Bulletin 190E/191E Eco Starters

Bulletin 190E Direct On-Line Eco Starters

Click to enlarge - 100-K_Starter_c4 Click to enlarge - 103S_wd_13_1

Note: Verify that the motor protection circuit breaker can be set to the rated motor current!

Click to enlarge - 190E-163-1 Click to enlarge - DC_symbol


Group Motor, Type E and Type F Combination Motor Controllers (UL/CSA)

The 190E/191E motor controllers can be used in a variety of applications. These starters can be used in a group motor application or as a stand-alone product without any additional short-circuit protection in the motor branch circuits.



Most of the 140M-C/D motor protection circuit breakers used in the 190E/191E starters are UL Listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass is to perform 6000 electrical ops. and an additional 4000 mechanical ops. after a short circuit.



By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits.



A combination of a 140M manual self protected combination motor controller and 100-C contactor can be listed as a Type E self-protected combination motor controller. In this case, the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require over sizing of the 140M motor protection circuit breaker or the 100-C contactor to achieve weld-free performance and meet the additional life requirements.


Product Selection and Coordination Ratings — UL/CSA in Group Motor Installations

Motor Current Adjustment Range [A] UL/CSA Hp Ratings (60 Hz) Max. Fuse or Circuit Breaker per NEC [A] Max. Short-Circuit Current [kA] DOL Starter Reversing Starter
Hp Ratings as a UL508 Motor Controller in Group Motor Installations§  Type 1 Coordination Type 2 Coordination Cat. No. Cat. No.
200V 230V 460V 575V 480V 600V 480V 600V
C-Frame with 100-K/104-K Mini Contactors
0.10…0.16 450 65 47 65 190E-KMNÄ2-CA16X 191E-KMNÄ1-CA16X
0.16…0.25 450 65 47 65 190E-KMNÄ2-CA25X 191E-KMNÄ1-CA25X
0.25…0.40 450 65 47 65 190E-KMNÄ2-CA40X 191E-KMNÄ1-CA40X
0.40…0.63 450 65 47 65 190E-KMNÄ2-CA63X 191E-KMNÄ1-CA63X
0.63…1.00 1/2 450 65 47 65 190E-KMNÄ2-CB10X 191E-KMNÄ1-CB10X
1.00…1.60 1/2 3/4 450 65 47 65 190E-KMNÄ2-CB16X 191E-KMNÄ1-CB16X
1.60…2.50 1/2 1/2 1/2…1 1...1-1/2 450 65 30 190E-KMNÄ2-CB25X 191E-KMNÄ1-CB25X
2.50…4.00 1/2…3/4 3/4 3/4…2 2…3 450 65 30 190E-KMNÄ2-CB40X 191E-KMNÄ1-CB40X
4.00…6.30 1 1...1-1/2 1-1/2…3 5 450 65 30 190E-KNNÄ2-CB63X 191E-KNNÄ1-CB63X
