Bulletin 140UE J-Frame

Product Selection — 250 A, J-Frame

Click to enlarge - 140U-39-3



Note: Terminal box lugs and mounting hardware included.

Circuit breakers can be assembled from a circuit breaker frame and a trip unit, or purchased as assembled units.



Example:

Cat. No. 140UE-J2X3 (frame) + Cat. No. 140UE-JTF3-C80 (trip unit) = Cat. No. 140UE-J2F3-C80 (equivalent assembled circuit breaker)


Breaker Frames

Rated
Current
In [A]
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V 3-Pole 4-Pole
250 65 65 25 25 20 12 12 6 65 25 18 140UE-J2X3 140UE-J2X4
85 85 40 40 35 20 12 6 85 35 18 140UE-J4X3 140UE-J4X4
100 100 70 70 42 20 14 7 100 65 25 140UE-J7X3 140UE-J7X4
  

Trip Units, Thermal-Magnetic

Rated Current In [A] Adjustment Range [A] Protection Type Cat. No.
Thermal Trip Adjusment Range
Ir = 0.8…1.0 In
Magnetic Trip
Im = 5…10 x In
3-Pole 4-Pole ¬ 
80 64…80 400…800 AA 140UE-JTF3-C80 140UE-JTF4-C80
100 80…100 500…1000 AA 140UE-JTF3-D10 140UE-JTF4-D10
125 100…125 625…1250 AA 140UE-JTF3-D12 140UE-JTF4-D12
160 128…160 800…1600 AA 140UE-JTF3-D16 140UE-JTF4-D16
200 160…200 1000…2000 AA 140UE-JTF3-D20 140UE-JTF4-D20
250 200…250 1250…2500 AA 140UE-JTF3-D25 140UE-JTF4-D25
  
¬ 4th pole neutral — 0/100% protected

Trip Units, Electronic

Rated Current In [A] Adjustment Range [A] Protection Type¬  Ground Fault Functions Cat. No.
Thermal Trip
Ir = 0.4…1.0 x In
Magnetic Trip
Im = 2…10 x In
IG=0.2…1.0IN TG=ms 3-Pole 4-Pole
50 20…50 40…700 LS 140UE-JTL3-C50 140UE-JTL4-C50
50 20…50 40…700 LSI 140UE-JTH3-C50 140UE-JTH4-C50
50 20…50 40…700 LSG 10…50 Inst., 120, 300 140UE-JTG3-C50 140UE-JTG4-C50
50 20…50 40…700 LSIG 10…50 Inst., 120, 300 140UE-JTI3-C50 140UE-JTI4-C50
100 40…100 80…1400 LS 140UE-JTL3-D10 140UE-JTL4-D10
100 40…100 80…1400 LSI 140UE-JTH3-D10 140UE-JTH4-D10
100 40…100 80…1400 LSG 20…100 Inst., 120, 300 140UE-JTG3-D10 140UE-JTG4-D10
100 40…100 80…1400 LSIG 20…100 Inst., 120, 300 140UE-JTI3-D10 140UE-JTI4-D10
160 63…160 126…2240 LS 140UE-JTL3-D16 140UE-JTL4-D16
160 63…160 126…2240 LSI 140UE-JTH3-D16 140UE-JTH4-D16
160 63…160 126…2240 LSG 32…160 Inst., 120, 300 140UE-JTG3-D16 140UE-JTG4-D16
160 63…160 126…2240 LSIG 32…160 Inst., 120, 300 140UE-JTI3-D16 140UE-JTI4-D16
250 100…250 200…3500 LS 140UE-JTL3-D25 140UE-JTL4-D25
250 100…250 200…3500 LSI 140UE-JTH3-D25 140UE-JTH4-D25
250 100…250 200…3500 LSG 50…250 Inst., 120, 300 140UE-JTG3-D25 140UE-JTG4-D25
250 100…250 200…3500 LSIG 50…250 Inst., 120, 300 140UE-JTI3-D25 140UE-JTI4-D25
  
Adjustable long-time delay: 2…24s @ 6 times Ir
Adjustable short-time delay: Inst., 120 ms, 300 ms

Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Current In [A] Protection Type
In
Breaking Capacity 380…415V (50 Hz)
3 Poles 4 Poles
25 kA 40 kA 70 kA 25 kA 40 kA 70 kA
Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
80 AA 140UE-J2F3-C80 140UE-J4F3-C80 140UE-J7F3-C80 140UE-J2F4-C80 140UE-J4F4-C80 140UE-J7F4-C80
100 AA 140UE-J2F3-D10 140UE-J4F3-D10 140UE-J7F3-D10 140UE-J2F4-D10 140UE-J4F4-D10 140UE-J7F4-D10
125 AA 140UE-J2F3-D12 140UE-J4F3-D12 140UE-J7F3-D12 140UE-J2F4-D12 140UE-J4F4-D12 140UE-J7F4-D12
160 AA 140UE-J2F3-D16 140UE-J4F3-D16 140UE-J7F3-D16 140UE-J2F4-D16 140UE-J4F4-D16 140UE-J7F4-D16
200 AA 140UE-J2F3-D20 140UE-J4F3-D20 140UE-J7F3-D20 140UE-J2F4-D20 140UE-J4F4-D20 140UE-J7F4-D20
250 AA 140UE-J2F3-D25 140UE-J4F3-D25 140UE-J7F3-D25 140UE-J2F4-D25 140UE-J4F4-D25 140UE-J7F4-D25
  

Assembled Circuit Breakers, Electronic Trip Units

Rated Current In [A] Protection Type Breaking Capacity 380…415V (50 Hz)
3 Poles 4 Poles
25 kA 40 kA 70 kA 25 kA 40 kA 70 kA
Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
50 LS 140UE-J2L3-C50 140UE-J4L3-C50 140UE-J7L3-C50 140UE-J2L4-C50 140UE-J4L4-C50 140UE-J7L4-C50
50 LSI 140UE-J2H3-C50 140UE-J4H3-C50 140UE-J7H3-C50 140UE-J2H4-C50 140UE-J4H4-C50 140UE-J7H4-C50
50 LSG 140UE-J2G3-C50 140UE-J4G3-C50 140UE-J7G3-C50 140UE-J2G4-C50 140UE-J4G4-C50 140UE-J7G4-C50
50 LSIG 140UE-J2I3-C50 140UE-J4I3-C50 140UE-J7I3-C50 140UE-J2I4-C50 140UE-J4I4-C50 140UE-J7I4-C50
100 LS 140UE-J2L3-D10 140UE-J4L3-D10 140UE-J7L3-D10 140UE-J2L4-D10 140UE-J4L4-D10 140UE-J7L4-D10
100 LSI 140UE-J2H3-D10 140UE-J4H3-D10 140UE-J7H3-D10 140UE-J2H4-D10 140UE-J4H4-D10 140UE-J7H4-D10
100 LSIG 140UE-J2G3-D10 140UE-J4G3-D10 140UE-J7G3-D10 140UE-J2G4-D10 140UE-J4G4-D10 140UE-J7G4-D10
100 LSIG 140UE-J2I3-D10 140UE-J4I3-D10 140UE-J7I3-D10 140UE-J2I4-D10 140UE-J4I4-D10 140UE-J7I4-D10
160 LS 140UE-J2L3-D16 140UE-J4L3-D16 140UE-J7L3-D16 140UE-J2L4-D16 140UE-J4L4-D16 140UE-J7L4-D16
160 LSI 140UE-J2H3-D16 140UE-J4H3-D16 140UE-J7H3-D16 140UE-J2H4-D16 140UE-J4H4-D16 140UE-J7H4-D16
160 LSG 140UE-J2G3-D16 140UE-J4G3-D16 140UE-J7G3-D16 140UE-J2G4-D16 140UE-J4G4-D16 140UE-J7G4-D16
160 LSIG 140UE-J2I3-D16 140UE-J4I3-D16 140UE-J7I3-D16 140UE-J2I4-D16 140UE-J4I4-D16 140UE-J7I4-D16
250 LS 140UE-J2L3-D25 140UE-J4L3-D25 140UE-J7L3-D25 140UE-J2L4-D25 140UE-J4L4-D25 140UE-J7L4-D25
250 LSI 140UE-J2H3-D25 140UE-J4H3-D25 140UE-J7H3-D25 140UE-J2H4-D25 140UE-J4H4-D25 140UE-J7H4-D25
250 LSG 140UE-J2G3-D25 140UE-J4G3-D25 140UE-J7G3-D25 140UE-J2G4-D25 140UE-J4G4-D25 140UE-J7G4-D25
250 LSIG 140UE-J2I3-D25 140UE-J4I3-D25 140UE-J7I3-D25 140UE-J2I4-D25 140UE-J4I4-D25 140UE-J7I4-D25
  

