Bulletin 140UE M-Frame

Product Selection — 800 A, M-Frame

Click to enlarge - 140U-39-6



Note: Terminal box lugs and mounting hardware must be ordered separately. See External Accessories

Breaker Frames

Rated Current In [A] Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] 3-Pole
220…240V 380…415V 500V 690V 240V 480V 600V Cat. No.
800 65 65 50 50 25 25 20 10 65 50 25 140UE-M5X3
100 100 70 50 35 13 25 13 100 65 35 140UE-M7X3
  

Trip Units and Rating Plugs

Trip Units, Thermal-Magnetic

Rated Current In [A] Adjustment Range [A] 3-Pole
Thermal Trip
Ir = In
Magnetic Trip
Im = 5…10 x In
Cat. No.
300 300 1500…3000 140UE-MTD3-D30
350 350 1750…3500 140UE-MTD3-D35
400 400 2000…4000 140UE-MTD3-D40
450 450 2250…4500 140UE-MTD3-D45
500 500 2500…5000 140UE-MTD3-D50
600 600 3000…5000 140UE-MTD3-D60
700 700 3500…7000 140UE-MTD3-D70
800 800 4000…8000 140UE-MTD3-D80

Trip Units, Electronic

Rated Current In [A] Adjustment Range [A] Protection Type Ground Fault Functions Cat. No.
Thermal Trip
Ir = 0.5…1.0 x In
Magnetic Trip
Im = 2…8 x In
IG=0.2…1.0IN TG=ms
800A 400…800¬  800…6400 400…800 A LS Electronic Trip Unit 140UE-MTL3-D80
400…800¬  400…800 A LSI Electronic Trip Unit 140UE-MTH3-D80
400…800¬  400…800 A LSG Electronic Trip Unit 126...630 Inst.,120, 300 140UE-MTG3-D80
400…800¬  400…800 A LSIG Electronic Trip Unit 126…630 Inst.,120, 300 140UE-MTI3-D80
  
¬ Complete circuit breaker with electronic trip unit requires purchase of a rating plug.

Rating Plugs

Rating Plugs
Description Cat. No.
400/500/630/800 A Rating Plug 140UE-MAP3-D80
  

Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Current In [A] Protection Type 3-Pole
50 kA 70 kA
Cat. No. Cat. No.
300 FA 140UE-M5D3-D30 140UE-M7D3-D30
350 FA 140UE-M5D3-D35 140UE-M7D3-D35
400 FA 140UE-M5D3-D40 140UE-M7D3-D40
450 FA 140UE-M5D3-D45 140UE-M7D3-D45
500 FA 140UE-M5D3-D50 140UE-M7D3-D50
600 FA 140UE-M5D3-D60 140UE-M7D3-D60
700 FA 140UE-M5D3-D70 140UE-M7D3-D70
800 FA 140UE-M5D3-D80 140UE-M7D3-D80
  

Assembled Circuit Breakers, Electronic Trip Units

Protection Type 3-Pole
50 kA 70 kA
Cat. No. Cat. No.
400…800 A LS Electronic Trip Unit ¬  140UE-M5L3-D80 140UE-M7L3-D80
400…800 A LSI Electronic Trip Unit ¬  140UE-M5H3-D80 140UE-M7H3-D80
400…800 A LSG Electronic Trip Unit ¬  140UE-M5G3-D80 140UE-M7G3-D80
400…800 A LSIG Electronic Trip Unit ¬  140UE-M5I3-D80 140UE-M7I3-D80
  
¬ Complete circuit breaker with electronic trip unit requires purchase of a rating plug.

Accessories — 800 A, M-Frame

Internal Control Modules — Field Installed

  Description Mounting Location Diagram Cat. No.
Click to enlarge - 140U-51-1 Auxiliary Contact (AX)
Electrically indicates "ON/OFF" status of breakers
(1) 1a-1b Click to enlarge - 140U-51-2 Click to enlarge - 140U-43-3 140U-M-EA1
(2) 1a-1b Left AND Right side 140U-M-EA2
Alarm Contact (AL)
Electrically indicates when the breaker is in the "TRIPPED" state
(1) 1M (make)-1B (break) Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-5 140U-M-ER1
Right side ONLY
Click to enlarge - 140U-51-6 Auxiliary/Alarm Contact (AX/AL)
Combination

Combination of auxiliary contact and alarm contact
(1) 1a-1b
(1) 1M (make)-1B (break)
Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-8 140U-M-EA1R1
Right side ONLY
Click to enlarge - 140U-51-9 Shunt Trip (SNT)
Provides remote tripping of the circuit breaker
Undervoltage trip not available when shunt trip is used
12…24V, 50/60/DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-11 140U-M-SNJ
110…240V AC, 110…125V DC 140U-M-SND
380…440V AC, 220…250V DC 140U-M-SNN
480…600V, 50/60 Hz Left side ONLY 140U-M-SNB
Undervoltage Release (UVT)
Automatically trips breaker when voltage falls between preset value, 35…70%
Shunt trip is not available when undervoltage release is used
24V, 50/60 Hz Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-13 140U-M-UJ
110…127V, 50/60 Hz 140U-M-UD
208…240V, 50/60 Hz 140U-M-UA
380…500V, 50/60 Hz Left side ONLY 140U-M-UB
  

