Bulletin 140UE N-Frame

Product Selection — 1250 A, N-Frame

Click to enlarge - 140U-39-7



Note: Terminal box lugs and mounting hardware must be ordered separately. See External Accessories

Assembled Circuit Breakers, Electronic Trip Units

Rated
Current
In [A]
Adjustment Range Ir [A] Protection
Type
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] 3-Pole 4-Pole
Thermal Trip
Ir = 0.5…1.0 x In
Magnetic Trip
Im = 2…8 x In
Icu /Ics [kA] Cat. No. Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V
50 kA Assembled Electronic Circuit Breakers
1250 600…1250¬  2400..10000 LS 100 100 70 50 35 18 25 13 100 65 35 140UE-N7L3-E12 140UE-N7L4-E12
LSI 100 100 70 50 35 18 25 13 100 65 35 140UE-N7H3-E12 140UE-N7H4-E12
LSG 100 100 70 50 35 18 25 13 100 65 35 140UE-N7G3-E12 140UE-N7G4-E12
LSIG 100 100 70 50 35 18 25 13 100 65 35 140UE-N7I3-E12 140UE-N7I4-E12
100 kA Assembled Electronic Ciruit Breakers
1250 600…1250¬  2400..10000 LS 200 100 100 50 65 33 35 18 200 100 50 140UE-N0L3-E12 140UE-N0L4-E12
LSI 200 100 100 50 65 33 35 18 200 100 50 140UE-N0H3-E12 140UE-N0H4-E12
LSG 200 100 100 50 65 33 35 18 200 100 50 140UE-N0G3-E12 140UE-N0G4-E12
LSIG 200 100 100 50 65 33 35 18 200 100 50 140UE-N0I3-E12 140UE-N0I4-E12
  
¬ Breakers include adjustable rating plug 600/800/1000/1200 A

Isolation Disconnector — IEC 60974-3

Rated Current In [A] Magnetic Trip
10 x In
Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] Cat. No. Cat. No.
220…240V 380…415V 500V 690V 240V 480V 600V
1250 12500 100 100 70 50 35 18 25 13 100 65 35 140UE-N7S3-E12 140UE-N7S4-E12
  

Accessories — 1250 A, N-Frame

Internal Control Modules — Field Installed

  Description Mounting Location Diagram Cat. No.
Click to enlarge - 140U-51-1 Auxiliary Contact (AX)
Electrically indicates "ON/OFF" status of breakers
(1) 1a-1b Click to enlarge - 140U-51-2 Click to enlarge - 140U-43-3 140U-N-EA1
(2) 1a-1b Left AND Right side 140U-N-EA2
Alarm Contact (AL)
Electrically indicates when the breaker is in the "TRIPPED" state
(1) 1M (make)-1B (break) Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-5 140U-N-ER1
Right side ONLY
Click to enlarge - 140U-51-6 Auxiliary/Alarm Contact (AX/AL)
Combination

Combination of auxiliary contact and alarm contact
(1) 1a-1b
(1) 1M (make)-1B (break)
Click to enlarge - 140U-43-2 Click to enlarge - 140U-43-8 140U-N-EA1R1
Right side ONLY
Click to enlarge - 140U-51-9 Shunt Trip (SNT)
Provides remote tripping of the circuit breaker
Undervoltage trip not available when shunt trip is used
12…24V, 50/60/DC Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-11 140U-N-SNJ
110…240V AC 140U-N-SND
380…440V AC, 220…250V DC 140U-N-SNN
480…600V, 50/60 Hz Left side ONLY 140U-N-SNB
Undervoltage Release (UVT)
Automatically trips breaker when voltage falls between preset value, 35…70%
Shunt trip is not available when undervoltage release is used
24V, 50/60 Hz Click to enlarge - 140U-43-10 Click to enlarge - 140U-43-13 140U-N-UJ
110…127V, 50/60 Hz 140U-N-UD
208…240V, 50/60 Hz 140U-N-UA
380…500V, 50/60 Hz Left side ONLY 140U-N-UB
  

Internal Control Modules — Factory Installed

Left side only

Mounting Location

Right side only

Click to enlarge - 140U-43-14
(1) Shunt Trip (SNT)or(1) Undervoltage Release (UVT)
(1) Auxiliary contact (AX)or(2) Auxiliary contacts (AX)or(1) Alarm contact (AL)or(1) Alarm contact (AL) + Auxiliary contact (AX)


