Bulletin 194L Control and Load Switches
|
Bulletin 194L IEC Control and Load Switches
- 12, 16, 20, 25, 32, and 40 A inductive load-rated switch
- IP66 water spray and dustproof handles
- IP20 finger-safe terminals
- Switches available for OFF-ON, changeover, star-delta (wye-delta),
reversing, ammeter, voltmeter and step switch configurations
- 1-…6-pole versions
- Front/door- or base/ DIN Rail-mounting configurations
- Thermoplastic enclosures IP66
- Suitable as motor disconnect (UL 508)
Bulletin 194L control and load switches are flexible, adaptable, time- and space-saving devices. Switches are available as front/door- or Base/DIN Rail mounting versions. Uniformly styled handles, featuring marked legend plates, are available in Selector-Knob, Disk-Style, Rectangular-Style and Key-Operated versions. Selector-Knob versions are available in three sizes. Most handles are available in grey/black or red/yellow and have padlockable versions.
A new thermoplastic enclosure features constructions of impact-resistant ABS or corrosion resistant NORYL materials. Both shallow and deep versions include 35 mm DIN Rail, grounding and neutral terminals, and captive cover screws. Enclosures may be ordered with or without cover openings for handle mounting. Enclosures are rated for use in IP66 (UL Type 1, 3, 3R, 12) environments.
Standards Compliance and Certifications
Standards Compliance
IEC 60947-3 Low-voltage switchgear and control gear part 3
UL 508
CSA: C22.2 No. 14
Certifications
UL Listed (File No. E14841, Guide NLRV)
CSA Certified (LR 13908)
Meets IEC, VDE and BS Standard requirements
CE
Product Overview
|
OFF-ON Switch
Two-position switch used to connect or disconnect a variety of inductive loads including: solenoids, handles, valves, magnetic starters and relays.
|
Ammeter Switch
Multi-position switch used to connect one or more phases of an electrical supply to an ammeter, so that the current in each phase can be displayed on one ammeter.
|
Changeover Switch
Two-position switch used in control applications to change between alternate power supplies. This device can typically be used to manually switch power supplies from a primary source to a stand-by/emergency supply in the event of a power outage.
|
Voltmeter Switch
Multi-position switch used to connect two lines of the electrical supply system to a voltmeter so that the voltage between the lines (phase-to-phase or phase-to-neutral) can be displayed on one voltmeter.
|
Star-Delta (Wye-Delta) Switch
Three-position (Off-Wye-Delta) switch used to manually control reduced-voltage motor starting. Operating the switch manually changes the wiring configuration of the motor from a star configuration to delta configuration after the controller operator has determined that the motor is up to operating speed.
|
Step Switch
Multi-position switch used to connect a variety of loads to an electrical supply in a pre-determined logical sequence. A typical application would be temperature control of a heating oven or furnace.
|
Reversing Switch
Three-phase, three-position (Forward-Off-Reverse) switch used to manually control a motors direction of rotation. Operating the switch changes the wiring configuration of the motor to operate in the forward or reverse direction.
Product Selection
Bulletin 194L Control and Load Switches
Catalog Number Explanation
| 194L | | A | 16 | | 175 | 3 | ||
| a | b | c | d |
| a | b | c | d | ||||||||||
| Installation Type | Load Size | Function/Circuit Diagram Ref. # | No. of Poles | ||||||||||
| Code | Description | Code | Description | Code | Function | Configuration | Use with Switch Style⋆ : | Circuit Diagram Ref. No. | Code | Description | |||
| A | Base/DIN mounting | 12 | 12 A | 150 | On/Off | 2-position (60 degrees) | 194L-E, 12…25 A, 1…6 poles | 1501…1506 | 1 | 1 pole | |||
| E | Front/door mounting | 16 | 16 A | 175 | 2-position (90 degrees) | 194L-E or 194L-A, 12…25 A, 1…6 poles | 1751…1756 | 2 | 2 poles | ||||
