description For Use With Cat. No.
Click to enlarge - 140M-20-5 Phase Barriers
Provides additional phase clearance when special connections that extend past the circuit breaker housing are required
Qty: 2 3-Pole MCCBs 140U-H-PB
Qty: 3 4-Pole MCCBs 140U-H-PB4
Click to enlarge - 140M-20-3 Padlock Kit
Padlocking hasp
Lock-OFF only
Qty: 1 3- or 4-Pole MCCBs 140U-H-PL
Click to enlarge - 140U-44-10 DIN Rail Adapter
Allows H-frame MCCB to mount to 35 mm DIN Rail
Qty: 1 3-Pole H-Frame MCCBs 140U-H-DRA
Click to enlarge - 140_BASE_R-bw Plug-in Base Adapters
Plug-in provides power terminations and adapter for applications where the ability to quickly remove or replace the circuit breakers is required
Qty: 1 3-Pole MCCBs 140U-H-PAD3
4-Pole MCCBs 140U-H-PAD4
Plug-in Base Auxiliary Contacts
Provides auxiliary contact functions to detect breaker installation status
Qty: 1 3- or 4-Pole MCCBs 140U-H-PDK
Click to enlarge - 140U-J-MHM_bw Replacement Mounting Hardware
(4) M4 - 0.7 x 75 mm
Qty: 1 3- or 4-Pole MCCBs 140U-H-MHM
Click to enlarge - motor_operator_sml_bw Motor Operator
Remotely opens, closes, and resets the circuit breaker
110…240V AC
Qty: 1 3- or 4-Pole MCCBs, 110…240V AC/DC 140U-H-EOPD
3- or 4-Pole MCCBs, 24V DC 140U-H-EOPZ
Click to enlarge - interlock 1 bw-21990 Slide Bar Interlock Qty: 1 140U-H-SBLK
  

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - h-frame_4p_3p_1