Rated Operational Current (Ie) Motor Current Adjustment Range Magnetic Release Operating Current Switching of Standard 3-phase AC Motors, AC-2, AC-3 Icu = Ics Cat. No.
3-phase [kW] (50 Hz)¬  3-phase [Hp] (60 Hz)T  400/415V
[A] [A] [A] 230V 400V 690V 230V 460V 575V [kA]
0.16 0.1…0.16 1.8 0.02 65 140A-C2A-A16
0.25 0.16…0.25 2.8 0.06 65 140A-C2A-A25
0.4 0.25…0.4 4.4 0.09 65 140A-C2A-A40
0.63 0.4…0.63 6.9 0.06/0.09 0.12/0.18 0.25 65 140A-C2A-A63
1 0.63…1.0 11 0.12 0.25 0.37/0.55 1/2 3/4 65 140A-C2A-B10
1.6 1.0…1.6 18 0.18/0.25 0.37/0.55 0.75/1.1 1 1 65 140A-C2A-B16
2.5 1.6…2.5 28 0.37 0.75 1.8 3/4 1-1/2 2 50 140A-C2A-B25
4 2.5…4.0 44 0.55/0.75 1.1/1.5 2.2/3.0 1 3 3 10 140A-C2A-B40
6.3 4.0…6.3 69 1.1/1.5 2.2 2 5 5 10 140A-C2A-B63
10 6.3…10 110 2.2 3.0/4.0 3 7-1/2 10 8 140A-C2A-C10
16 10…16 176 3.0/4.0 5.5/7.5 5 10 15 6 140A-C2A-C16
  
¬ Power ratings: Preferred values according to IEC 60072-1
T UL 508 approved as manual motor controller. Suitable for use in group motor applications: see UL / CSA Performance Data

Accessories

  Description Connection Diagram For Use With Cat. No.
Click to enlarge - 140A-C-AEA10 pp_bw Auxiliary Contact for Flush Mounting
1-pole
No additional space required
Click to enlarge - 140A-C-AEA10 wd 140A 140A-C-AEA10
Click to enlarge - 140A-C-AEA210 wd 140A-C-AEA210
Click to enlarge - 140A-C-AEA01 wd 140A-C-AEA01
Click to enlarge - 140A-C-AEA201 wd 140A-C-AEA201
Click to enlarge - 140A-C-ASA11 pp_bw Auxiliary Contact for Left-side Mounting
2-pole
Adds 9 mm to the width of the Manual Motor Starter
Use compact bus bars with 54 mm spacing
Click to enlarge - 140A-C-ASA20 wd 140A 140A-C-ASA20
Click to enlarge - 140A-C-ASA11 wd 140A-C-ASA11
Click to enlarge - 140A-C-ASA02 wd 140A-C-ASA02
  
Package Quantity = 1

Accessories

  Description Trip Rating Connection Diagram For Use With Cat. No.
Click to enlarge - 140A-C-UXJ pp_bw Undervoltage Trip Release
For right-side mounting
Adds 18 mm to the width of the Manual Motor Starter
24V 60 Hz Click to enlarge - 140A-C-UX_wd 140A 140A-C-UXJ
24V 50 Hz 140A-C-UXK
48V 60 Hz 140A-C-UXX
220…230V 50 Hz 140A-C-UXF
240V 50 Hz / 277V 60 Hz 140A-C-UXT
400V 50 Hz / 460V 60 Hz 140A-C-UXN
415V 50 Hz / 480V 60 Hz 140A-C-UXB
500V 50 Hz / 575V 60 Hz 140A-C-UXM
110V 50 Hz / 120V 60 Hz 140A-C-UXD
240…260V 60 Hz 140A-C-UXA
110V 50 / 60 Hz 140A-C-UXKD
525V 50 Hz / 600V 60 Hz 140A-C-UXVC
Click to enlarge - 140A-C-SXJ pp_bw Shunt Trip Release
For right-side mounting
Adds 18 mm to the width of the Manual Motor Starter
24V 60 Hz Click to enlarge - 140A-C-SX_wd 140A 140A-C-SXJ
24V 50 Hz 140A-C-SXK
48V 60 Hz 140A-C-SXX
220…230V 50 Hz 140A-C-SXF
240V 50 Hz / 277V 60 Hz 140A-C-SXT
400V 50 Hz / 460V 60 Hz 140A-C-SXN
415V 50 Hz / 480V 60 Hz 140A-C-SXB
500V 50 Hz / 575V 60 Hz 140A-C-SXM
110V 50 Hz / 120V 60 Hz 140A-C-SXD
240…260V 60 Hz 140A-C-SXA
525V 50 Hz / 600V 60 Hz 140A-C-SXVC
  Terminal links  
Click to enlarge - 140A-C-W544 pp_bw Compact Bus Bars
45 mm spacing for manual motor starters with flush-mounted auxiliary contact blocks
2 x 3 140A 140A-C-W452
3 x 3 140A-C-W453
4 x 3 140A-C-W454
5 x 3 140A-C-W455
Compact Bus Bars
54 mm spacing for manual motor starters with side-mounted auxiliary contact blocks
2 x 3 140A 140A-C-W542
3 x 3 140A-C-W543
4 x 3 140A-C-W544
5 x 3 140A-C-W545
Click to enlarge - 140A-C-WT pp_bw Bus Bar Feeder Terminal
Supply of compact busbars
Increases wiring capacity
140A-C-W 140A-C-WT
Click to enlarge - 140A-C-WS pp_bw Blank Space Cover
For covering unused terminal links
140A-C-W 140A-C-WS
Click to enlarge - 140A-C-N12 pp_bw Screw Adapter
Hut (DIN) rail 35 x 7.5 mm, length 44 mm
140A 140A-C-N12
  
