Bulletin 140UE L-Frame

Product Selection — 630 A, L-Frame


Click to enlarge - 140UE-L6-09189_bw


Circuit breakers can be assembled from a circuit breaker frame and a trip unit, or purchased as assembled units.



Example:

Cat. No. 140UE-L3X3 (frame) + Cat. No. 140UE-LTF3-D25 (trip unit) = Cat. No. 140UE-L3F3-D25 (equivalent assembled circuit breaker)


Breaker Frames

Rated
Current
In [A]
Breaking Capacity (50 Hz)
Icu /Ics [kA]
NEMA Interrupt Rating (60 Hz)
[kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V 3-Pole 4-Pole
630 65 65 35 35 18 18 12 9 65 35 18 140UE-L3X3 140UE-L3X4
85 85 50 50 25 25 20 10 85 50 25 140UE-L5X3 140UE-L5X4
100 100 70 70 35 35 25 13 100 65 35 140UE-L7X3 140UE-L7X4
  

Trip Units, Thermal-Magnetic

Rated Current In [A] Adjustment Range [A] Protection Type Cat. No.
Thermal Trip
Ir = (0.8…1.0) In (Adjustable)
Magnetic Trip
Im = 5…10 x In
3-Pole 4-Pole ¬ 
250 200…250 1250…2500 AA 140UE-LTF3-D25 140UE-LTF4-D25
320 256…320 1600…3200 AA 140UE-LTF3-D32 140UE-LTF4-D32
400 320…400 2000…4000 AA 140UE-LTF3-D40 140UE-LTF4-D40
500 400…500 2500…5000 AA 140UE-LTF3-D50 140UE-LTF4-D50
630 504…630 3150...6300 AA 140UE-LTF3-D63 140UE-LTF4-D63
  
¬ 4th pole neutral — 0/100% protected

Trip Units, Electronic¬ 

Rated Current In [A] Adjustment Range [A] Protection Type Ground Fault Functions Cat. No.
Thermal Trip T 
Ir = 0.4…1.0 x In
Magnetic Trip
Im = 2…10 x In
IG=0.2…1.0In TG=ms 3-Pole 4-Pole
630 250…630 1260…6300 250…630 A LS Electronic Trip Unit 140UE-LTL3-D63 140UE-LTL4-D63
630 250…630 1260…6300 250…630 A LSI Electronic Trip Unit 140UE-LTH3-D63 140UE-LTH4-D63
630 250…630 1260…6300 250…630 A LSG Electronic Trip Unit 126...630 Inst.,120, 300 140UE-LTG3-D63 140UE-LTG4-D63
630 250…630 1260…6300 250…630 A LSIG Electronic Trip Unit 126…630 Inst.,120, 300 140UE-LTI3-D63 140UE-LTI4-D63
  
¬ Adjustable long-time delay: 2…24 s at 6 time Ir
T Thermal trip settings: 250, 300, 315, 400, 500, 600, 630 A

Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Current In [A] Protection Type
In
Breaking Capacity 380…415V (50 Hz)
3 Poles 4 Poles
35 kA 50 kA 70 kA 35 kA 50 kA 70 kA
Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
250 AA 140UE-L3F3-D25 140UE-L5F3-D25 140UE-L7F3-D25 140UE-L3F4-D25 140UE-L5F4-D25 140UE-L7F4-D25
320 AA 140UE-L3F3-D32 140UE-L5F3-D32 140UE-L7F3-D32 140UE-L3F4-D32 140UE-L5F4-D32 140UE-L7F4-D32
400 AA 140UE-L3F3-D40 140UE-L5F3-D40 140UE-L7F3-D40 140UE-L3F4-D40 140UE-L5F4-D40 140UE-L7F4-D40
500 AA 140UE-L3F3-D50 140UE-L5F3-D50 140UE-L7F3-D50 140UE-L3F4-D50 140UE-L5F4-D50 140UE-L7F4-D50
630 AA 140UE-L3F3-D63 140UE-L5F3-D63 140UE-L7F3-D63 140UE-L3F4-D63 140UE-L5F4-D63 140UE-L7F4-D63
  