| C | Front/door mounting (For use with 32 A and 40 A switches only. Use when selecting 22.5 mm hole-mounting style handle.) | 20 | 20 A | 178 | 2-position (90 degrees-inverted) | 194L-E or 194L-A, 12…25 A, 1…4 poles | 1781…1784 | 3 | 3 poles | ||||
| 25 | 25 A | 225 | Change-Over | 1-2 (without 0, 45 degrees) | 194L-E, 12…25 A, 1…5 poles or | 2251…2255 | 4 | 4 poles | |||||
| 32 | 32 A | 250 | 1-2 (without 0, 60 degrees) | 194L-A, 12…25 A, 1…2 poles | 2501…2505 | 5 | 5 poles | ||||||
| 40 | 40 A | 300 | 1-0-2 (with 0, 30 degrees, spring return) | 194L-E, 12…25 A, 1…5 poles | 3001…3003 | 6 | 6 poles | ||||||
| 325 | 1-0-2 (with 0, 45 degrees) | 194L-E, 12 A, 1…3 poles | 3251…3254 | ||||||||||
| 326 | 1-0-2 (with 0, 45 degrees, spring return) | 194L-E or 194L-A, 12…25 A, 1…4 poles | 3261…3263 | ||||||||||
| 350 | 1-0-2 (with 0, 60 degrees) | 194L-E, 12 A, 1…3 poles | 3501…3504 | ||||||||||
| 375 | 1-0-2 (with 0, 90 degrees) | 3751…3754 | |||||||||||
| 425 | Step Switch | 1-2-3 (45 degrees) | 194L-E or 194L-A, 12…25 A, 1 pole | 4251…4253 | |||||||||
| 426 | 1-2-3-4 (45 degrees) | 194L-E, 12…25 A, 2…3 poles | 4261…4263 | ||||||||||
| 427 | 1-2-3-4-5 (45 degrees) | 194L-E, 12…25 A, 1…3 poles | 4271 | ||||||||||
| 428 | 1-2-3-4-5-6 (45 degrees) | 4281 | |||||||||||
| 450 | 1-2-3 (60 degrees) | 194L-E or 194L-A, 12…25 A, 1 pole | 4501…4503 | ||||||||||
| 451 | 1-2-3-4 (60 degrees) | 4511…4513 | |||||||||||
| 452 | 1-2-3-4-5 (60 degrees) | 194L-E, 12…25 A, 1 pole | 4521 | ||||||||||
| 453 | 1-2-3-4-5-6 (60 degrees) | 4531 | |||||||||||
| 500 | 0-1-2-3-4 (30 degrees) | 194L-E, 12…25 A, 1…3 poles | 5001…5003 | ||||||||||
| 501 | 0-1-2-3-4-5 (30 degrees) | 5011…5013 | |||||||||||
| 525 | 0-1-2 (45 degrees) | 5251…5253 | |||||||||||
| 526 | 0-1-2-3 (45 degrees) | 194L-E or 194L-A, 12…25 A, 1 pole 194L-E, 12…25 A, 2…3 poles |
5261…5263 | ||||||||||
| 527 | 0-1-2-3-4 (45 degrees) | 5271…5273 | |||||||||||
| 528 | 0-1-2-3-4-5 (45 degrees) | 5281…5283 | |||||||||||
| 550 | 0-1-2 (60 degrees) | 194L-E, 12…25 A, 1…3 poles | 5501…5503 | ||||||||||
| 551 | 0-1-2-3 (60 degrees) | 5511…5513 | |||||||||||
| 552 | 0-1-2-3-4 (60 degrees) | 5551…5553 | |||||||||||
| 553 | 0-1-2-3-4-5 (60 degrees) | 5531…5533 | |||||||||||
| 725 | Star-Delta (Wye-Delta) |
0-Y-D (45/90 degrees) | 194L-E or 194L-A, 12…25 A, 3 poles | 7253 | |||||||||
| 732 | 0-Y-D (45/90 degrees) | 7323 | |||||||||||
| 750 | 0-Y-D (60 degrees) | 194L-E, 12…25 A, 3 poles | 7503 | ||||||||||
| 730 | Reversing | 1-0-2 (45 degrees) | 194L-E or 194L-A, 12…25 A, 3 poles | 7303 | |||||||||
| 754 | 1-0-2 (60 degrees) | 194L-E, 12…25 A, 3 poles | 7543 | ||||||||||
| 825 | Voltmeter | 0-RN-SN-TN-TR-ST-RS (45 degrees) | 194L-E or 194L-A, 12…25 A, 1 pole | 8251 | |||||||||
| 827 | 0-RS-ST-TR (45 degrees) | 8271 | |||||||||||
| 875 | Ammeter | 0-1-2-3 (90 degrees) | 8751 | ||||||||||
| 876 | 0-1-2-3-4 (90 degrees) | 8761 | |||||||||||
| 877 | 0-1 (90 degrees inverted) | 8771 | |||||||||||
| ⋆ Switch load size of 32 A and 40 A can also be chosen in similar style and pole options. When choosing front mount style 194L-E for 32 A or 40 A, use the 194L-C code. |
|||||||||||||
Frequently Ordered 194L Switches — Base/Front-Mounted Switches
(Switch Handles listed on Bulletin 194L Handles (for use with Bulletin 194L Switches))
Bulletin 194L Handles (for use with Bulletin 194L Switches)
Catalog Number Explanation
| 194L | | HE | 6 | N | | 175 | ||
| a | b | c | d |
| a | |
| Code | Installation Type |
| HC | 22.5 mm mounting hole style handle (for use with front-mounted switches) |
| HE | Screw-mounting handle (for use with front- and base-mounted switches) |
| b | |||
| Code | Use with Handle Type |
Handle Legend Plate Size |
Use With 194L Switch Size |
| 4 | A, E, I, L | 48 mm x 48 mm (1-57/64 in. x 1-57/64 in.) |
194L-A12…A25 194L-E12…E25 194L-C32…C40 |
| S | 48 mm x 62 mm (1-57/64 in. x 2-7/16 in.) |
||
| 6 | A, E, I, L | 64 mm x 64 mm (2-33/64 in. x 2-33/64 in.) |
194L-A12…40 A 194L-E12…40 A |
| G, N | 67 mm x 67 mm (2-41/64 in. x 2-41/64 in.) |
||
| S | 64 mm x 78 mm (2-33/64 in. x 3-5/64 in.) |
||
Use Type G and N with ON-OFF function only (selection "d").