6.30…9.00 1-1/2…2 2 5 5 450 65 30 190E-KNNÄ2-CC10X 191E-KNNÄ1-CC10X
6.30…10.0 1-1/2…2 2...3 5 7-1/2 450 65 30 190E-KPNÄ2-CC10X 191E-KPNÄ1-CC10X
10.0…11.0 3 3 7-1/2 7-1/2 450 30 30 190E-KPNÄ2-CC16X 191E-KPNÄ1-CC16X
C-Frame with 100-C/104-C Contactors
0.10…0.16 450 65 47 65 47 190E-ANÄ2-CA16X 191E-ANÄ3-CA16X
0.16…0.25 450 65 47 65 47 190E-ANÄ2-CA25X 191E-ANÄ3-CA25X
0.25…0.40 450 65 47 65 47 190E-ANÄ2-CA40X 191E-ANÄ3-CA40X
0.40…0.63 450 65 47 65 47 190E-ANÄ2-CA63X 191E-ANÄ3-CA63X
0.63…1.00 1/2 3/4 450 65 47 65 47 190E-ANÄ2-CB10X 191E-ANÄ3-CB10X
1.00…1.60 1/2…1 3/4...1 450 65 47 65 47 190E-ANÄ2-CB16X 191E-ANÄ3-CB16X
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 1…2 450 65 30 65 10 190E-ANÄ2-CB25X 191E-ANÄ3-CB25X
2.50…4.00 1/2…1 3/4...1 1-1/2…3 2…3 450 65 30 50 190E-ANÄ2-CB40X 191E-ANÄ3-CB40X
4.00…6.30 1...1-1/2 1…2 3...5 5 450 65 30 50 190E-ANÄ2-CB63X 191E-ANÄ3-CB63X
6.30…9.00 1-1/2…2 2 5 7-1/2 450 65 30 50 190E-ANÄ2-CC10X 191E-ANÄ3-CC10X
6.30…10.0 1-1/2…3 2...3 5...7-1/2 7-1/2...10 450 65 30 50 190E-BNÄ2-CC10X 191E-BNÄ3-CC10X
10.0…12.0 3 3 7-1/2 10 450 30 30 190E-BNÄ2-CC16X 191E-BNÄ3-CC16X
10.0…16.0 3...5 5 7-1/2…10 10...15 450 30 30 190E-DNÄ2-CC16X 191E-DNÄ3-CC16X
14.5…20.0 5 5...7-1/2 15 15 450 30 30 190E-DNÄ2-CC20X 191E-DNÄ3-CC20X
18.0…23.0 5 7-1/2 15 15 450 30 30 190E-DNÄ2-CC25X 191E-DNÄ3-CC25X
D-Frame with 100-C/104-C Contactors
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 1…2 450 65 30 65 10 190E-ANÄ2-DB25X 191E-ANÄ3-DB25X
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 1…2 450 65 30 65 30 190E-DNÄ2-DB25X 191E-DNÄ3-DB25X
2.50…4.00 1/2…1 3/4...1 1-1/2…3 2…3 450 65 30 65 190E-ANÄ2-DB40X 191E-ANÄ3-DB40X
2.50…4.00 1/2…1 3/4...1 1-1/2…3 2…3 450 65 30 65 30 190E-DNÄ2-DB40X 191E-DNÄ3-DB40X
4.00…6.30 1…1-1/2 1…2 3…5 5 450 65 30 65 190E-ANÄ2-DB63X 191E-ANÄ3-DB63X
6.30…9.00 1-1/2…2 2 5 7-1/2 450 65 30 65 190E-ANÄ2-DC10X 191E-ANÄ3-DC10X
6.30…10.0 1-1/2…3 2...3 5…7-1/2 7-1/2…10 450 65 30 65 190E-BNÄ2-DC10X 191E-BNÄ3-DC10X
6.30…10.0 1-1/2…3 2...3 5…7-1/2 7-1/2…10 450 65 30 65 190E-CNÄ2-DC10X 191E-CNÄ3-DC10X
10.0…12.0 3 3 7-1/2 10 450 65 30 65 190E-BNÄ2-DC16X 191E-BNÄ3-DC16X
10.0…16.0 3…5 5 7-1/2…10 10 450 65 30 65 190E-CNÄ2-DC16X 191E-CNÄ3-DC16X
10.0…16.0 3…5 5 7-1/2…10 10…15 450 65 30 65 190E-DNÄ2-DC16X 191E-DNÄ3-DC16X
14.5…20.0 5 5...7-1/2 15 15 450 65 30 65 190E-DNÄ2-DC20X 191E-DNÄ3-DC20X
18.0…23.0 5 7-1/2 15 15 450 65 30 65 190E-DNÄ2-DC25X 191E-DNÄ3-DC25X
  