Assembled Circuit Breakers, Electronic Trip Units

Rated Current In [A] Protection Type Breaking Capacity 380…415V (50 Hz)
3 Poles 4 Poles
35 kA 50 kA 70 kA 35 kA 50 kA 70 kA
Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
630 250…630 A LS Electronic Trip Unit 140UE-L3L3-D63 140UE-L5L3-D63 140UE-L7L3-D63 140UE-L3L4-D63 140UE-L5L4-D63 140UE-L7L4-D63
630 250…630 A LSI Electronic Trip Unit 140UE-L3H3-D63 140UE-L5H3-D63 140UE-L7H3-D63 140UE-L3H4-D63 140UE-L5H4-D63 140UE-L7H4-D63
630 250…630 A LSG Electronic Trip Unit 140UE-L3G3-D63 140UE-L5G3-D63 140UE-L7G3-D63 140UE-L3G4-D63 140UE-L5G4-D63 140UE-L7G4-D63
630 250…630 A LSIG Electronic Trip Unit 140UE-L3I3-D63 140UE-L5I3-D63 140UE-L7I3-D63 140UE-L3I4-D63 140UE-L5I4-D63 140UE-L7I4-D63
  

Isolation Disconnector — IEC 60947-3

Rated Current
In [A]
Thermal Trip
Ir = In [A]
Magnetic Trip [A]
Im = 10 x In
Breaking Capacity (50 Hz)
Icu /Ics [kA]
Interrupting Rating
(60 Hz) [kA]
Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V 3-Pole 4-Pole
630 6300 100 100 70 70 32 32 25 13 100 65 32 140UE-L7S3-D63 140UE-L7S4-D63
  

Earth Leakage Protector

Earth Leakage Adjustment Range [A] Max. Current [A] Cat. No.
3-Pole 4-Pole
0.3…10 400 140U-L-ELP4003 140U-L-ELP4004
630 140U-L-ELP6303 140U-L-ELP6304
  

Accessories — 630 A, L-Frame

Internal Control Modules — Field Installed

  Description Mounting location Diagram Cat. No.
Click to enlarge - 140U-43-1 Auxiliary Contact (AX)
Electrically indicates "ON/OFF" status of breakers
(1) 1a-1b Click to enlarge - 140U-51-2 Click to enlarge - 140U-43-3 140U-H-EA1
(2) 1a-1b Left AND Right Side 140U-H-EA2
Alarm Contact (AL)
Electronically indicates when the breaker is in the "TRIPPED" state
(1) 1M (make)-1B (break) Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-5 140U-J-ER1
Right Side Only
Click to enlarge - 140U-43-6 Auxiliary/Alarm Contact (AX/AL)
Combination

Combination of auxiliary contact and alarm contact
(1) 1a-1b
(1) 1M (make)-1B (break)
Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-8 140U-J-EA1R1
Right Side Only
Click to enlarge - 140U-43-9 Shunt Trip (SNT)
Provides remote tripping of the circuit breaker
Undervoltage trip not available when shunt trip is used
24…60 V, 50/60/DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-11 140U-H-SNJ
110…240V, 50/60/DC 140U-H-SND
380…440V AC, 220…250V DC 140U-H-SNN
380…600V, 50/60 Hz Left Side Only 140U-H-SNB
Undervoltage Release (UVT)
Automatically trips breaker when voltage falls between preset value, 35…70%
Shunt trip is not available when undervoltage release is used
24V, 50/60Hz AC; 24V DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-13 140U-H-UJ
110…127V, 50/60 Hz 140U-H-UD
208…240V, 50/60 Hz 140U-H-UA
380…500V, 50/60 Hz Left Side Only 140U-H-UB
  

Internal Control Modules — Factory Installed

Left side only

Mounting Location

Right side only

Click to enlarge - 140U-43-14
(1) Shunt Trip (SNT)or(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or(2) Auxiliary contacts (AX)or(1) Alarm contact (AL)or(1) Alarm contact (AL) + Auxiliary contact (AX)


Auxiliary and
Alarm Contacts
Suffix
(1) AX - A
(2) AX - B
(1) AL - D
(1) AX + (1) AL - F
  

Shunt Trip
Combinations
Suffix
(1) SNT only - PÄ
(1) AX + (1) SNT - QÄ
(2) AX + (1) SNT - RÄ
(1) AX + (1) AL + (1) SNT - TÄ
(1) AL + (1) SNT - VÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24…60 110…240 380…600
AC,
50/60 Hz
J D B
DC J D
  

Undervoltage Release Combinations Suffix
(1) UVT only - GÄ
(1) AX + (1) UVT - HÄ
(2) AX + (1) UVT - JÄ
(1) AX + (1) AL + (1) UVT - LÄ
(1) AL + (1) UVT - NÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24 110…127 208…240 380…500 525…600
AC,
50/60 Hz
J D A B C
DC J
  

¬  For additional voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.


