Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140U R-Frame
Bulletin 140U R-Frame
Product Selection — 2500 A, R-Frame
|
- UL 489
- CSA 22.2, No. 5
- IEC 60947-2
- CE
- KEMA
- CCC
Note: Terminal box lugs must be ordered separately. See Terminal Lugs.
Assembled Circuit Breakers, Electronic Trip Units
| Rated Current In [A] |
Adjustment Range Ir [A] | Protection Type |
Breaking Capacity (50 Hz) | Interrupting Rating (60 Hz) [kA] | Cat. No. | |||||||||
| Icu /Ics [kA] | ||||||||||||||
| 220…240V | 380…415V | 500V | 690V | 240V | 480V | 600V | ||||||||
| 1600 | Select Rating Plug⋆ | LS | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6L3-E16 |
| LSI | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6H3-E16 | ||
| LSG | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6G3-E16 | ||
| LSIG | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6I3-E16 | ||
| 2000 | Select Rating Plug⋆ | LS | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6L3-E20 |
| LSI | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6H3-E20 | ||
| LSG | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6G3-E20 | ||
| LSIG | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6I3-E20 | ||
| 2500 | Select Rating Plug⋆ | LS | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6L3-E25 |
| LSI | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6H3-E25 | ||
| LSG | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6G3-E25 | ||
| LSIG | 135 | 100 | 70 | 50 | — | — | 25 | 13 | 125 | 65 | 50 | 140U-R6I3-E25 | ||
| 100 kA @ 480V | ||||||||||||||
| 1600 | Select Rating Plug⋆ | LS | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0L3-E16 |
| LSI | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0H3-E16 | ||
| LSG | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0G3-E16 | ||
| LSIG | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0I3-E16 | ||
| 2000 | Select Rating Plug⋆ | LS | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0L3-E20 |
| LSI | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0H3-E20 | ||
| LSG | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0G3-E20 | ||
| LSIG | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0I3-E20 | ||
| 2500 | Select Rating Plug⋆ | LS | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0L3-E25 |
| LSI | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0H3-E25 | ||
| LSG | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0G3-E25 | ||
| LSIG | 200 | 100 | 100 | 50 | — | — | 35 | 18 | 200 | 100 | 65 | 140U-R0I3-E25 | ||
| ⋆ Select proper rating plug to cover thermal trip equipment. | ||||||||||||||
Rating Plugs
| 1600 A Frame | 2000 A Frame | 2500 A Frame | |||
| Rated Operational Current In [A] |
Cat. No. | Rated Operational Current In [A] |
Cat. No. | Rated Operational Current In [A] |
Cat. No. |
| 800 | 140U-R16RP3-E80 | 1000 | 140U-R20RP3-E10 | 1200 | 140U-R25RP3-E12 |
| 1000 | 140U-R16RP3-E10 | 1200 | 140U-R20RP3-E12 | 1250 | 140U-R25RP3-E125 |
| 1200 | 140U-R16RP3-E12 | 1250 | 140U-R20RP3-E125 | 1600 | 140U-R25RP3-E16 |
| 1250 | 140U-R16RP3-E125 | 1400 | 140U-R20RP3-E14 | 2000 | 140U-R25RP3-E20 |
| 1400 | 140U-R16RP3-E14 | 1600 | 140U-R20RP3-E16 | 2500 | 140U-R25RP3-E25 |
| 1500 | 140U-R16RP3-E15 | 2000 | 140U-R20RP3-E20 | — | — |
| 1600 | 140U-R16RP3-E16 | — | — | — | — |
Protection Type
| Protection Type∆ | ||||
| LS | LSI | LSG | LSIG | |
| Short Time Range | 2…8 x In | 2…8 x In | 2…8 x In | 2…8 x In |
| Short Time Delay | — | 1…300 ms | — | 1…300 ms |
| Ground Fault Pickup | — | — | 200…1200 A | 200…1200 A |
| Ground Fault Delay | — | — | 1…500 ms | 1…500 ms |
∆ Protection Type Definitions
- L: Adjustable long delay pickup (by adjustable rating plug)
- S: Adjustable short delay pickup with fixed short delay time (I2t response) or adjustable short delat time (flat response)
- I: Adjustable instantaneous pickup by setting short delay time to instantaneous
- G: Adjustable ground fault pickup with adjustable ground fault delay (flat response)