| c | ||
| Code | Legend Plate Type | Color |
| A | Square | Grey/black |
| I | Square | Red/yellow |
| E | Square/lockable | Grey/black |
| L | Square/lockable | Red/yellow |
| G | Disc/lockable (up to 3 locks) |
Grey/black |
| N | Disc/lockable (up to 3 locks) |
Red/yellow |
| S | Large square with extra legend area |
Grey/black |
| d |
| See Table on the next page. |
Frequently Ordered 194L Handles — Base/Front-Mounted Switch Handles
(Switch Body listed on Bulletin 194L Control and Load Switches)
| Handle Type | Degree of Protection | Handle Color | Legend Plate Size | For Use With | Legend Plate Marking | Cat. No.⋆ |
| A | IP66 | Black/Grey | 48 mm x 48 mm (1-57/64 in. x 1-57/64 in.) |
194L-E12…40 A, -7543 | 1-0-2 | 194L-HC4A-350 |
| 48 mm x 48 mm (1-57/64 in. x 1-57/64 in.) |
194L-E12…40 A, -7543 194L-A12…40 A, -7543 |
194L-HE4A-350 | ||||
| 64 mm x 64 mm (2-33/64 in. x 2-33/64 in.) |
194L-E12…40 A, -7543 194L-A12…40 A, -7543 |
194L-HE6A-350 | ||||
| E | Black/Grey | 48 x 48 mm (1-57/64 x 1-57/64 in.) |
194E-16…63 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 | 194L-HE4E-175 | |
| OFF-ON | 194L-HE4E-175I | |||||
| L | Red/Yellow | 48 x 48 mm (1-57/64 x 1-57/64 in.) |
194E-16…63 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 | 194L-HE4L-175 | |
| OFF-ON | 194L-HE4L-175I | |||||
| G | IP66 (UL Type 3/3R/12) | Black/Grey | 67 x 67 mm (2-41/64 x 2-41/64 in.) |
194E-25…100 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 OFF-ON |
194L-HE6G-175 |
| N | Red/Yellow | 67 x 67 mm (2-41/64 x 2-41/64 in.) |
194E-25…100 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 OFF-ON |
194L-HE6N-175 | |
| L | IP66 (UL Type 3/3R/12) | Red/Yellow | 48 x 48 mm (1-57/64 x 1-57/64 in.) |
194L-E12…40 A, -1753 | 0-1 | 194L-HC4L-175 |
| OFF-ON | 194L-HC4L-175I | |||||
| ⋆ For 22.5 mm mounting hole style (code HC), select either handle type A, E, I, or L with 48 x 48 mm legend plate size (code 4) only or handle type G or N with 64 x 64 mm legend plate size (code 6) only. | ||||||
22.5 mm Mounting Hole Style Knob and Keyed Type Handles
Accessories
Switching Diagrams
Contact target tables: X = Contact Closed
[Blank] = Contact Open
Circuit Diagram Nos. 1501…4253
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Circuit Diagram Nos. 4271…5531
|
|
|
|
|
|
|
|
|
|
|
|
Circuit Diagram Nos. 5012…5272
|
|
|
|
|
|
|
|
|
|
Circuit Diagram Nos. 5273…8771
|
|
|
|
|
|
|
|
Specifications
Electrical Ratings
| Performance Data | 12 A | 16 A | 20 A | 25 A | 32 A | 40 A | |||||||||||
| IEC Applications | |||||||||||||||||
| Rated voltage Ue ⋆ | IEC-947 | [V] | 690 | 690 | 690 | 690 | 690 | 690 | |||||||||
| Isolating conditions acc. to VDE fulfilled up to rated impulse voltage Uimp | [kV] |
6 |
6 |
6 |
6 |
8 |
8 |
||||||||||
| Thermal rated current Ith⋆ | 40 °C | IEC-947 | [A] | 16 | 20 | 25 | 30 | 32 | 45 | ||||||||
| Thermal rated current Ithe | 60 °C | IEC-947 | [A] | 12 | 16 | 20 | 25 | 32 | 45 | ||||||||
| Rated current Ie⋆ | IEC-947 | 690V | [A] | 12 | 16 | 20 | 25 | 32 | 40 | ||||||||
| AC-1/ AC-21A |
Non-inductive or slightly inductive loads/ switching of resistive loads with slight overload |
||||||||||||||||
| AC-1 | Non-inductive or slightly inductive loads | SEV | 660V | [A] | 12 | 16 | 20 | 25 | 32 | 40 | |||||||
| AC22A | Switching of mixed resistive and inductive loads with slight overload | IEC-947 | 220…500V 690V |
[A] [A] |
12 12 |
16 16 |
20 20 |
25 25 |
32 32 |
40 40 |
|||||||