External Accessories

  Description Cat. No.
Click to enlarge - 140U-L-TS_r_bw Terminal Shields
IP20 Ingress Protection Rating
Qty: 1 140U-L-TS
Terminal Shield, 4-Pole Qty: 1 140U-L-TS4
Click to enlarge - 140_BASE_R-bw Plug-in Adapter, 3-Pole Qty: 1 140U-L-PAD3
Plug-in Adapter, 4-Pole Qty: 1 140U-L-PAD4
Plug-in adapter auxiliary contact Qty: 1 140U-L-PDK
Click to enlarge - ab_switch-21474_bw Motor Operator
Remotely opens, closes, and resets the circuit breaker
110…240V AC
Qty: 1 140U-L-EOPD
Motor Operator
Remotely opens, closes, and resets the circuit breaker
24V DC
Qty: 1 140U-L-EOPZ
Click to enlarge - interlock 2 bw-21996 Sliding Bar Interlock Qty: 1 140U-L-SBLK
Click to enlarge - 140U-52-3 Flex-Cable Operating Mechanism
Includes handle, cable, operating, and bail mechanism
Pre-assembled and adjusted
UL Type 1/3/12/4/4X
Flange-Mount Operating Handle
Non-Metallic
4 ft (1.2 m) Cable 140U-L-FCX04
6 ft (1.9 m) Cable 140U-L-FCX06
10 ft (3.0 m) Cable 140U-L-FCX10
Click to enlarge - 140M-21-2 Flex-Cable Operating Mechanism
Includes handle, cable, operating, and bail mechanism
Pre-assembled and adjusted
UL Type 4/4X
Flange-Mount Operating Handle
Stainless Steel
4 ft (1.2 m) Cable 140U-L-FCS04
6 ft (1.9 m) Cable 140U-L-FCS06
10 ft (3.0 m) Cable 140U-L-FCS10
Click to enlarge - lockout lrg_bw Rotary, Variable-Depth Operating Mechanism
UL Type 3/12/4/4X, IP 66 Rotary handle
12 in. (30.48 cm) operating rod
Black Handle 140U-L-RVM12B
Red/Yellow Handle 140U-L-RVM12R
Rotary, Variable-Depth Operating Mechanism
UL Type 3/12/4/4X, IP 66 Rotary handle
21 in. (53.34 cm) operating rod
Black Handle 140U-L-RVM21B
Red/Yellow Handle 140U-L-RVM21R
Click to enlarge - 140M-20-4 End Cap Kit
Provides 3-phase connections for terminal or bolt-on connections
Metric hardware provided
Qty: 1 140U-L-ECM
End Cap Kit, 4-Pole - Metric Hardware (1) Qty: 1 140U-L-ECM4
Click to enlarge - 140U-L-MHM Replacement Mounting Hardware
(4) M5 - 0.8 x 100 mm
Qty: 1 140U-L-MHM
  

Optional Terminal Lug Kits

  Description Terminal Body Material Wire Type Wire Size, AWG Wire Size, Metric Pkg. Quantity Cat. No.
Click to enlarge - 140U-L-TL6C1_r_bw Terminal Lugs Aluminum Cu/Al (1) 500…750 MCM (1) 240…380 mm2 3 (includes shield) 140U-L-TL6A1
4 (includes shield) 140U-L-TL6A14
Copper Cu only (1) 500…750 MCM (1) 240…380 mm2 3 (includes shield) 140U-L-TL6C1
4 (includes shield) 140U-L-TL6C14
Click to enlarge - 140U-L-TL6A2_r_bw Aluminum Cu/Al (2) 2…500 MCM (2) 35…240 mm2 3 (includes shield) 140U-L-TL6A2
4 (includes shield) 140U-L-TL6A24
Copper Cu only (2) 2…500 MCM (2) 35…240 mm2 3 (includes shield) 140U-L-TL6C2
4 (includes shield) 140U-L-TL6C24
Click to enlarge - 140U-L-TL6C1_r_bw Aluminum Cu/Al (1) 2…500 MCM (1) 35…240 mm2 1 140U-L-TL4A1
Copper Cu only 140U-L-TL4C1
  

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - l-frame_4p_3p