Isolation Disconnector — IEC 60947-3

Rated Current
In [A]
Thermal Trip
Ir = In [A]
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
Interrupting Rating
(60 Hz) [kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V 3-Pole 4-Pole
250 2500 100 100 70 70 25 10 14 7 100 65 25 140UE-J7S3-D25 140UE-J7S4-D25
  

Accessories

Internal Control Modules — Field Installed

  Description Mounting Location Diagram Cat. No.
Click to enlarge - 140U-43-1 Auxiliary Contact (AX)
Electrically indicates "ON/OFF" status of breakers
(1) 1a-1b Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-3 140U-H-EA1
(2) 1a-1b Left AND Right Side 140U-H-EA2
Alarm Contact (AL)
Electronically indicates when the breaker is in the "TRIPPED" state
(1) 1M (make)-1B (break) Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-5 140U-J-ER1
Right Side Only
Click to enlarge - 140U-43-6 Auxiliary/Alarm Contact (AX/AL)
Combination

Combination of auxiliary contact and alarm contact
(1) 1a-1b
(1) 1M (make)-1B (break)
Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-8 140U-J-EA1R1
Left AND Right Side
Click to enlarge - 140U-43-9 Shunt Trip (SNT)
Provides remote tripping of the circuit breaker
Undervoltage trip not available when shunt trip is used
24…60 V, 50/60/DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-11 140U-H-SNJ
110…240V, 50/60/DC 140U-H-SND
380…600V, 50/60 Hz Left Side Only 140U-H-SNB
Undervoltage Release (UVT)
Automatically trips breaker when voltage falls between preset value, 35…70%
Shunt trip is not available when undervoltage release is used
24V, 50/60Hz AC; 24V DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-13 140U-H-UJ
110…127V, 50/60 Hz 140U-H-UD
208…240V, 50/60 Hz 140U-H-UA
380…500V, 50/60 Hz 140U-H-UB
525…600V, 50/60 Hz Left Side Only 140U-H-UC
  

Internal Control Modules — Factory Installed

Left side only

Mounting Location

Right side only

Click to enlarge - 140U-43-14
(1) Shunt Trip (SNT)or(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or(2) Auxiliary contacts (AX)or(1) Alarm contact (AL)or(1) Alarm contact (AL) + Auxiliary contact (AX)


Auxiliary and
Alarm Contacts
Suffix
(1) AX - A
(2) AX - B
(1) AL - D
(1) AX + (1) AL - F
  

Shunt Trip
Combinations
Suffix
(1) SNT only - PÄ
(1) AX + (1) SNT - QÄ
(2) AX + (1) SNT - RÄ
(1) AX + (1) AL + (1) SNT - TÄ
(1) AL + (1) SNT - VÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24…60 110…240 380…600
AC,
50/60 Hz
J D B
DC J D
  

Undervoltage Release Combinations Suffix
(1) UVT only - GÄ
(1) AX + (1) UVT - HÄ
(2) AX + (1) UVT - JÄ
(1) AX + (1) AL + (1) UVT - LÄ
(1) AL + (1) UVT - NÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24 110…127 208…240 380…500 525…600
AC,
50/60 Hz
J D A B C
DC J
  

¬  For additional voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.