§ Hp ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current and service factor.

ÄCoil voltage code—see Ä Coil Voltage Codes for AC or DC Control


Product Selection and Coordination Ratings — UL/CSA as a UL508 Type F Combination Motor Controller

Motor Current Adjustment Range [A] UL/CSA Hp Ratings (60 Hz) Max. Short-Circuit Current [kA] DOL Starter Reversing Starter
Hp Ratings as a UL508 Type F Combination Motor Controller§  Type 1 Coordination Type 2 Coordination
200V 230V 460V 575V 480Y/277V 600Y/347V 480Y/277V 600Y/347V Cat. No. Cat. No.
C-Frame with Bulletin 100-K/104-K Mini Contactors
0.10…0.16 65 47 190E-KMNÄ2-CA16X-TE 191E-KMNÄ1-CA16X-TE
0.16…0.25 65 47 190E-KMNÄ2-CA25X-TE 191E-KMNÄ1-CA25X-TE
0.25…0.40 65 47 190E-KMNÄ2-CA40X-TE 191E-KMNÄ1-CA40X-TE
0.40…0.63 65 47 190E-KMNÄ2-CA63X-TE 191E-KMNÄ1-CA63X-TE
0.63…1.00 1/2 65 47 190E-KMNÄ2-CB10X-TE 191E-KMNÄ1-CB10X-TE
1.00…1.60 1/2 3/4 65 47 190E-KMNÄ2-CB16X-TE 191E-KMNÄ1-CB16X-TE
1.60…2.50 1/2 1/2 1/2…1 3/4...1-1/2 65 30 190E-KMNÄ2-CB25X-TE 191E-KMNÄ1-CB25X-TE
2.50…4.00 1/2…3/4 3/4 3/4…2 2…3 65 30 190E-KMNÄ2-CB40X-TE 191E-KMNÄ1-CB40X-TE
4.00…6.30 1 1...1-1/2 1-1/2…3 65 v  v  190E-KNNÄ2-CB63X-TE 191E-KNNÄ1-CB63X-TE
6.30…8.50 1-1/2…2 2 5 65 v  v  190E-KNNÄ2-CC10X-TE 191E-KNNÄ1-CC10X-TE
6.30…10.0 1-1/2…2 2...3 5 65 v  v  190E-KPNÄ2-CC10X-TE 191E-KPNÄ1-CC10X-TE
10.0…11.0 3 3 7-1/2 30 v  v  190E-KPNÄ2-CC16X-TE 191E-KPNÄ1-CC16X-TE
C-Frame with Bulletin 100-C/104-C Contactors
0.10…0.16 65 47 65 47 190E-ANÄ2-CA16X-TE 191E-ANÄ3-CA16X-TE
0.16…0.25 65 47 65 47 190E-ANÄ2-CA25X-TE 191E-ANÄ3-CA25X-TE
0.25…0.40 65 47 65 47 190E-ANÄ2-CA40X-TE 191E-ANÄ3-CA40X-TE
0.40…0.63 65 47 65 47 190E-ANÄ2-CA63X-TE 191E-ANÄ3-CA63X-TE
0.63…1.00 1/2 3/4 65 47 65 47 190E-ANÄ2-CB10X-TE 191E-ANÄ3-CB10X-TE
1.00…1.60 1/2…1 3/4...1 65 47 65 47 190E-ANÄ2-CB16X-TE 191E-ANÄ3-CB16X-TE
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 1…2 65 30 65 10 190E-ANÄ2-CB25X-TE 191E-ANÄ3-CB25X-TE
2.50…4.00 1/2…1 3/4...1 1-1/2…3 2…3 65 30 190E-ANÄ2-CB40X-TE 191E-ANÄ3-CB40X-TE
4.00…6.30 1...1-1/2 1…2 3...5 65 v  v  190E-ANÄ2-CB63X-TE 191E-ANÄ3-CB63X-TE
6.30…9.00 1-1/2…2 2 5 65 v  v  190E-ANÄ2-CC10X-TE 191E-ANÄ3-CC10X-TE
6.30…10.0 1-1/2…3 2...3 5...7-1/2 65 v  v  190E-BNÄ2-CC10X-TE 191E-BNÄ3-CC10X-TE
10.0…12.0 3 3 7-1/2 30 v  v  190E-BNÄ2-CC16X-TE 191E-BNÄ3-CC16X-TE
10.0…16.0 3...5 5 7-1/2…10 30 v  v  190E-CNÄ2-CC16X-TE 191E-CNÄ3-CC16X-TE
10.0…16.0 3...5 5 7-1/2…10 30 v  v  190E-DNÄ2-CC16X-TE 191E-DNÄ3-CC16X-TE
14.5…20.0 5 5...7-1/2 15 10 v  v  190E-DNÄ2-CC20X-TE 191E-DNÄ3-CC20X-TE
18.0…23.0 v  v  v  v  190E-DNÄ2-CC25X-TE 191E-DNÄ3-CC25X-TE
D-Frame with Bulletin 100-C/104-C Contactors
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 1…2 65 30 65 10 190E-ANÄ2-DB25X-TE 191E-ANÄ3-DB25X-TE
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 1…2 65 30 65 30 190E-DNÄ2-DB25X-TE 191E-DNÄ3-DB25X-TE
2.50…4.00 1/2…1 3/4...1 1-1/2…3 2…3 65 30 65 190E-ANÄ2-DB40X-TE 191E-ANÄ3-DB40X-TE
2.50…4.00 1/2…1 3/4...1 1-1/2…3 2…3 65 30 65 30 190E-DNÄ2-DB40X-TE 191E-DNÄ3-DB40X-TE
4.00…6.30 1…1-1/2 1…2 3…5 5 65 30 65 190E-ANÄ2-DB63X-TE 191E-ANÄ3-DB63X-TE
6.30…9.00 1-1/2…2 2 5 7-1/2 65 30 65 190E-ANÄ2-DC10X-TE 191E-ANÄ3-DC10X-TE
6.30…10.0 1-1/2…3 2...3 5…7-1/2 7-1/2…10 65 30 65 190E-BNÄ2-DC10X-TE 191E-BNÄ3-DC10X-TE
6.30…10.0 1-1/2…3 2...3 5…7-1/2 7-1/2…10 65 30 65 190E-CNÄ2-DC10X-TE 191E-CNÄ3-DC10X-TE
10.0…12.0 3 3 7-1/2 10 65 30 65 190E-BNÄ2-DC16X-TE 191E-BNÄ3-DC16X-TE
10.0…16.0 3…5 5 7-1/2…10 10 65 30 65 190E-CNÄ2-DC16X-TE 191E-CNÄ3-DC16X-TE
10.0…16.0 3…5 5 7-1/2…10 10…15 65 30 65 190E-DNÄ2-DC16X-TE 191E-DNÄ3-DC16X-TE
14.5…20.0 5 5...7-1/2 15 65 v  65 v  190E-DNÄ2-DC20X-TE 191E-DNÄ3-DC20X-TE
18.0…23.0 5 7-1/2 15 65 v  65 v  190E-DNÄ2-DC25X-TE 191E-DNÄ3-DC25X-TE
  