| AC-15 | Switching of inductive drives, motors, valves, and electromagnets. | IEC-947 | 220…240V 380…415V 500V |
[A] [A] [A] |
5 3 2 |
6 4 2.5 |
7 5 3 |
8 6 4 |
— | — | |||||||
| DC switching capacity Rated current Ie |
Contacts in series |
||||||||||||||||
| Rated Voltage [V] | 1 | 2 | 3 | 4 | 5 | 6 | 8 | ||||||||||
| 24 | 48 | 72 | 96 | 120 | 144 | 192 | [A] | 12 | 16 | 20 | 22 | — | — | ||||
| 48 | 96 | 144 | 192 | 240 | 288 | 384 | [A] | 10 | 12 | 16 | 18 | — | — | ||||
| 60 | 120 | 180 | 240 | 300 | 360 | 450 | [A] | 8 | 10 | 12 | 14 | 32 | 40 | ||||
| DC-21A | For resistive loads, T £ 1ms | 110 | 220 | 330 | 440 | 550 | 660 | — | [A] | 2 | 2.5 | 4 | 5 | — | — | ||
| 220 | 440 | 660 | — | — | — | — | [A] | 0.5 | 0.6 | 0.7 | 0.8 | — | — | ||||
| Ue max = 600V | 440 | — | — | — | — | — | — | [A] | 0.4 | 0.4 | 0.5 | 0.5 | — | — | |||
| Rated making/breaking capacity (= 1.5 x Ie) | |||||||||||||||||
| 25.2 | 50.4 | 75.6 | 100.8 | 126 | 151.2 | 201.6 | [A] | 18 | 24 | 30 | 33 | — | — | ||||
| 1.05 x Rated voltage [V] | 50.4 | 100.8 | 151.2 | 201.6 | 252 | 302.4 | 403.2 | [A] | 15 | 21 | 24 | 27 | — | — | |||
| For resistive loads, T Ith 1ms | 63 | 126 | 189 | 252 | 315 | 378 | 504 | [A] | 12 | 18 | 18 | 21 | 48 | 60 | |||
| 115.5 | 231 | 346.5 | 462 | 577.5 | — | — | [A] | 3 | 4.5 | 6 | 7.5 | — | — | ||||
| Ue max = 600V | 231 | 462 | — | — | — | — | — | [A] | 0.75 | 1.12 | 1.05 | 1.2 | — | — | |||
| 462 | — | — | — | — | — | — | [A] | 0.52 | 0.78 | 0.47 | 0.75 | — | — | ||||
| Rated current Ie | |||||||||||||||||
| Rated voltage [V] | 24 | 48 | 72 | 96 | 120 | 144 | 192 | [A] | 8 | 10 | 12 | 14 | 16 | 16 | |||
| 30 | 60 | 90 | 120 | 150 | 180 | 240 | [A] | 4.5 | 5.5 | 7 | 8 | — | — | ||||
| For inductive loads T = 50 ms | 48 | 96 | 144 | 192 | 240 | 288 | 384 | [A] | 1.5 | 2 | 2.5 | 3 | 8 | 8 | |||
| Rated voltage [V] | 60 | 120 | 180 | 240 | 300 | 360 | 450 | [A] | 1 | 1.2 | 1.5 | 1.8 | 4.8 | 4.8 | |||
| 110 | 220 | 330 | 440 | 550 | 660 | — | [A] | 0.4 | 0.5 | 0.6 | 0.7 | 2 | 2 | ||||
| 220 | — | — | — | — | — | — | [A] | — | — | — | — | 0.6 | 0.6 | ||||
| Rated making/breaking capacity (= 1.1 x Ie) | |||||||||||||||||
| 1.1 x Rated voltage [V] | 26.4 | 52.8 | 79.2 | 105.6 | 132 | 158.4 | 184.8 | [A] | 8.8 | 11 | 13.2 | 1.54 | — | 17.6 | |||
| 33 | 66 | 99 | 132 | 165 | 198 | 231 | [A] | 4.95 | 6.05 | 7.7 | 8.8 | — | — | ||||
| For inductive loads T = 50 ms | 52.8 | 105.6 | 158.4 | 211.2 | 264 | 316.8 | 369.6 | [A] | 1.65 | 2.2 | 2.75 | 3.3 | 8.8 | 8.8 |
|||
| Ue max = 600V | 66 | 132 | 198 | 264 | 330 | 396 | 462 | [A] | 1.1 | 1.32 | 1.65 | 1.98 | 5.28 | 5.28 |
|||
| 121 | 242 | 363 | 484 | 605 | — | — | [A] | 4.95 | 6.05 | 7.7 | 8.8 | 2.2 | 2.2 | ||||
| Power Lost | [W] | 0.3 | 0.5 | 0.6 | 0.9 | 0.8 | 1.4 | ||||||||||
| Rated power | |||||||||||||||||
| Pe | Contacts in series | ||||||||||||||||
| Rated voltage [V] DC-23A, DC-3, DC-5 For inductive loads, T £1 ms |
24 | 1 | [kW] | 0.12 | 0.15 | 0.20 | 0.25 | 0.30 | 0.30 | ||||||||
| 24 | 2 | [kW] | 0.20 | 0.25 | 0.30 | 0.37 | — | — | |||||||||
| 48 | 2 | [kW] | 0.25 | 0.30 | 0.37 | 0.50 | 0.50 | 0.50 | |||||||||
| 48 | 3 | [kW] | 0.30 | 0.37 | 0.50 | 0.75 | — | — | |||||||||
| 60 | 2 | [kW] | 0.25 | 0.30 | 0.37 | 0.50 | 1.00 | 1.00 | |||||||||
| 60 | 4 | [kW] | 0.37 | 0.50 | 0.75 | 1.00 | — | — | |||||||||
| 110 | 4 | [kW] | 0.50 | 0.75 | 1.00 | 1.20 | — | — | |||||||||
| 110 | 6 | [kW] | 1.00 | 1.20 | 1.40 | 1.60 | — | — | |||||||||
