Molded Case Circuit Breakers

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Molded Case Circuit Breakers > Bulletin 140U R-Frame

Bulletin 140U R-Frame

Product Selection — 2500 A, R-Frame Accessories Approximate Dimensions
Product Selection — 2500 A, R-Frame

Click to enlarge - 140U-R_left



Note: Terminal box lugs must be ordered separately. See Terminal Lugs.

Assembled Circuit Breakers, Electronic Trip Units

Rated
Current
In [A]
Adjustment Range Ir [A] Protection
Type
Breaking Capacity (50 Hz) Interrupting Rating (60 Hz) [kA] Cat. No.
Icu /Ics [kA]
220…240V 380…415V 500V 690V 240V 480V 600V
1600 Select Rating Plug⋆  LS 135 100 70 50 25 13 125 65 50 140U-R6L3-E16
LSI 135 100 70 50 25 13 125 65 50 140U-R6H3-E16
LSG 135 100 70 50 25 13 125 65 50 140U-R6G3-E16
LSIG 135 100 70 50 25 13 125 65 50 140U-R6I3-E16
2000 Select Rating Plug⋆  LS 135 100 70 50 25 13 125 65 50 140U-R6L3-E20
LSI 135 100 70 50 25 13 125 65 50 140U-R6H3-E20
LSG 135 100 70 50 25 13 125 65 50 140U-R6G3-E20
LSIG 135 100 70 50 25 13 125 65 50 140U-R6I3-E20
2500 Select Rating Plug⋆  LS 135 100 70 50 25 13 125 65 50 140U-R6L3-E25
LSI 135 100 70 50 25 13 125 65 50 140U-R6H3-E25
LSG 135 100 70 50 25 13 125 65 50 140U-R6G3-E25
LSIG 135 100 70 50 25 13 125 65 50 140U-R6I3-E25
100 kA @ 480V
1600 Select Rating Plug⋆  LS 200 100 100 50 35 18 200 100 65 140U-R0L3-E16
LSI 200 100 100 50 35 18 200 100 65 140U-R0H3-E16
LSG 200 100 100 50 35 18 200 100 65 140U-R0G3-E16
LSIG 200 100 100 50 35 18 200 100 65 140U-R0I3-E16
2000 Select Rating Plug⋆  LS 200 100 100 50 35 18 200 100 65 140U-R0L3-E20
LSI 200 100 100 50 35 18 200 100 65 140U-R0H3-E20
LSG 200 100 100 50 35 18 200 100 65 140U-R0G3-E20
LSIG 200 100 100 50 35 18 200 100 65 140U-R0I3-E20
2500 Select Rating Plug⋆  LS 200 100 100 50 35 18 200 100 65 140U-R0L3-E25
LSI 200 100 100 50 35 18 200 100 65 140U-R0H3-E25
LSG 200 100 100 50 35 18 200 100 65 140U-R0G3-E25
LSIG 200 100 100 50 35 18 200 100 65 140U-R0I3-E25
  
⋆ Select proper rating plug to cover thermal trip equipment.

Rating Plugs

1600 A Frame 2000 A Frame 2500 A Frame
Rated Operational Current
In [A]
Cat. No. Rated Operational Current
In [A]
Cat. No. Rated Operational Current
In [A]
Cat. No.
800 140U-R16RP3-E80 1000 140U-R20RP3-E10 1200 140U-R25RP3-E12
1000 140U-R16RP3-E10 1200 140U-R20RP3-E12 1250 140U-R25RP3-E125
1200 140U-R16RP3-E12 1250 140U-R20RP3-E125 1600 140U-R25RP3-E16
1250 140U-R16RP3-E125 1400 140U-R20RP3-E14 2000 140U-R25RP3-E20
1400 140U-R16RP3-E14 1600 140U-R20RP3-E16 2500 140U-R25RP3-E25
1500 140U-R16RP3-E15 2000 140U-R20RP3-E20
1600 140U-R16RP3-E16
  

Protection Type

  Protection Type∆ 
LS LSI LSG LSIG
Short Time Range 2…8 x In 2…8 x In 2…8 x In 2…8 x In
Short Time Delay 1…300 ms 1…300 ms
Ground Fault Pickup 200…1200 A 200…1200 A
Ground Fault Delay 1…500 ms 1…500 ms
  

∆ Protection Type Definitions