§ Hp ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current and service factor.
v This starter is not valid for application at this horsepower and voltage.

ÄCoil voltage code—see Ä Coil Voltage Codes for AC or DC Control


Product Selection and Coordination Ratings — UL/CSA as a UL508 Self-Protected Type E Combination Motor Controller

Motor Current Adjustment Range [A] UL/CSA Hp Ratings (60 Hz) Max. Short-Circuit Current [kA] DOL Starter Reversing Starter
Hp Ratings as a UL508 Self-Protected Type E Combination Motor Controller§ 
200V 230V 460V 575V 480Y/277V 600Y/347V Cat. No. Cat. No.
C-Frame with Bulletin 100-K/104-K Mini Contactors
0.10…0.16 v  v  190E-KMNÄ2-CA16X-TE 191E-KMNÄ1-CA16X-TE
0.16…0.25 v  v  190E-KMNÄ2-CA25X-TE 191E-KMNÄ1-CA25X-TE
0.25…0.40 v  v  190E-KMNÄ2-CA40X-TE 191E-KMNÄ1-CA40X-TE
0.40…0.63 v  v  190E-KMNÄ2-CA63X-TE 191E-KMNÄ1-CA63X-TE
0.63…1.00 v  v  190E-KMNÄ2-CB10X-TE 191E-KMNÄ1-CB10X-TE
1.00…1.60 v  v  190E-KMNÄ2-CB16X-TE 191E-KMNÄ1-CB16X-TE
1.60…2.50 v  v  190E-KMNÄ2-CB25X-TE 191E-KMNÄ1-CB25X-TE
2.50…4.00 v  v  190E-KMNÄ2-CB40X-TE 191E-KMNÄ1-CB40X-TE
4.00…6.30 v  v  190E-KNNÄ2-CB63X-TE 191E-KNNÄ1-CB63X-TE
6.30…8.50 v  v  190E-KNNÄ2-CC10X-TE 191E-KNNÄ1-CC10X-TE
6.30…10.0 v  v  190E-KPNÄ2-CC10X-TE 191E-KPNÄ1-CC10X-TE
10.0…11.0 v  v  190E-KPNÄ2-CC16X-TE 191E-KPNÄ1-CC16X-TE
C-Frame with Bulletin 100-C/104-C Contactors
0.10…0.16 65 47 190E-ANÄ2-CA16X-TE 191E-ANÄ3-CA16X-TE
0.16…0.25 65 47 190E-ANÄ2-CA25X-TE 191E-ANÄ3-CA25X-TE
0.25…0.40 65 47 190E-ANÄ2-CA40X-TE 191E-ANÄ3-CA40X-TE
0.40…0.63 65 47 190E-ANÄ2-CA63X-TE 191E-ANÄ3-CA63X-TE
0.63…1.00 1/2 3/4 65 47 190E-ANÄ2-CB10X-TE 191E-ANÄ3-CB10X-TE
1.00…1.60 1/2…1 3/4...1 65 47 190E-ANÄ2-CB16X-TE 191E-ANÄ3-CB16X-TE
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 65 v  190E-ANÄ2-CB25X-TE 191E-ANÄ3-CB25X-TE
2.50…4.00 v  v  190E-ANÄ2-CB40X-TE 191E-ANÄ3-CB40X-TE
4.00…6.30 v  v  190E-ANÄ2-CB63X-TE 191E-ANÄ3-CB63X-TE
6.30…9.00 v  v  190E-ANÄ2-CC10X-TE 191E-ANÄ3-CC10X-TE
6.30…10.0 v  v  190E-BNÄ2-CC10X-TE 191E-BNÄ3-CC10X-TE
10.0…12.0 v  v  190E-BNÄ2-CC16X-TE 191E-BNÄ3-CC16X-TE
10.0…16.0 v  v  190E-CNÄ2-CC16X-TE 191E-CNÄ3-CC16X-TE
10.0…16.0 v  v  190E-DNÄ2-CC16X-TE 191E-DNÄ3-CC16X-TE
14.5…20.0 v  v  190E-DNÄ2-CC20X-TE 191E-DNÄ3-CC20X-TE
18.0…23.0 v  v  190E-DNÄ2-CC25X-TE 191E-DNÄ3-CC25X-TE
D-Frame with Bulletin 100-C/104-C Contactors
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 65 v  190E-ANÄ2-DB25X-TE 191E-ANÄ3-DB25X-TE
1.60…2.50 1/2 1/2...3/4 3/4…1-1/2 1…2 65 30 190E-DNÄ2-DB25X-TE 191E-DNÄ3-DB25X-TE
2.50…4.00 v  v  190E-ANÄ2-DB40X-TE 191E-ANÄ3-DB40X-TE
2.50…4.00 1/2…1 3/4...1 1-1/2…3 2…3 65 30 190E-DNÄ2-DB40X-TE 191E-DNÄ3-DB40X-TE
4.00…6.30 v  v  190E-ANÄ2-DB63X-TE 191E-ANÄ3-DB63X-TE
6.30…9.00 v  v  190E-ANÄ2-DC10X-TE 191E-ANÄ3-DC10X-TE
6.30…10.0 v  v  190E-BNÄ2-DC10X-TE 191E-BNÄ3-DC10X-TE
6.30…10.0 v  v  190E-CNÄ2-DC10X-TE 191E-CNÄ3-DC10X-TE
10.0…12.0 v  v  190E-BNÄ2-DC16X-TE 191E-BNÄ3-DC16X-TE
10.0…16.0 v  v  190E-CNÄ2-DC16X-TE 191E-CNÄ3-DC16X-TE
10.0…16.0 v  v  190E-DNÄ2-DC16X-TE 191E-DNÄ3-DC16X-TE
14.5…20.0 v  v  190E-DNÄ2-DC20X-TE 191E-DNÄ3-DC20X-TE
18.0…23.0 v  v  190E-DNÄ2-DC25X-TE 191E-DNÄ3-DC25X-TE
  
