Open Type Starters

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Open Type Starters > Bulletin 140A Manual Motor Starters

Bulletin 140A Manual Motor Starters

Product Selection Accessories Specifications Approximate Dimensions
Product Selection

3-pole Manual Motor Starter


Click to enlarge - 140A-C2A-A10 pp_bw


Rated Operational Current (Ie) Motor Current Adjustment Range Magnetic Release Operating Current Switching of Standard 3-phase AC Motors, AC-2, AC-3 Icu = Ics Cat. No.
3-phase [kW] (50 Hz)¬  3-phase [Hp] (60 Hz)T  400/415V
[A] [A] [A] 230V 400V 690V 230V 460V 575V [kA]
0.16 0.1…0.16 1.8 0.02 65 140A-C2A-A16
0.25 0.16…0.25 2.8 0.06 65 140A-C2A-A25
0.4 0.25…0.4 4.4 0.09 65 140A-C2A-A40
0.63 0.4…0.63 6.9 0.06/0.09 0.12/0.18 0.25 65 140A-C2A-A63
1 0.63…1.0 11 0.12 0.25 0.37/0.55 1/2 3/4 65 140A-C2A-B10
1.6 1.0…1.6 18 0.18/0.25 0.37/0.55 0.75/1.1 1 1 65 140A-C2A-B16
2.5 1.6…2.5 28 0.37 0.75 1.8 3/4 1-1/2 2 50 140A-C2A-B25
4 2.5…4.0 44 0.55/0.75 1.1/1.5 2.2/3.0 1 3 3 10 140A-C2A-B40
6.3 4.0…6.3 69 1.1/1.5 2.2 2 5 5 10 140A-C2A-B63
10 6.3…10 110 2.2 3.0/4.0 3 7-1/2 10 8 140A-C2A-C10
16 10…16 176 3.0/4.0 5.5/7.5 5 10 15 6 140A-C2A-C16
  
¬ Power ratings: Preferred values according to IEC 60072-1
T UL 508 approved as manual motor controller. Suitable for use in group motor applications: see UL / CSA Performance Data