| 220 | 4 | [kW] | 0.37 | 0.50 | 0.75 | 1.00 | — | — | |||||||||
| 220 | 6 | [kW] | 1.00 | 1.20 | 1.40 | 1.50 | — | — | |||||||||
| ⋆ See standards compliance listed on page IEC 60947-3 Low-voltage switchgear and control gear part 3 UL 508 CSA: C22.2 No. 14. |
|||||||||||||||||
| Performance Data, Continued | 12 A | 16 A | 20 A | 25 A | 32 A | 40 A | ||||||
| IEC Applications, Continued | ||||||||||||
| Rated making/breaking capacity (= 4 x Ie) | Contacts in series | |||||||||||
| Rated Voltage [V] | 25.2 25.2 50.4 50.4 63 63 115.5 115.5 231 231 |
1 2 2 3 2 4 4 6 4 6 |
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A] |
20.0 33.3 21.0 25.0 16.6 24.6 18.1 36.4 6.7 18.1 |
25.0 41.6 25.0 30.8 20.0 33.3 27.2 43.6 9.1 21.8 |
33.3 50.0 30.8 42.0 24.6 50.0 36.4 51.0 13.6 25.2 |
41.6 61.6 41.6 62.4 33.2 66.4 44.0 58.2 18.2 27.2 |
50.0 — 41.6 — 66.6 — — — — — |
50.0 — 41.6 — 66.6 — — — — — |
|||
| DC-23A, DC-3, DC-5 | ||||||||||||
| For inductive loads, T £ 7.5 ms | ||||||||||||
| Rated breaking capacity | at 220V 0.45 [cos j] at 380V 0.45 [cos j] at 660V 0.45[cos j] |
[A] [A] [A] |
72 72 53 |
96 96 72 |
128 128 86 |
176 176 112 |
296 280 196 |
296 336 196 |
||||
| Rated power Pe⋆ | IEC-947 | |||||||||||
| AC-2 | Slip-ring motors: starting, reversing and electric braking; star/delta starting |
3-phase 3-pole |
240V 380V 415V 440V 500V 660V |
[kW] [kW] [kW] [kW] [kW] [kW] |
3 5.5 5.5 5.5 7.5 7.5 |
4 7.5 7.5 7.5 10 10 |
5.5 9 9 9 11 11 |
5.5 13 13 13 15 15 |
— — — — — — |
— — — — — — |
||
| AC-3 | Squirrel-cage motors: starting and stopping of running motors |
IEC-947 | ||||||||||
| 3-phase 3-pole |
220…240V 380…440V 500V 660V |
[kW] [kW] [kW] [kW] |
2.2 4 5.5 5.5 |
3 5.5 7.5 7.5 |
4.5 7.5 10 8 |
5.5 11 13 11 |
7.5 15 — 18.5 |
7.5 18.5 — 18.5 |
||||
| 1-phase 2-pole |
110V 220…240V 380…440V |
[kW] [kW] [kW] |
0.75 1.3 2.2 |
1.1 2.2 3.7 |
1.2 2.5 4.5 |
1.6 3.2 5.5 |
— 4 8 |
— 4 16 |
||||
| AC-4 | Squirrel-cage motors: starting, reversing, electric braking, inching |
IEC-947 | ||||||||||
| 3-phase 3-pole |
220…240V 380…415V 440…550V |
[kW] [kW] [kW] |
0.75 1.5 1.5 |
1.5 2.2 2.2 |
3 3.7 3.7 |
4 5.5 5.5 |
5.5 7.5 7.5 |
5.5 7.5 11 |
||||
| 1-phase 2-pole |
110V 240V 380V 440V |
[kW] [kW] [kW] [kW] |
0.18 0.37 0.75 0.75 |
0.37 0.75 1.1 1.1 |
0.55 1.5 1.8 1.8 |
0.75 2.2 3 3 |
— — — — |
— — — — |
||||
| ⋆ See standards compliance listed on IEC 60947-3 Low-voltage switchgear and control gear part 3 UL 508 CSA: C22.2 No. 14. |
||||||||||||
| Performance Data, Continued | 12 A | 16 A | 20 A | 25 A | 32 A | 40 A | |||||
| IEC Applications, Continued | |||||||||||
| AC-23A | Occasional switching of motors and other highly inductive loads (criterion for selecting main switches) |
IEC-947 3-phase 3-pole |
220…240V 380…440V 500V 660V |
[kW] [kW] [kW] [kW] |
2.2 4 5.5 5.5 |
3 5.5 7.5 7.5 |
4.5 7.5 10 8 |
5.5 11 13 11 |
11 18.5 — 22 |
11 22 — 22 |
|
| 1-phase 2-pole |
110V 220…240V 380…440V |
[kW] [kW] [kW] |
0.75 1.3 2.2 |
1.1 2.2 3.7 |
1.2 2.5 4.5 |
1.6 3.2 5.5 |
— 5.5 11 |
— 5.5 11 |
|||
| Short-circuit ratings | |||||||||||
| Rated short-time current (1s) Strongest series fuse, not in enclosure Conditional rated short-circuit |
(gL characteristic) | [kArms] [A] [kA] |
0.48 20⋆ 6 |
0.48 20⋆ 6 |
0.6 20⋆ 5 |
0.75 25⋆ 5 |
0.8 35 5 |
0.8 40 5 |
|||
| Switch Rate | electrical | [ops/h] | 120 | 120 | 120 | 120 | 120 | 120 | |||
| CSA and UL Applications | |||||||||||
| Rated Voltage Ue | [V AC] | 600 | 600 | 600 | 600 | 600 | 600 | ||||