External Accessories

  Description For Use With Cat. No.
Click to enlarge - 140U-J-TS_r Terminal Shields
IP20 Ingress Protection Rating
Qty: 1 3-Pole MCCBs 140U-J-TS
4-Pole MCCBs 140U-J-TS4
Click to enlarge - 140U-52-3 Flex-Cable Operating Mechanism
Non-Metallic IP 66/UL Type 1/3/12/4/4X
Flange-Mount Operating Handle
3 ft (0.9 m) Cable 3- or 4-Pole MCCBs 140U-J-FCX03
4 ft (1.3 m) Cable 140U-J-FCX04
6 ft (1.8 m) Cable 140U-J-FCX06
10 ft (3.0 m) Cable 140U-J-FCX10
Flex-Cable Operating Mechanism
Stainless Steel IP66/ UL Type 1/3/12/4/4X
Flange-Mount Operating Handle
3 ft (0.9 m) Cable 3- or 4-Pole MCCBs 140U-J-FCS03
4 ft (1.3 m) Cable 140U-J-FCS04
6 ft (1.8 m) Cable 140U-J-FCS06
10 ft (3.0 m) Cable 140U-J-FCS10
Click to enlarge - lockout sml_bw Rotary, Variable-Depth Operating Mechanism
IP66/ UL Type 1/3/12/4/4X rotary handle
12 in. (30.48 cm) operating rod
Black Handle 3- or 4-Pole MCCBs 140U-J-RVM12B
Red/Yellow Handle 140U-J-RVM12R
Rotary, Variable-Depth Operating Mechanism
IP66/ UL Type 1/3/12/4/4X rotary handle
21 in. (53.34 cm) operating rod
Black Handle 140U-J-RVM21B
Red/Yellow Handle 140U-J-RVM21R
Click to enlarge - 140U-44-6 Rotary, Direct Couple Operating Mechanism
Breaker mounted
Black Handle 3- or 4-Pole MCCBs 140U-J-RCB
Red/Yellow Handle 140U-J-RCR
Click to enlarge - 140M-20-5 Phase Barriers
Provides additional phase clearance when special connections that extend past the circuit breaker housing are required
Qty: 2 3-Pole MCCBs 140U-J-PB
4-Pole MCCBs 140U-J-PB4
Click to enlarge - 140M-20-3 Padlock Kit
Padlocking hasp
Lock-OFF only
Qty: 1 3- or 4-Pole MCCBs 140U-J-PL
Click to enlarge - 140U-48-8 Terminal Lugs Stainless Steel Box Lugs,
Cu wire Only
(1) 4…350 MCM
or (1) 25…185 mm2
Qty: 1 3- or 4-Pole MCCBs 140U-J-TLS1
Aluminum lugs, Al or Cu wire
(1) 4…350 MCM
or (1) 25…185 mm2
Qty: 1 3- or 4-Pole MCCBs 140U-J-TLA1
Click to enlarge - 140M-20-4 End Cap Kit
Provides 3-phase connections for
terminal or bolt-on connections
Metric hardware
Qty: 1 3-Pole MCCBs 140U-J-ECM
4-Pole MCCBs 140U-J-ECM4
  

External Accessories, Continued

  Description For Use With Cat. No.
Click to enlarge - 140U_H_MTL3AN_right_bw Multi-Tap Terminal Lug Kit — with IP20 terminal cover (3) #14…2 AWG
or (3) 2.5…25 mm2
Qty: 3 3-Pole MCCBs 140U-J-MTL3A
(6) #14…6 AWG
or (6) 2.5…10 mm2
140U-J-MTL6A
Click to enlarge - 140U_H_MTL6AN_right_bw Multi-Tap Terminal Lugs — with IP20 terminal cover (3) #14…2 AWG
or (3) 2.5…25 mm2
Qty: 4 4-Pole MCCBs 140U-J-MTL3A4
(6) #14…6 AWG
or (6) 2.5…10 mm2
140U-J-MTL6A4
Click to enlarge - 140_BASE_R-bw Plug-in Base Adapters
Plug-in provides power terminations and adapter
Qty: 1 3-Pole MCCBs 140U-J-PAD3
Qty: 1 4-Pole MCCBs 140U-J-PAD4
Plug-in Base Auxiliary Contacts
Provides auxiliary contact functions to detect breaker insulation status
Qty: 1 3- or 4-Pole MCCBs 140U-J-PDK
Click to enlarge - 140U-J-MHM_bw Replacement Mounting Hardware
(4) M4 - 0.7 x 90 mm
Qty: 1 3- or 4-Pole MCCBs 140U-J-MHM
Click to enlarge - interlock 1 bw-21990 Slide Bar Interlock Qty: 1 3- or 4-Pole MCCBs 140U-J-SBLK
Click to enlarge - ab_switch-21474_bw Motor Operator
Remotely opens, closes, and resets the circuit breaker
110…240V AC
Qty: 1 3- or 4-Pole MCCBs, 110…240V AC/DC 140U-J-EOPD
3- or 4-Pole MCCBs, 24V DC 140U-J-EOPZ
Click to enlarge - 140U-J-ELP_front_a_bw 160 A Earth Leakage Module
0.3…10 A, adjustable
Qty: 1 3-Pole MCCBs 140U-J-ELP1603
4-Pole MCCBs 140U-J-ELP1604
250 A Earth Leakage Module
0.3…10 A, adjustable
Qty: 1 3-Pole MCCBs 140U-J-ELP2503
4-Pole MCCBs 140U-J-ELP2504
  

Approximate Dimensions — 250 A, J-Frame

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - j-frame_4p_3p