Package Quantity = 1

Accessories

  Description For Use With Cat. No.
Click to enlarge - 140A-C-EA41_4c Enclosures for Surface Mounting
With centre marks for two indicator lights
Includes protective earth and neutral wire terminals

Protection Class: IP41
140A 140A-C-EA41
Protection Class: IP55
(with seal and protective membrane)
140A 140A-C-EA55
Click to enlarge - 140A-C-EE_ pp_bw Enclosures for Flush Mounting
Includes protective earth and neutral wire terminals

Protection Class: IP41
140A 140A-C-EE41
Protection Class: IP55
(with seal and protective membrane)
140A 140A-C-EE55
Click to enlarge - 140A-C-N55_4c Button Membrane
For IP55 enclosures
Replacement part with four screws (mounting frame included)
140A-C-EA55
140A-C-EE55
140A-C-N55
Click to enlarge - 140-LR120 pp_bw Pilot Lights
Length of connection leads 180 mm, includes lamp, protection class IP54.
Green 120V 198E-A…, 198E-C…, 140A-C-E… 140-LG120
240V 198E-A…, 198E-C…, 140A-C-E… 140-LG240
400V 198E-A…, 198E-C…, 140A-C-E… 140-LG400
415V 198E-A…, 198E-C…, 140A-C-E… 140-LG415
480V 198E-A…, 198E-C…, 140A-C-E… 140-LG480
Red 120V 198E-A…, 198E-C…, 140A-C-E… 140-LR120
240V 198E-A…, 198E-C…, 140A-C-E… 140-LR240
400V 198E-A…, 198E-C…, 140A-C-E… 140-LR400
415V 198E-A…, 198E-C…, 140A-C-E… 140-LR415
480V 198E-A…, 198E-C…, 140A-C-E… 140-LR480
White 120V 198E-A…, 198E-C…, 140A-C-E… 140-LW120
240V 198E-A…, 198E-C…, 140A-C-E… 140-LW240
400V 198E-A…, 198E-C…, 140A-C-E… 140-LW400
415V 198E-A…, 198E-C…, 140A-C-E… 140-LW415
480V 198E-A…, 198E-C…, 140A-C-E… 140-LW480
Yellow 120V 198E-A…, 198E-C…, 140A-C-E… 140-LY120
240V 198E-A…, 198E-C…, 140A-C-E… 140-LY240
400V 198E-A…, 198E-C…, 140A-C-E… 140-LY400
415V 198E-A…, 198E-C…, 140A-C-E… 140-LY415
480V 198E-A…, 198E-C…, 140A-C-E… 140-LY480
Click to enlarge - 140A-C-M3 pp_bw Locking Arrangement
For locking ON-button of the Manual Motor Starter
For 1…3 padlocks with ø 4…6 mm
140A 140A-C-M3
Click to enlarge - 140A-C-M3E pp_bw Locking Arrangement
Suitable for enclosures 140A-C-E…
For 1…3 padlocks with ø 4…8 mm
140A-C-E… 140A-C-M3E
Click to enlarge - 140A-C-MT_4c Emergency-Stop Push Button Set
For use with enclosures
Twist to release
140A-C-E… 140A-C-MT
Click to enlarge - 140A-C-MK_4c Emergency-Stop Push Button Set
For use with enclosures
Key release
140A-C-E… 140A-C-MK
  