| Ampere Rating |
Pilot Duty General Use |
Contact class Non-inductive or slightly inductive load |
[A] | A600 12 |
A600 16 |
— 20 |
— 25 |
— 32 |
— 40 |
||
| Rated power Pe§ | UL (CSA) | (FLA) | (FLA) | (FLA) | (FLA) | ||||||
| Standard motor DOL rating (similar to AC-3) |
3-phase 3-pole |
120V 240V 480V 600V |
[Hp] [Hp] [Hp] [Hp] |
1 (7.2) 2 (6.8) 5 (7.6) 5 (6.1) |
1.5 (12) 3 (9.6) 7.5 (11) 7.5 (9) |
2 (13.6) 4 (12.4) 8 (11.6) 10 (11) |
3 (19.2) 6 (18) 12 (17) 15 (17) |
5 (30.4) 7.5 (22) 20 (27) 20 (22) |
5 (30.4) 10 (28) 25 (34) 25 (27) |
||
| 1-phase 2-pole |
120V 240V 480V 600V |
[Hp] [Hp] [Hp] [Hp] |
0.5 (9.8) 1 (8.0) 2 (6.0) 3 (6.8) |
.75 (13.8) 1.5 (10.0) 3 (8.5) 3 (6.8) |
1 (16) 2 (12) 4 (11.2) 5 (11.2) |
1.5 (20) 3 (17) 6 (17) 7.5 (16) |
2 (24) 5 (28) 7.5 (21) 10 (20) |
2 (24) 5 (28) 10 (26) 15 (27) |
|||
| Heavy motor load, reversing Rating (similar to AC-4) Max. back-up fuse |
3-phase 3-pole (gG characteristic) |
120V 240V |
[Hp] [Hp] [A] |
— — 35 |
— — 55 |
— — 60 |
— — 80 |
||||
| Short Circuit Ratings |
Maximum Short Circuit Prospective Fault Current Maximum Fuse Size |
[kA] [A] |
5 35 |
5 55 |
5 60 |
5 80 |
|||||
| Switching Rate | electrical | [ops/h] | 120 | 120 | 120 | 120 | 120 | 120 | |||
Mechanical Data
| Performance Data | 12/16 A | 20/25 A | 32/40 A | ||
| Protection class acc. to IEC 529 | Handles Switch Bodies |
IP66 IP20 |
IP66 IP20 |
IP66 IP20 |
|
| Mechanical Endurance | [mil.ops] | 1 | 1 | 1 | |
| Switching rate | mechanical | [ops/h] | 1200 | 1200 | 1200 |
| Maximum Wire Gauges | |||||
| rigid wire fine strands |
AWG [mm2] AWG [mm2] |
(2)18…12 (2)1…2.5 (2)18…12 (2)1…2.5 |
(2)16…10 (2)1.5…6 (2)16…10 (2)1.5…4 |
(2)12…8 (2)4…10 (2)14…10 (2)2.5…6 |
|
Environmental Data
| Performance Data | 12/16/20/25 A | 32/40 A | |
| Ambient temperature | |||
| Operation | -25…+60 °C (-13…+140 °F) |
-25…+60 °C (-13…+140 °F) |
|
| Storage | -40…+80 °C (-40…+176 °F) |
-40…+80 °C (-40…+176 °F) |
|
| ⋆ Does not apply to switches in enclosure. | |||
| Suitable for switching off-load (AC-20) above 660V, but only up to 660V for switches with screws at the rear. | |||
| § See standards compliance listed on page IEC 60947-3 Low-voltage switchgear and control gear part 3 UL 508 CSA: C22.2 No. 14. |
|||
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 194L-C… for Central Fixing (194L-HC…)
|
| Cat. No. | L | ||||
| No. of Contacts | |||||
| 1…2 | 3…4 | 5…6 | 7…8 | 9…10 | |
| 194L-C32/40... | 86 (3-25/64) | 103.5 (4-5/64) | 121 (4-49/64) | 138.5 (5-29/64) | 156 (6-9/64) |
Cat. No. 194L… for Front (Door) Installation
|
Mounting Dimensions
|
|
| Cat. No. | L | ||||
| No. of Contacts | |||||
| 1…2 | 3…4 | 5…6 | 7…8 | 9…10 | |
| 194L-E12/16... | 44 (1-47/64) | 54 (2-1/8) | 64 (2-33/64) | 74 (2-29/32) | 84 (3-5/16) |
| 194L-E20/25... | 44.5 (1-3/4) | 57 (2-1/4) | 69.5 (2-3/4) | 82 (3-15/64) | 94.5 (3-23/32) |
| 194L-E32/40... | 43 (1-11/16) | 58.5 (2-5/16) | 76 (2-63/64) | 93.5 (3-11/16) | 111 (4-3/8) |
Control Knob
| Cat. No. | P | Q |
| 194L-HE4A... | 28 (1-7/64) | 48 (1-57/64) x 48 (1-57/64) |
| 194L-HE4I... | ||
| 194L-HE4S... | 48 (1-57/64) x 62 (2-7/16) | |
| 194L-HE6A... | 64 (2-33/64) x 64 (2-33/64) | |
| 194L-HE6I... | ||
| 194L-HE6S... | 64 (2-33/64) x 78 (3-5/64) | |
| 194L-HE6N... | 67 (2-41/64) x 67 (2-41/64) | |
| 194L-HE6G... | 34 (1-11/32) | |
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 194L-A… for Base/DIN Rail Installation
|
| Cat. No. | L ⋆ | |||