Internal Control Modules — Factory Installed

Left side only

Mounting Location

Right side only

Click to enlarge - 140U-43-14
(1) Shunt Trip (SNT)or(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or(2) Auxiliary contacts (AX)or(1) Alarm contact (AL)or(1) Alarm contact (AL) + Auxiliary contact (AX)


Auxiliary and
Alarm Contacts
Suffix
(1) AX - A
(2) AX - B
(1) AL - D
(1) AX + (1) AL - F
  

Shunt Trip Combinations Suffix
(1) SNT only - PÄ
(1) AX + (1) SNT - QÄ
(2) AX + (1) SNT - RÄ
(1) AX + (1) AL + (1) SNT - TÄ
(1) AL + (1) SNT - VÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 12…24 110…240 380…440 480…600
AC,
50/60 Hz
J D N B
Voltage [V] 12…24 110…125 220…250
DC J D N
  

Undervoltage Release Combinations Suffix
(1) UVT only - GÄ
(1) AX + (1) UVT - HÄ
(2) AX + (1) UVT - JÄ
(1) AX + (1) AL + (1) UVT - LÄ
(1) AL + (1) UVT - NÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24 110…127 208…240 380…480
AC,
50/60 Hz
J D A B
Voltage [V]
DC
  

¬  For additional voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.


External Accessories

  Description Cat. No.
Click to enlarge - 140U-52-3 Flex-Cable Operating Mechanism
Includes handle, cable, operating, and bail mechanism
Pre-assembled and adjusted
UL Type 1/3/12/4/4X
Flange-Mount Operating Handle
Non-Metallic
4 ft (1.3 m) Cable 140U-M-FCX04
6 ft (1.8 m) Cable 140U-M-FCX06
10 ft (3.0 m) Cable 140U-M-FCX10
Flex-Cable Operating Mechanism
Includes handle, cable, operating, and bail mechanism
Pre-assembled and adjusted
UL Type 4/4X
Flange-Mount Operating Handle
Stainless Steel
4 ft (1.3 m) Cable 140U-M-FCS04
6 ft (1.8 m) Cable 140U-M-FCS06
10 ft (3.0 m) Cable 140U-M-FCS10
Click to enlarge - Handlekit_m-frame_bw Rotary, Variable-Depth Operating Mechanism
UL Type 3/12/4/4X, IP 66 Rotary Handle
12 in. (30.48 cm) operating rod
Black Handle 140U-M-RVM12B
Red/Yellow Handle 140U-M-RVM12R
Rotary, Variable-Depth Operating Mechanism
UL Type 3/12/4/4X, IP 66 Rotary Handle
21 in. (53.34 cm) operating rod
Black Handle 140U-M-RVM21B
Red/Yellow Handle 140U-M-RVM21R
Click to enlarge - 140U-M-TLA3_r_bw Terminal Lugs Copper lug, Cu wire Only
(3) 3/0…300 MCM
or (3) 95…135 mm2
Qty: 1 140U-M-TLC3
Aluminum lug, Al or Cu wire
(3) 3/0…400 MCM
or (3) 95…185 mm2
Qty: 1 140U-M-TLA3
Click to enlarge - 140U_M_TLA2_right_bw Terminal Lugs Aluminum lug, Al or Cu wire
(2) 1…500 MCM
or (2) 50…240 mm2
Qty: 1 140U-M-TLA2
Click to enlarge - 140U_M_TLC2A_right_bw Terminal Lugs Aluminum lug, Al or Cu wire
(2) 500…750 MCM
or (2) 240…400 mm2
Qty: 1 140U-M-TLA2A
Click to enlarge - 140U_M_TLC2_right_bw Terminal Lugs Copper lug, Cu wire only
(2) 2/0…500 MCM
or (2) 70…240 mm2
Qty: 1 140U-M-TLC2
Click to enlarge - 140M-20-5 Phase Barriers
Provides additional phase clearance when special connections that extend past the circuit breaker housing are required
Qty: 2 140U-M-PB
Click to enlarge - 140M-20-3 Padlock Kit
Padlocking Hasp
Lock-OFF only
Qty: 1 140U-M-PL
Click to enlarge - 140M-21-6 Operating Handle Extension
Provides handle extension for ease of
operation
Qty: 1 140U-M-OHE
Click to enlarge - 140R-M-MHM_bw Replacement Mounting Hardware
(4) M8 - 1 x 35 mm
Qty: 1 140U-M-MHM
  

Approximate Dimensions — 800 A, M-Frame

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - 140U-61-1