Package Quantity = 1

Specifications

IEC Performance Data

  Cat. No. 140A-C2A-…
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16
Rated Operational Current Ie [A] 0.16 0.25 0.4 0.63 1.0 1.6 2.5 4.0 6.3 10 16
Magnetic Release Current [A] 1.8 2.8 4.4 6.9 11 18 28 44 69 110 176
Switching of Standard Three-Phase Motors ¬ 
AC-2, AC-3
230/240V [kW] 0.06/0.09 0.12 0.18/0.25 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0
400/415V [kW] 0.02 0.06 0.09 0.18/0.25 0.25 0.37/0.55 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5
500V [kW] 0.18 0.25/0.37 0.55/0.75 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10
690V [kW] 0.25 0.37/0.55 0.75/1.1 1.8 2.2/3.0
Back-Up Fuses
gG, aM, only if Icc³Icu
230/240V [A] No fuses required 50
400/415V [A]   63 50
500V [A]   63 50 50
690V [A]   25 35
Ultimate- (Icu) and Rated Service (Ics) Short Circuit Breaking Capacity
Icu = Ics
230/240V [kA] 65 65 65 65 65 65 50 50 50 50 3
400/415V [kA] 65 65 65 65 65 65 50 10 10 8 6
500V [kA] 50 50 50 50 50 50 50 3 10 4.5 4.5
690V [kA] 50 50 50 50 50 50 4.5 2
  
¬ Power ratings: Preferred values according to IEC 60072-1

UL / CSA Performance Data

Manual Motor Controller
(UL 508, CSA C22.2 No.14, for group installation, in combination with a short-circuit protection device)


  Cat. No. 140A-C2A-…
A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16
Max. short-circuit current
480V [kA] 42 42 42 42 42 42 42 18 18 10 5
600V [kA] 42 42 42 42 42 42 10 5 5 5 5
Motor load
1-phase
115V [HP] 1/10 1/8 1/4 1/2 1
230V [HP] 1/10 1/6 1/3 3/4 1-1/2 3
3-phase
200V [HP] 1/2 3/4 1-1/2 2 3
230V [HP] 3/4 1 2 3 5
460V [HP] 1/2 1 1-1/2 3 5 7-1/2 10
575V [HP] 3/4 1 2 3 5 10 15
Maximum rated current of protection device
  [A] 175
  

Specifications

General Data

Cat. No. 140A-C2A
Rated Insulation Voltage Ui
EN/IEC [V] 690
UL, CSA [V] 600
Overvoltage Category / Pollution degree lll / 3
Rated Impulse Withstand Voltage Uimp
Main circuits 6 kV
Auxiliary circuits 6 kV
Rated Frequency [Hz] 40…60
Life Span
Mechanical [operations] 100000
Electrical (Ie max.) [operations] 50000
Switching Frequency [operations/h] max. 30
Ambient Temperature
Storage [°C] - 25…+ 80
Operation [°C] - 25…+ 60
Resistance to Climatic Stress C IV (according to IEC 68)
Moisture/heat resistance 40 °C, 92 %, 56 days
Moisture/change resistance 23 °C, 83 %/40 °C, 93 %,
56 cycles
Site Altitude [m] £ 2000
Protection Class IP20, when wired
Resistance to Shock [g] 50, 11ms
Resistance to Vibration  
Frequency range [Hz] 10…150
in all directions [g] 7.5
Rated Thermal Current Ith
IEC  
up to 40°C ambient temperature [A] 0.1…16
up to 60°C ambient temperature [A] 0.1…16
Rated Supply Current Ie [A] 0.1…16
Number of setting ranges 11
Dependence on Temperature
40 °C [A] no reduction
50 °C [A]
60 °C [A]
70 °C [A] 15 % current reduction of the upper rated current Ie
Overload Protection
Characteristics EN/IEC 60947-4-1
Motor protection
Ambient Temperature Compensation [°C] - 20…+ 60
Trip class 10
Magnetic Release fixed setting
Release current 11 x Ie max.
Ie max. = maximum values of setting ranges
Total Power dissipation
Manual motor starter at rated load [W] 7
Main Supply Application Usable as main supply switch according to EN/IEC 60-204 with corresponding accessories
  