| No. of Contacts | ||||
| 1…2 | 3…4 | 5…6 | 7…8 | |
| 194L-A12/16... | 58 (2-9/32) | 68 (2-11/16) | 78 (3-5/64) | 88 (3-15/32) |
| 194L-A20/25... | 58 (2-9/32) | 71.5 (2-13/16) | 84 (3-5/16) | 96.5 (3-51/64) |
| 194L-A32/40... | 67.5 (2-21/32) | 85 (3-11/32) | 102.5 (4-1/32) | 120 (4-47/64) |
Control Knob
| Cat. No. | P | B | Q |
| 194L-HE4A… | 28 (1-7/64) | 36 (1-27/64) | 48 (1-57/64) x 48 (1-57/64) |
| 194L-HE4I… | |||
| 194L-HE4S… | 48 (1-57/64) x 62 (2-7/16) | ||
| 194L-HE6A… | 48 (1-57/64) | 64 (2-33/64) x 64 (2-33/64) | |
| 194L-HE6I… | |||
| 194L-HE6S… | 64 (2-33/64) x 78 (3-5/64) | ||
| 194L-HE6N… | 34 (1-11/32) | 67 (2-41/64) x 67 (2-41/64) | |
| 194L-HE6G… | |||
| ⋆ With DIN 46 277 (35) Rail + 2.5 mm (7/64) | |||
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 194L-A… With Shaft Extension Cat. No. 194L-G2853
|
| No. of Extensions | Cat. No. 194L-A12/16... 10mm (0.39) | Cat. No. 194L-A20/25... 12.5mm (0.49) | Cat. No. 194L-A32/40 | |||||||||
| L | ||||||||||||
| No. of Contacts | ||||||||||||
| 1…2 | 3…4 | 5…6 | 7…8 | 1…2 | 3…4 | 5…6 | 7…8 | 1…2 | 3…4 | 5…6 | 7…8 | |
| With 1 extension | 82 (3-15/64) |
92 (3-5/8) |
102 (4-1/64) |
112 (4-13/32) |
83 (3-17/64) |
95.5 (3-49/64) |
108 (4-1/4) |
120.5 (4-3/4) |
91.5 (3-15/64) |
108 (4-1/4) |
126.5 (5-63/64) |
144 (6-43/64) |
| With 2 extensions | 106 (4-11/64) |
116 (4-37/64) |
126 (4-31/32) |
136 (5-23/64) |
107 (4-7/32) |
119.5 (4-45/64) |
132 (5-13/64) |
144.5 (5-11/16) |
115.5 (5-35/64) |
133 (5-15/64) |
150.5 (6-5/16) |
168 (7-5/8) |
| With 3 extensions | 130 (5-1/8) |
140 (5-33/64) |
150 (5-29/32) |
160 (6-19/64) |
131 (5-5/32) |
143.5 (5-21/32) |
156 (6-9/64) |
168.5 (6-5/8) |
135.5 (5-11/32) |
157 (6-3/16) |
174.5 (7-7/8) |
182 (8-9/16) |
| With 4 ⋆ extensions | 154 (6-1/16) |
164 (6-15/32) |
174 (6-55/64) |
184 (7-15/64) |
155 (6-7/64) |
167.5 (6-19/32) |
180 (7-3/32) |
192.5 (7-37/64) |
163.5 (6-7/16) |
181 (7-1/8) |
198.5 (8-53/64) |
216 (9-33/64) |
| With 5 ⋆ extensions | 178 (7-1/64) |
188 (7-13/32) |
198 (7-51/64) |
208 (8-3/16) |
179 (7-3/64) |
191.5 (7-35/64) |
204 (8-1/32) |
216.5 (8-33/64) |
187.5 (7-3/8) |
205 (8-5/64) |
222.5 (9-49/64) |
240 (9-29/64) |
| With 6 ⋆ extensions | 202 (7-61/64) |
212 (8-23/64) |
222 (8-3/4) |
232 (9-1/8) |
203 (7-63/64) |
215.5 (8-31/64) |
228 (8-63/64) |
240.5 (9-15/32) |
211.5 (8-21/64) |
229 (12) |
246.5 (10-23/32) |
264 (10-13/32) |
Control Knob
| Cat. No. | Q | B |
| 194L-HE4A… | 48 (1-57/64) x 48 (1-57/64) | 36 (1-27/64) |
| 194L-HE4I… | ||
| 194L-HE6A… | 64 (2-33/64) x 64 (2-33/64) | 48 (1-57/64) |
| 194L-HE6I… | ||
| 194L-HE6N… | 67 (2-41/64) x 67 (2-41/64) | |
| 194L-HE6G… | ||
| ⋆ When more than four modules are used, attach the first one to the switch body using the screws supplied with the extension (Cat. No. 194L-G2853). Mounting on DIN 46 277 (35) Rails. |
||
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. 194L-A… With Metal Shafts
|
| Cat. No. | A |
| 194L-G3393… | 110 (4-21/64)…235(9-1/4) |
| 194L-G3394… | 230 (9-1/16)…350 (13-25/32) |
| Cat. No. | L⋆ | |||
| No. of Contacts | ||||
| 1…2 | 3…4 | 5…6 | 7…8 | |
| 194L-A12/16... | 54 (2-1/8) | 64 (2-33/64) | 74 (2-29/32) | 84 (3-5/16) |
| 194L-A20/25... | 55 (2-11/64) | 67.5 (2-21/32) | 80 (3-5/32) | 92.5 (3-41/64) |
| 194L-A32/40... | 63.5 (2-31/64) | 81 (3-3/16) | 88.5 (3-7/8) | 116 (4-9/16) |
Modular Shaft Extensions (Cat. No. 194L-G2853)
Select No. of Extension Modules and Shaft for use with enclosures.