§ Hp ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current and service factor.
v This starter is not valid for application at this horsepower and voltage.

ÄCoil voltage code—see Ä Coil Voltage Codes for AC or DC Control


Product Selection and Coordination Ratings (IEC Type 1 and Type 2 Short-Circuit Coordination)

Motor Current Adjustment Range [A] IEC kW Ratings for Standard Motors, 1500 rpm Max. Short-Circuit Current [kA] Max. Short-Circuit Current [kA] DOL Starter Reversing Starter
Max. kW, 50 Hz§  Type 1 Coordination Type 2 Coordination Cat. No. Cat. No.
230V 400V 500V 690V 230V 400V 500V 690V 230V 400V 500V 690V
C-Frame with Bulletin 100-K/104-K Mini Contactors
0.10…0.16 0.02 100 65 65 65 65 65 190E-KMNÄ2-CA16X 191E-KMNÄ1-CA16X
0.16…0.25 0.02 0.06 0.06 100 65 65 65 65 65 190E-KMNÄ2-CA25X 191E-KMNÄ1-CA25X
0.25…0.40 0.06 0.09 0.12 100 65 65 65 65 65 190E-KMNÄ2-CA40X 191E-KMNÄ1-CA40X
0.40…0.63 0.09 0.18 0.18 100 65 65 65 65 65 190E-KMNÄ2-CA63X 191E-KMNÄ1-CA63X
0.63…1.00 0.12 0.25 0.37 100 65 65 65 65 65 190E-KMNÄ2-CB10X 191E-KMNÄ1-CB10X
1.00…1.60 0.25 0.55 0.75 100 65 65 10 65 65 190E-KMNÄ2-CB16X 191E-KMNÄ1-CB16X
1.60…2.50 0.55 0.75 1.1 100 65 65 8 50 50 190E-KMNÄ2-CB25X 191E-KMNÄ1-CB25X
2.50…4.00 0.75 1.5 2.2 100 65 65 8 190E-KMNÄ2-CB40X 191E-KMNÄ1-CB40X
4.00…6.30 1.5 2.2 2.2 100 65 65 4 190E-KNNÄ2-CB63X 191E-KNNÄ1-CB63X