Cat. No. 140A-C2A
Conformity to Standards IEC 60947-1/ -2/ -4/ -5-1
UL 508; CSA 22.2, Part 1
Approvals/Markings CE, cULus Listed
Terminal Parts Click to enlarge - 140A_004 tp
Type of terminals
Screwdriver Pozidriv No. 2/Blade No. 3
Click to enlarge - 140A_001 tp 1. conductor [mm2 ]/[AWG] 1…4/No. 16…12
2. conductor [mm2 ]/[AWG] 1…4/No. 16…12
Click to enlarge - 140A_002 tp 1. conductor [mm2 ]/[AWG] 1…6/No. 16…12
2. conductor [mm2 ]/[AWG] 1…6/No. 16…12
Click to enlarge - 140A_003 tp 1. conductor [mm2 ]/[AWG] 1.5…6/No. 16…12
2. conductor [mm2 ]/[AWG] 1.5…6/No. 16…12
Tightening torque [Nm]/[lb-in] 2…2.5/18…22
  

Weights

Description Cat. No. Weight
Manual Motor Starter 140A-C2A-… 290 g
Auxiliary Contact Blocks for Flush Mounting 140A-C-AEA… 12 g
Auxiliary Contact Blocks for Left-side Mounting 140A-C-ASA… 35 g
Undervoltage Release 140A-C-UX… 104 g
Shunt Release 140A-C-SX… 100 g
Bus Bar Feeder Terminal 140A-C-WT 36 g
Compact Bus Bar 140A-C-W452 42 g
140A-C-W453 69 g
140A-C-W454 94 g
140A-C-W455 119 g
140A-C-W542 45 g
140A-C-W543 76 g
140A-C-W544 104 g
140A-C-W545 135 g
Blank Space Cover 140A-C-WS 3.3 g
Enclosure for Surface Mounting 140A-C-EA41 250 g
140A-C-EA55 258 g
Enclosure for Flush Mounting 140A-C-EE41 126 g
140A-C-EE55 134 g
Button Membrane 140A-C-N55 8 g
Indicator Light 140-L… 10 g
Hut (DIN) rail Adapter 140A-C-N12 16 g
Locking Arrangement 140A-C-M3E 19 g
140A-C-M3 11 g
  

Specifications

Specifications of Accessories

  Cat. No. 140A-C-AEA...
Auxiliary Contact Block
for Flush Mounting
Cat. No. 140A-C-ASA...
Auxiliary Contact Block
for Left-side Mounting
Rated Thermal Current Ith    
at 40°C ambient temperature [A] 6 10
at 60°C ambient temperature [A] 4 6
Contact Class Coordination
According to NEMA
   
(UL/CSA Standards) AC B 600 Standard Pilot Duty B 600 Standard Pilot Duty
  DC R 300 Light Pilot Duty R 300 Light Pilot Duty
Back-Up Fuses gG, gL [A] 16 16
Rated Supply Current [V] 230/240 400/415 500 690 230/240 400/415 500 690
  AC-15 [A] 2 1 0.8 0.5 2 1 0.8 0.5
  DC-13 [V] 24 48 110 220 24 48 110 220
  [A] 2 0.6 0.2 0.1 2 0.6 0.2 0.1
Terminal Parts  
Type of terminals Click to enlarge - 140A_005 tp Click to enlarge - 140A_005 tp
Screwdriver Pozidriv No. 2/Blade No. 3
Click to enlarge - 140A_001 tp 1. conductor [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14
2. conductor [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14
Click to enlarge - 140A_002 tp 1. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14
2. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14
Click to enlarge - 140A_003 tp 1. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14
2. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14
Tightening torque [Nm]/[lb-in.] 1…1.5/9…13 1…1.5/9…13
  