| No. of Extension Modules | Required End Shaft | Enclosure Mounting Depth§ | |
| Cat. No. 194L-A12/16… | Cat. No. 194L-A20/25… | ||
| 0 | 44 (1-47/64) ♣ | 71.5…77.5 (2-13/16…3-1/16) | 75…80.5 (2-61/64…3-11/64) |
| 52 (2-3/64) | 77…87 (3-1/32…3-27/64) | 80…90 (3-5/32…3-35/64) | |
| 57 (2-1/4) | 82…92 (3-15/64…3-5/8) | 85…95 (3-11/32…3-3/4) | |
| 1 | 44 (1-47/64) ♣ | 95.5…101.5 (3-49/64…4) | 99…105 (3-29/32…4-9/64) |
| 52 (2-3/64) | 97.5…111 (3-27/32…4-3/8) | 101…114.5 (3-63/64…4-33/64) | |
| 57 (2-1/4) | 102.5…116 (4-3/64…4-37/64) | 106…119.5 (4-11/64…4-45/64) | |
| 2 | 44 (1-47/64) ♣ | 119.5…125.5 (4-45/64…4-61/64) | 123…129 (4-27/32…5-5/64) |
| 52 (2-3/64) | 121.5…135 (4-51/64…5-5/16) | 125…138.5 (4-59/64…5-29/64) | |
| 57 (2-1/4) | 126.5…140 (4-63/64…5-33/64) | 130…143.5 (5-1/8…5-21/32) | |
| 3 | 44 (1-47/64) ♣ | 143.5…149.5 (5-21/32…5-57/64) | 147…153 (5-51/64…6-1/32) |
| 52 (2-3/64) | 145.5…159 (5-47/64…6-17/64) | 149…162.5 (5-7/8…6-13/32) | |
| 57 (2-1/4) | 150.5…164 (5-15/16…6-15/32) | 154…167.5 (6-1/16…6-19/32) | |
| 4 | 44 (1-47/64) ♣ | 167.5…173.5 (6-19/32…6-27/32) | 171…177 (6-47/64…6-31/32) |
| 52 (2-3/64) | 169.5…183 (6-43/64…7-13/64) | 173…186.5 (6-13/16…7-11/32) | |
| 57 (2-1/4) | 174.5…188 (6-7/8…7-13/32) | 178…191.5 (7-1/64…7-35/64) | |
| 5 | 44 (1-47/64) ♣ | 191.5…197.5 (7-35/64…7-25/32) | 195…201 (7-43/64…7-59/64) |
| 52 (2-3/64) | 193.5…207 (7-5/8…8-5/32) | 197…210.5 (7-49/64…8-19/64) | |
| 57 (2-1/4) | 198.5…212 (7-53/64…8-23/64) | 202…215.5 (7-61/64…8-31/64) | |
| 6 | 44 (1-47/64) ♣ | 215.5…221.5 (8-31/64…8-23/32) | 219…225 (8-5/8…8-55/64) |
| 52 (2-3/64) | 217.5…231 (8-37/64…9-3/32) | 221…234.5 (8-45/64…9-15/64) | |
| 57 (2-1/4) | 222.5…236 (8-49/64…9-19/64) | 226…239.5 (8-29/32…9-7/16) | |
| ⋆ When more than 4 modules are used, attach the first one to the switch body using the screws supplied with the extension (Cat. No. 194L-G2853). | |||
| § For DIN Rail-mounted devices, remember to deduct the offset distance provided by the rail. For example, deduct 2.5 mm (7/64 in.) from the mounting depth for Bulletin 194L switch body mounted on DIN 46277 rail. | |||
| ♣ One 44 mm (1-47/64 in) end shaft is supplied with all Bulletin 194L Switch Bodies. | |||
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Enclosure
Cat. No. 194L-G3572…Cat. No. 194L-G3579
|
|