Auxiliary and
Alarm Contacts
Suffix
(1) AX - A
(2) AX - B
(1) AL - D
(1) AX + (1) AL - F
  

Shunt Trip Combinations Suffix
(1) SNT only - PÄ
(1) AX + (1) SNT - QÄ
(2) AX + (1) SNT - RÄ
(1) AX + (1) AL + (1) SNT - TÄ
(1) AL + (1) SNT - VÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 12…24 110…240 380…440 480…600
AC,
50/60 Hz
J D N B
Voltage [V] 12…24 110…125 220…250
DC J D N
  

Undervoltage Release Combinations Suffix
(1) UVT only - GÄ
(1) AX + (1) UVT - HÄ
(2) AX + (1) UVT - JÄ
(1) AX + (1) AL + (1) UVT - LÄ
(1) AL + (1) UVT - NÄ
ÄStandard Voltage Suffix Codes¬ 
Voltage [V] 24 110…127 208…240 380…480
AC,
50/60 Hz
J D A B
Voltage [V]
DC
  

¬  For additional voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.


External Accessories

  Description Cat. No.
Click to enlarge - 140U-52-3 Flex-Cable Operating Mechanism
NEMA Type 1/3/12/4/4X
Flange-Mount Handle
4 ft. (1.2 m) Cable 140U-N-FCX04
6 ft. (1.9 m) Cable 140U-N-FCX06
10 ft. (3.0 m) Cable 140U-N-FCX10
Click to enlarge - 140U-52-4 Rotary, Variable-Depth Operating Mechanism
Type 1/12 Rotary Handle
12 in. (30.48 cm) operating rod
Black Handle 140U-N-RM12B
Click to enlarge - 140M-20-5 Phase Barriers
Provides additional phase clearance when special connections that extend past the circuit breaker housing are required
Qty: 2 140U-N-PB
Click to enlarge - 140M-20-3 Padlock Kit
Padlocking Hasp
Lock-OFF only
Qty: 1 140U-N-PL
Click to enlarge - EOP4MT07_right_bw Motor Operator
Remotely opens, closes, and resets the circuit breaker
110…240V AC
Qty: 1 140U-N-EOPD
Motor Operator, 230..240V AC Qty: 1 140U-N-EOPA
Click to enlarge - 140R-M-MHM_bw Replacement Mounting Hardware
(4) M8 - 1 x 35 mm
Qty: 1 140U-M-MHM
  

Terminal Lugs

  Product Description Terminal Body Material Wire Type Wire Size, AWG Wire Size, Metric Pkg. Quantity Cat. No.
Click to enlarge - 140U-N-TLA4_L_bw Terminal Lug Copper Cu (4) 3/0…400 MCM (4) 95…185 mm2 Qty: 1 140U-N-TLC4M
Aluminum Cu/Al (4) 4/0…500 MCM (4) 120…300 mm2 Qty: 1 140U-N-TLA4M
  

Approximate Dimensions — 1200 A, N-Frame

Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - n-frame_4p_3p


Click to enlarge - 140UE-Dims


  A3 A4 B C D E F G H
H-Frame 77
(3)
102
(4)
140
(5-1/2)
88
(3-1/2)
75
(3)
25.4
(1)
96.8
(3-13/16)
24.6
(31/32)
22.4
(7/8)
J-Frame 105
(4-1/8)
140
(5-1/2)
178
(7)
113
(4-29/64)
88
(3-1/2)
35
(1-3/8)
139.7
(5-1/2)
19.8
(25/32)
20.6
(13/16)
L-Frame 140
(5-1/2)
184
(7-1/4)
258
(10-5/32)
138
(5-7/16)
110
(4-21/64)
43.7
(1-23/32)
214.4
(8-7/16)
21.3
(27/32)
24.7
(31/32)
M-Frame 210
(8-17/64)
407
(16-1/64)
139
(5-15/32)
104
(4-3/32)
69.9
(2-3/4)
374.7
(14-3/4)
16
(5/8)
26.2
(1-1/32)
N-Frame 210
(8-17/64)
280
(11-1/64)
407
(16-1/64)
183
(7-13/64)
140
(5-1/2)
69.9
(2-3/4)
374.7
(14-3/4)
16
(5/8)
29.5
(1-5/32)