  Cat. No. 140A-C-UX...
Undervoltage Release Unit
for Right-side Mounting
Cat. No. 140A-C-SX...
Shunt Release
for Right-side Mounting
Cat. No. 140A-C-WT
Supply Block
Actuating Voltage  
Pull-in 0.8…1.1 x Us 0.7…1.1 x Us  
Drop-out 0.7…0.35 x Us  
Rated Control Voltage min. 12V 50 Hz, 14V 60 Hz 12V 50 Hz, 14V 60 Hz  
  max. 600V 50 Hz 600V 50 Hz  
On-Time 100 % 100 %  
Coil Rating Pull-in 8.5 VA, 6 W 8.5 VA, 6 W  
Hold 3 VA, 1.2 W 3 VA, 1.2 W  
Terminal Parts  
Type of terminals Click to enlarge - 140A_005 tp Click to enlarge - 140A_005 tp Click to enlarge - 140A_006 tp
Screwdriver Pozidriv No. 2/Blade No. 3 Pozidriv No. 2/Blade No. 3 Pozidriv No. 2/Blade No. 3
Click to enlarge - 140A_001 tp 1. conductor [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 4…16/No. 14…6
2. conductor [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 4…16/No. 14…6
Click to enlarge - 140A_002 tp 1. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14 4…16/No. 14…6
2. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14 4…16/No. 14…6
Click to enlarge - 140A_003 tp 1. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14 4…16/No. 14…6
2. conductor [mm2]/[AWG] 0.75…4/No. 18…14 0.75…4/No. 18…14 4…16/No. 14…6
Tightening torque [Nm]/[lb-in.] 1…1.5/9…13 1…1.5/9…13 4/36
  

  Cat. No. 140A-C-W45...
Compact Bus Bar
Cat. No. 140A-C-W54...
Compact Bus Bar
Rated Insulation Voltage Ui [V] 690 690
Rated Thermal Current Ith [A] 63 63
  

  Cat. No. 140A-C-EA41 / -EE41
Enclosure
Cat. No. 140A-C-EA55 / -EE55
Enclosure
Cat. No. 140-L...
Indicator light
IP Protection IP41 IP55
(with seal and protective membrane)
IP54
Ambient Temperature [°C] - 25…+ 40 - 25…+ 40
Rated Operating Voltage [V] 120, 240, 415, 480
  

Specifications

Cut-off current

The Bulletin 140A-C2A manual motor starter limits short-circuit current Icc (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagram as a function of the system short-circuit current.

Click to enlarge - 140A_001 cu


Click to enlarge - 140A Let-Through cut-off Current_400V cu


Click to enlarge - 140A Time-current charact cu


Correspondingly the maximum forward i2 dt energy is limited. This value is indicated in the following diagram as a function of the system short-circuit current.

Click to enlarge - 140A Let-Through-Energy_400V cu


1) Operating Current of Thermal Releases:

The adjustable inverse bimetal trip reliability protects motors against overloads. The curve shows the mean operating current at an ambient temperature of 20 °C starting from cold.

In equipment at operating temperature, release time is less than or equal to release time from the cold state.


2) Operating Current of Magnetic Releases:

Electromagnetic instantaneous releases react at a fixed tripping current.

At the upper thermal release setting, this tripping current is 11 times the set current.


Current To Be Set:

Thermal releases meet the requirements for a thermal release of a starter in accordance with IEC 60947-4-1 f. If a different value is specified (such as reduced Ie in motors with an ambient temperature higher than 40 °C or a site altitude >2000 m above sea level), the rated operating current Ie must be adjusted.


Dimensions

Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - 140A-C2A_001 mo
140A-C2A


¬ Can be mounted on DIN Rail EN 50 022-35
T Auxiliary contact block for side-mounting of 140A-C-ASA…
‡ 140A-C-SX… shunt release or 140A-C-UX… undervoltage release


Click to enlarge - 140A-C2A_003 mo
140A-C2A with 140A-C-W…


Click to enlarge - 140A-C-EA41 mo
140A-C-EA41 / -EA55


Click to enlarge - 140A-C2A_002 mo
Mounting position/Safety clearance of 140A-C2A


Click to enlarge - 140A-C-N12 mo
140A-C-N12


Click to enlarge - 140A-C-WT mo
140A-C-WT


Click to enlarge - 140A-C2A_004 mo
140A-C2A with 140A-C-WT


Click to enlarge - 140A-C-EE41 mo
140A-C-EE41 / -EE55